SPEC 26341

HVTECK CU 3/C 175NLEPR TS PVC AIA PVC 15kV 100% CSA

3 Conductor, 175 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 100% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Conductor Shield:Semi-conducting cross-linked copolymer
  3. Insulation:175 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 100% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
  6. Filler:Interstices filled with non-hydroscoping/non-wicking fillers
  7. Grounding Conductor:Class B compressed stranded bare copper ground per ASTM B3 and ASTM B8
  8. Binder:Polypropylene tape
  9. Inner Jacket:PVC inner jacket
  10. Armour:Aluminum Interlocked Armour (AIA)
  11. Overall Jacket:Red Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 15kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 3/C [#AWG or #kcmil] CU 175 NLEPR AIA 15kV 100% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldGroundInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.inchinchmilinchNo. x AWGmilinchmilinchlb/1000ftlb/1000ftinch
    TBA270.2830.6711750.7311x61102.135602.25588621253
    TBA1190.3220.711750.771x61102.219602.339105623693
    TBA1/0190.3620.751750.811x61102.306752.456127227273
    5837522/0190.4050.7941750.8541x41102.458752.608159937563.5
    TBA3/0190.4560.8441750.9041x41102.509752.659192535663.5
    TBA4/0190.5120.91750.961x41102.63752.78234841003.5
    TBA250370.5580.9541751.0141x41102.746752.896272245933.5
    TBA350370.6611.0571751.1171x31102.969753.119371857954
    TBA500370.7891.1851751.2451x31253.275853.445515375564.5
    TBA750610.9681.3741751.4341x21253.683853.8537581103985
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    215.815920.1620.2210.0380.0280.588+j0.5020.221+j0.0452296172201
    116.420080.1280.1750.0350.0260.544+j0.4820.175+j0.0432417197228
    1/017.225340.1020.1390.0330.0250.509+j0.4630.139+j0.0412541225257
    2/018.331940.0820.1120.030.0230.483+j0.4440.112+j0.0402677260292
    3/018.640270.0640.0870.0280.0220.458+j0.4230.087+j0.0382832297330
    4/019.550780.0510.070.0260.020.440+j0.4010.070+j0.0373005342372
    25020.360000.0430.0590.0240.020.427+j0.3810.059+j0.0363173376410
    35021.884000.0310.0430.0210.0180.406+j0.3460.043+j0.0343492460487
    50024.1120000.0210.030.0180.0160.384+j0.3090.030+j0.0333888556573
    75027180000.0140.0210.0150.0150.361+j0.2630.021+j0.0314474678668
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3/C in air copper and aluminum: D17N
    3/C direct buried copper and aluminum: D17E
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldGroundInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.mmmmmmmmNo. x AWGmmmmmmmmkg/kmkg/kminch
    TBA277.1917.044.4418.571x62.7954.231.5257.28131931623
    TBA1198.1818.034.4419.561x62.7956.361.5259.41157235253
    TBA1/0199.1919.054.4420.571x62.7958.571.9162.38189340583
    5837522/01910.2920.174.4421.691x42.7962.431.9166.24238055903.5
    TBA3/01911.5821.444.4422.961x42.7963.731.9167.54286553073.5
    TBA4/01913.0022.864.4424.381x42.7966.801.9170.61349461013.5
    TBA2503714.1724.234.4425.761x42.7969.751.9173.56405168353.5
    TBA3503716.7926.854.4428.371x32.7975.411.9179.22553386244
    TBA5003720.0430.104.4431.621x33.1883.182.1687.507669112454.5
    TBA7506124.5934.904.4436.421x23.1893.552.1697.8711282154745
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    2401.3270840.53150.730.01160.09190.588+j0.5020.221+j0.0452296172201
    1416.5689360.41990.570.01070.08530.544+j0.4820.175+j0.0432417197228
    1/0436.88112760.33460.460.01010.08200.509+j0.4630.139+j0.0412541225257
    2/0464.82142130.26900.370.00910.07550.483+j0.4440.112+j0.0402677260292
    3/0472.44179200.21000.290.00850.07220.458+j0.4230.087+j0.0382832297330
    4/0495.30225970.16730.230.00790.06560.440+j0.4010.070+j0.0373005342372
    250515.62267000.14110.190.00730.06560.427+j0.3810.059+j0.0363173376410
    350553.72373800.10170.140.00640.05910.406+j0.3460.043+j0.0343492460487
    500612.14534000.06890.100.00550.05250.384+j0.3090.030+j0.0333888556573
    750685.80801000.04590.070.00460.04920.361+j0.2630.021+j0.0314474678668
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3/C in air copper and aluminum: D17N
    3/C direct buried copper and aluminum: D17E

    Revision: 1.000.000

    Updated On: Dec. 31, 2024, 11:07 p.m. UTC