SPEC 26332
HVTECK AL 1/C 220TRXLPE TS PVC AIA PVC 15kV 133% CSA
Single Conductor, 220 Mils Tree Retardant Cross Linked Polyethylene, 133% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

Construction:
- Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
- Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
- Insulation:220 Mils Tree Retardant Cross Linked Polyethylene 133% insulation level
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
- Inner Jacket:PVC inner jacket
- Armour:Aluminum Interlocked Armour (AIA)
- Overall Jacket:Red Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire's 15kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.
Specifications:
Sample Print Legend:
(CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CPT AL 220 TRXLPE AIA 15kV 133% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
Table 1 – Weights and Measurements
| Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Conduit Size* |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | inch | inch | mil | inch | mil | inch | mil | inch | lb/1000ft | lb/1000ft | inch |
| 2 | 7 | 0.268 | 0.746 | 220 | 0.806 | 80 | 1.196 | 50 | 1.296 | 66 | 828 | 3.5 |
| 1 | 19 | 0.299 | 0.777 | 220 | 0.837 | 80 | 1.227 | 50 | 1.327 | 69 | 874 | 3.5 |
| 1/0 | 19 | 0.336 | 0.814 | 220 | 0.874 | 80 | 1.264 | 50 | 1.364 | 72 | 930 | 3.5 |
| 2/0 | 19 | 0.376 | 0.854 | 220 | 0.914 | 80 | 1.304 | 50 | 1.404 | 75 | 996 | 3.5 |
| 3/0 | 19 | 0.423 | 0.901 | 220 | 0.961 | 80 | 1.351 | 50 | 1.451 | 79 | 1075 | 3.5 |
| 4/0 | 19 | 0.475 | 0.953 | 220 | 1.013 | 80 | 1.403 | 50 | 1.503 | 83 | 1167 | 4 |
| 250 | 37 | 0.52 | 1.006 | 220 | 1.066 | 80 | 1.456 | 50 | 1.556 | 88 | 1259 | 4 |
| 350 | 37 | 0.616 | 1.102 | 220 | 1.162 | 80 | 1.652 | 60 | 1.772 | 96 | 1630 | 4.5 |
| 500 | 37 | 0.736 | 1.222 | 220 | 1.282 | 80 | 1.772 | 60 | 1.892 | 105 | 1904 | 5 |
| 750 | 61 | 0.908 | 1.404 | 220 | 1.464 | 80 | 1.954 | 60 | 2.074 | 120 | 2348 | 5.5 |
| 1000 | 61 | 1.117 | 1.613 | 220 | 1.673 | 110 | 2.223 | 60 | 2.343 | 138 | 2937 | 6 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Strand count meets minimum number per ASTM
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 2 | 9.1 | 398 | 0.266 | 0.365 | 0.061 | 0.058 | 0.718+j0.465 | 0.366+j0.063 | 2528 | 169 | 176 |
| 1 | 9.3 | 502 | 0.211 | 0.289 | 0.057 | 0.056 | 0.643+j0.450 | 0.290+j0.060 | 2624 | 194 | 198 |
| 1/0 | 9.5 | 633 | 0.167 | 0.229 | 0.053 | 0.054 | 0.584+j0.434 | 0.230+j0.058 | 2739 | 222 | 223 |
| 2/0 | 9.8 | 798 | 0.133 | 0.182 | 0.049 | 0.052 | 0.537+j0.418 | 0.183+j0.056 | 2863 | 255 | 250 |
| 3/0 | 10.2 | 1006 | 0.105 | 0.144 | 0.046 | 0.05 | 0.499+j0.400 | 0.145+j0.054 | 3009 | 290 | 278 |
| 4/0 | 10.5 | 1269 | 0.084 | 0.115 | 0.042 | 0.048 | 0.469+j0.381 | 0.116+j0.052 | 3170 | 329 | 309 |
| 250 | 10.9 | 1500 | 0.07 | 0.096 | 0.039 | 0.047 | 0.449+j0.364 | 0.097+j0.051 | 3334 | 370 | 347 |
| 350 | 12.4 | 2100 | 0.051 | 0.07 | 0.035 | 0.046 | 0.417+j0.334 | 0.071+j0.050 | 3631 | 446 | 402 |
| 500 | 13.2 | 3000 | 0.036 | 0.05 | 0.03 | 0.043 | 0.391+j0.301 | 0.051+j0.047 | 4003 | 533 | 451 |
| 750 | 14.5 | 4500 | 0.023 | 0.033 | 0.026 | 0.041 | 0.361+j0.259 | 0.035+j0.044 | 4567 | 631 | 500 |
| 1000 | 16.4 | 6000 | 0.017 | 0.025 | 0.022 | 0.039 | 0.337+j0.222 | 0.027+j0.044 | 5215 | 707 | 539 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
Table 3 – Weights and Measurements (Metric)
| Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Conduit Size* |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | mm | mm | mm | mm | mm | mm | mm | mm | kg/km | kg/km | inch |
| 2 | 7 | 6.81 | 18.95 | 5.59 | 20.47 | 2.03 | 30.38 | 1.27 | 32.92 | 98 | 1232 | 3.5 |
| 1 | 19 | 7.59 | 19.74 | 5.59 | 21.26 | 2.03 | 31.17 | 1.27 | 33.71 | 103 | 1301 | 3.5 |
| 1/0 | 19 | 8.53 | 20.68 | 5.59 | 22.20 | 2.03 | 32.11 | 1.27 | 34.65 | 107 | 1384 | 3.5 |
| 2/0 | 19 | 9.55 | 21.69 | 5.59 | 23.22 | 2.03 | 33.12 | 1.27 | 35.66 | 112 | 1482 | 3.5 |
| 3/0 | 19 | 10.74 | 22.89 | 5.59 | 24.41 | 2.03 | 34.32 | 1.27 | 36.86 | 118 | 1600 | 3.5 |
| 4/0 | 19 | 12.07 | 24.21 | 5.59 | 25.73 | 2.03 | 35.64 | 1.27 | 38.18 | 124 | 1737 | 4 |
| 250 | 37 | 13.21 | 25.55 | 5.59 | 27.08 | 2.03 | 36.98 | 1.27 | 39.52 | 131 | 1874 | 4 |
| 350 | 37 | 15.65 | 27.99 | 5.59 | 29.51 | 2.03 | 41.96 | 1.52 | 45.01 | 143 | 2426 | 4.5 |
| 500 | 37 | 18.69 | 31.04 | 5.59 | 32.56 | 2.03 | 45.01 | 1.52 | 48.06 | 156 | 2833 | 5 |
| 750 | 61 | 23.06 | 35.66 | 5.59 | 37.19 | 2.03 | 49.63 | 1.52 | 52.68 | 179 | 3494 | 5.5 |
| 1000 | 61 | 28.37 | 40.97 | 5.59 | 42.49 | 2.79 | 56.46 | 1.52 | 59.51 | 205 | 4371 | 6 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Strand count meets minimum number per ASTM
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 4 – Electrical and Engineering Data (Metric)
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | mm | newton | Ω/km | Ω/km | MΩ*km | Ω/km | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 2 | 231.14 | 1771 | 0.8727 | 1.20 | 0.0186 | 0.1903 | 0.718+j0.465 | 0.366+j0.063 | 2528 | 169 | 176 |
| 1 | 236.22 | 2234 | 0.6923 | 0.95 | 0.0174 | 0.1837 | 0.643+j0.450 | 0.290+j0.060 | 2624 | 194 | 198 |
| 1/0 | 241.30 | 2817 | 0.5479 | 0.75 | 0.0162 | 0.1772 | 0.584+j0.434 | 0.230+j0.058 | 2739 | 222 | 223 |
| 2/0 | 248.92 | 3551 | 0.4364 | 0.60 | 0.0149 | 0.1706 | 0.537+j0.418 | 0.183+j0.056 | 2863 | 255 | 250 |
| 3/0 | 259.08 | 4477 | 0.3445 | 0.47 | 0.0140 | 0.1640 | 0.499+j0.400 | 0.145+j0.054 | 3009 | 290 | 278 |
| 4/0 | 266.70 | 5647 | 0.2756 | 0.38 | 0.0128 | 0.1575 | 0.469+j0.381 | 0.116+j0.052 | 3170 | 329 | 309 |
| 250 | 276.86 | 6675 | 0.2297 | 0.31 | 0.0119 | 0.1542 | 0.449+j0.364 | 0.097+j0.051 | 3334 | 370 | 347 |
| 350 | 314.96 | 9345 | 0.1673 | 0.23 | 0.0107 | 0.1509 | 0.417+j0.334 | 0.071+j0.050 | 3631 | 446 | 402 |
| 500 | 335.28 | 13350 | 0.1181 | 0.16 | 0.0091 | 0.1411 | 0.391+j0.301 | 0.051+j0.047 | 4003 | 533 | 451 |
| 750 | 368.30 | 20025 | 0.0755 | 0.11 | 0.0079 | 0.1345 | 0.361+j0.259 | 0.035+j0.044 | 4567 | 631 | 500 |
| 1000 | 416.56 | 26700 | 0.0558 | 0.08 | 0.0067 | 0.1280 | 0.337+j0.222 | 0.027+j0.044 | 5215 | 707 | 539 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
Revision: 1.000.000
Updated On: Dec. 31, 2024, 11:07 p.m. UTC

