SPEC 26315
HVTECK CU 1/C 175TRXLPE CB PVC AIA PVC 15kV 100% CSA
Single Conductor, 175 Mils Tree Retardant Cross Linked Polyethylene, 100% Insulation Level, Concentric Bond, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

Construction:
- Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
- Conductor Shield:Semi-conducting cross-linked copolymer
- Insulation:175 Mils Tree Retardant Cross Linked Polyethylene 100% insulation level
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Concentric Shield:Concentrically applied copper bond / shield wires. Complies with greater than the minimum requirement as per Table 44, CSA Standard C68.10 and Table 16A, Canadian Electrical Code Part 1
- Neutral Separator:Mylar tape
- Inner Jacket:PVC inner jacket
- Armour:Aluminum Interlocked Armour (AIA)
- Overall Jacket:Red Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire's 15kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.
Specifications:
Sample Print Legend:
(CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CU 175 TRXLPE AIA 15kV 100% INS LEVEL CB [No. x SIZE] AWG SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
Table 1 – Weights and Measurements
| Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Concentric Neutral | Inner Jacket Thickness | Dia. Over Inner Jacket | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Conduit Size* |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | inch | inch | mil | inch | No. x AWG | mil | inch | inch | mil | inch | lb/1000ft | lb/1000ft | inch |
| 2 | 7 | 0.283 | 0.671 | 175 | 0.731 | 5x12 | 80 | 1.181 | 1.391 | 50 | 1.491 | 346 | 1282 | 4 |
| 1 | 19 | 0.322 | 0.71 | 175 | 0.77 | 7x12 | 80 | 1.22 | 1.43 | 50 | 1.53 | 450 | 1427 | 4 |
| 1/0 | 19 | 0.362 | 0.75 | 175 | 0.81 | 7x12 | 80 | 1.26 | 1.57 | 60 | 1.69 | 522 | 1715 | 4.5 |
| 2/0 | 19 | 0.405 | 0.793 | 175 | 0.853 | 7x12 | 80 | 1.303 | 1.613 | 60 | 1.733 | 610 | 1853 | 4.5 |
| 3/0 | 19 | 0.456 | 0.844 | 175 | 0.904 | 9x12 | 80 | 1.354 | 1.664 | 60 | 1.784 | 755 | 2057 | 4.5 |
| 4/0 | 19 | 0.512 | 0.9 | 175 | 0.96 | 9x12 | 80 | 1.41 | 1.72 | 60 | 1.84 | 895 | 2262 | 5 |
| 250 | 37 | 0.558 | 0.954 | 175 | 1.014 | 11x12 | 80 | 1.464 | 1.774 | 60 | 1.894 | 1060 | 2493 | 5 |
| 350 | 37 | 0.661 | 1.057 | 175 | 1.117 | 13x12 | 80 | 1.567 | 1.877 | 60 | 1.997 | 1431 | 2984 | 5 |
| 500 | 37 | 0.789 | 1.185 | 175 | 1.245 | 17x12 | 110 | 1.755 | 2.065 | 60 | 2.185 | 1972 | 3789 | 5.5 |
| 750 | 61 | 0.968 | 1.374 | 175 | 1.434 | 21x12 | 110 | 1.944 | 2.254 | 75 | 2.404 | 2845 | 4965 | 6.5 |
| 1000 | 61 | 1.117 | 1.523 | 175 | 1.583 | 21x12 | 110 | 2.093 | 2.403 | 75 | 2.553 | 3629 | 5935 | 6.5 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 2 | 10.4 | 530 | 0.162 | 0.221 | 0.05 | 0.06 | 0.520+j0.198 | 0.224+j0.066 | 2770 | 215 | 221 |
| 1 | 10.7 | 669 | 0.128 | 0.175 | 0.046 | 0.058 | 0.419+j0.127 | 0.179+j0.063 | 3879 | 245 | 247 |
| 1/0 | 11.8 | 844 | 0.102 | 0.139 | 0.043 | 0.057 | 0.382+j0.126 | 0.143+j0.062 | 3879 | 278 | 275 |
| 2/0 | 12.1 | 1064 | 0.082 | 0.112 | 0.04 | 0.055 | 0.355+j0.125 | 0.116+j0.060 | 3879 | 317 | 306 |
| 3/0 | 12.5 | 1342 | 0.064 | 0.087 | 0.036 | 0.053 | 0.288+j0.088 | 0.092+j0.058 | 4987 | 357 | 335 |
| 4/0 | 12.9 | 1692 | 0.051 | 0.07 | 0.034 | 0.051 | 0.271+j0.087 | 0.075+j0.056 | 4987 | 404 | 369 |
| 250 | 13.3 | 2000 | 0.043 | 0.059 | 0.031 | 0.05 | 0.229+j0.067 | 0.065+j0.054 | 6095 | 456 | 412 |
| 350 | 14 | 2800 | 0.031 | 0.043 | 0.027 | 0.047 | 0.190+j0.053 | 0.050+j0.051 | 7203 | 537 | 456 |
| 500 | 15.3 | 4000 | 0.021 | 0.03 | 0.024 | 0.045 | 0.145+j0.038 | 0.038+j0.048 | 9420 | 616 | 497 |
| 750 | 16.8 | 6000 | 0.014 | 0.021 | 0.02 | 0.043 | 0.115+j0.030 | 0.030+j0.045 | 11636 | 706 | 551 |
| 1000 | 17.9 | 8000 | 0.011 | 0.018 | 0.018 | 0.041 | 0.112+j0.029 | 0.027+j0.043 | 11636 | 813 | 596 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
Table 3 – Weights and Measurements (Metric)
| Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Concentric Neutral | Inner Jacket Thickness | Dia. Over Inner Jacket | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Conduit Size* |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | mm | mm | mm | mm | No. x AWG | mm | mm | mm | mm | mm | kg/km | kg/km | inch |
| 2 | 7 | 7.19 | 17.04 | 4.44 | 18.57 | 5x12 | 2.03 | 30.00 | 35.33 | 1.27 | 37.87 | 515 | 1908 | 4 |
| 1 | 19 | 8.18 | 18.03 | 4.44 | 19.56 | 7x12 | 2.03 | 30.99 | 36.32 | 1.27 | 38.86 | 670 | 2124 | 4 |
| 1/0 | 19 | 9.19 | 19.05 | 4.44 | 20.57 | 7x12 | 2.03 | 32.00 | 39.88 | 1.52 | 42.93 | 777 | 2552 | 4.5 |
| 2/0 | 19 | 10.29 | 20.14 | 4.44 | 21.67 | 7x12 | 2.03 | 33.10 | 40.97 | 1.52 | 44.02 | 908 | 2758 | 4.5 |
| 3/0 | 19 | 11.58 | 21.44 | 4.44 | 22.96 | 9x12 | 2.03 | 34.39 | 42.27 | 1.52 | 45.31 | 1124 | 3061 | 4.5 |
| 4/0 | 19 | 13.00 | 22.86 | 4.44 | 24.38 | 9x12 | 2.03 | 35.81 | 43.69 | 1.52 | 46.74 | 1332 | 3366 | 5 |
| 250 | 37 | 14.17 | 24.23 | 4.44 | 25.76 | 11x12 | 2.03 | 37.19 | 45.06 | 1.52 | 48.11 | 1577 | 3710 | 5 |
| 350 | 37 | 16.79 | 26.85 | 4.44 | 28.37 | 13x12 | 2.03 | 39.80 | 47.68 | 1.52 | 50.72 | 2130 | 4441 | 5 |
| 500 | 37 | 20.04 | 30.10 | 4.44 | 31.62 | 17x12 | 2.79 | 44.58 | 52.45 | 1.52 | 55.50 | 2935 | 5639 | 5.5 |
| 750 | 61 | 24.59 | 34.90 | 4.44 | 36.42 | 21x12 | 2.79 | 49.38 | 57.25 | 1.91 | 61.06 | 4234 | 7389 | 6.5 |
| 1000 | 61 | 28.37 | 38.68 | 4.44 | 40.21 | 21x12 | 2.79 | 53.16 | 61.04 | 1.91 | 64.85 | 5401 | 8832 | 6.5 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 4 – Electrical and Engineering Data (Metric)
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | mm | newton | Ω/km | Ω/km | MΩ*km | Ω/km | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 2 | 264.16 | 2359 | 0.5315 | 0.73 | 0.0152 | 0.1969 | 0.520+j0.198 | 0.224+j0.066 | 2770 | 215 | 221 |
| 1 | 271.78 | 2977 | 0.4199 | 0.57 | 0.0140 | 0.1903 | 0.419+j0.127 | 0.179+j0.063 | 3879 | 245 | 247 |
| 1/0 | 299.72 | 3756 | 0.3346 | 0.46 | 0.0131 | 0.1870 | 0.382+j0.126 | 0.143+j0.062 | 3879 | 278 | 275 |
| 2/0 | 307.34 | 4735 | 0.2690 | 0.37 | 0.0122 | 0.1804 | 0.355+j0.125 | 0.116+j0.060 | 3879 | 317 | 306 |
| 3/0 | 317.50 | 5972 | 0.2100 | 0.29 | 0.0110 | 0.1739 | 0.288+j0.088 | 0.092+j0.058 | 4987 | 357 | 335 |
| 4/0 | 327.66 | 7529 | 0.1673 | 0.23 | 0.0104 | 0.1673 | 0.271+j0.087 | 0.075+j0.056 | 4987 | 404 | 369 |
| 250 | 337.82 | 8900 | 0.1411 | 0.19 | 0.0094 | 0.1640 | 0.229+j0.067 | 0.065+j0.054 | 6095 | 456 | 412 |
| 350 | 355.60 | 12460 | 0.1017 | 0.14 | 0.0082 | 0.1542 | 0.190+j0.053 | 0.050+j0.051 | 7203 | 537 | 456 |
| 500 | 388.62 | 17800 | 0.0689 | 0.10 | 0.0073 | 0.1476 | 0.145+j0.038 | 0.038+j0.048 | 9420 | 616 | 497 |
| 750 | 426.72 | 26700 | 0.0459 | 0.07 | 0.0061 | 0.1411 | 0.115+j0.030 | 0.030+j0.045 | 11636 | 706 | 551 |
| 1000 | 454.66 | 35600 | 0.0361 | 0.06 | 0.0055 | 0.1345 | 0.112+j0.029 | 0.027+j0.043 | 11636 | 813 | 596 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
Revision: 1.000.000
Updated On: Dec. 31, 2024, 11:07 p.m. UTC

