SPEC 26305

HVTECK CU 1/C 175NLEPR CB PVC AIA PVC 15kV 100% CSA

Single Conductor, 175 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 100% Insulation Level, Concentric Bond, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Conductor Shield:Semi-conducting cross-linked copolymer
  3. Insulation:175 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 100% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Concentric Shield:Concentrically applied copper bond / shield wires. Complies with greater than the minimum requirement as per Table 44, CSA Standard C68.10 and Table 16A, Canadian Electrical Code Part 1
  6. Neutral Separator:Mylar tape
  7. Inner Jacket:PVC inner jacket
  8. Armour:Aluminum Interlocked Armour (AIA)
  9. Overall Jacket:Red Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 15kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CU 175 NLEPR AIA 15kV 100% INS LEVEL CB [No. x SIZE] AWG SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. Weight
    AWG/KcmilNo.inchinchmilinchNo. x AWGmilinchmilinchlb/1000ftlb/1000ft
    270.2820.6701750.7307x14801.350501.450299938
    1190.3220.7101750.77011x14801.390501.4904071077
    1/0190.3610.7491750.80911x14801.429501.5294741175
    2/0190.4050.7931750.85311x14801.473501.5735591295
    3/0190.4560.8441750.90413x14801.524601.6446941502
    4/0190.5120.9001750.96013x14801.580601.7008291683
    250370.5580.9541751.01417x14801.658601.77810011935
    350370.6611.0571751.11721x14801.795601.91513652400
    500370.7891.1851751.24526x14801.923602.04318963132
    750610.9681.3741751.43421x121102.172602.29227534290
    1000611.1171.5231751.58321x121102.321752.47135255277
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    217.45300.1620.2040.0410.0590.561 + j0.4560.205 + j0.0605458215221
    117.96690.1280.1620.0380.0570.520 + j0.4360.163 + j0.0578577245247
    1/018.38440.1020.1280.0350.0550.487 + j0.4180.129 + j0.0558577278275
    2/018.910640.0810.1020.0320.0530.461 + j0.3990.103 + j0.0538577317306
    3/019.713420.0640.0810.0290.0510.438 + j0.3780.082 + j0.05110137357335
    4/020.416920.0510.0650.0270.0490.420 + j0.3570.066 + j0.04910137404369
    25021.320000.0430.0560.0250.0480.408 + j0.3380.057 + j0.04813256456412
    35023.028000.0310.0410.0220.0460.386 + j0.3060.042 + j0.04616376537456
    50024.540000.0220.0300.0190.0440.365 + j0.2710.031 + j0.04420275616497
    75027.560000.0140.0230.0160.0420.341 + j0.2290.024 + j0.04126018706551
    100029.780000.0110.0190.0140.0400.323 + j0.2020.020 + j0.04026018813596
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3-1/C in air copper and aluminum: D17M
    3-1/C direct buried copper and aluminum: D17A
    Table 3 – Weights and Measurements (Metric)
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. Weight
    AWG/KcmilNo.mmmmmmmmNo. x AWGmmmmmmmmkg/kmkg/km
    277.1617.024.4418.547x142.0334.291.2736.834451396
    1198.1818.034.4419.5611x142.0335.311.2737.856061603
    1/0199.1719.024.4420.5511x142.0336.301.2738.847051749
    2/01910.2920.144.4421.6711x142.0337.411.2739.958321927
    3/01911.5821.444.4422.9613x142.0338.711.5241.7610332235
    4/01913.0022.864.4424.3813x142.0340.131.5243.1812342505
    2503714.1724.234.4425.7617x142.0342.111.5245.1614902880
    3503716.7926.854.4428.3721x142.0345.591.5248.6420313572
    5003720.0430.104.4431.6226x142.0348.841.5251.8928224661
    7506124.5934.904.4436.4221x122.7955.171.5258.2240976384
    10006128.3738.684.4440.2121x122.7958.951.9162.7652467853
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    2441.9623590.53150.670.01250.19360.561 + j0.4560.205 + j0.0605458215221
    1454.6629770.41990.530.01160.18700.520 + j0.4360.163 + j0.0578577245247
    1/0464.8237560.33460.420.01070.18040.487 + j0.4180.129 + j0.0558577278275
    2/0480.0647350.26570.330.00980.17390.461 + j0.3990.103 + j0.0538577317306
    3/0500.3859720.21000.270.00880.16730.438 + j0.3780.082 + j0.05110137357335
    4/0518.1675290.16730.210.00820.16080.420 + j0.3570.066 + j0.04910137404369
    250541.0289000.14110.180.00760.15750.408 + j0.3380.057 + j0.04813256456412
    350584.20124600.10170.130.00670.15090.386 + j0.3060.042 + j0.04616376537456
    500622.30178000.07220.100.00580.14440.365 + j0.2710.031 + j0.04420275616497
    750698.50267000.04590.080.00490.13780.341 + j0.2290.024 + j0.04126018706551
    1000754.38356000.03610.060.00430.13120.323 + j0.2020.020 + j0.04026018813596
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3-1/C in air copper and aluminum: D17M
    3-1/C direct buried copper and aluminum: D17A