SPEC 26252

HVTECK CU 3/C 140TRXLPE TS PVC AIA PVC 8kV 133% CSA

3 Conductor, 140 Mils Tree Retardant Cross Linked Polyethylene, 133% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Conductor Shield:Semi-conducting cross-linked copolymer
  3. Insulation:140 Mils Tree Retardant Cross Linked Polyethylene 133% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
  6. Filler:Interstices filled with non-hydroscoping/non-wicking fillers
  7. Grounding Conductor:Class B compressed stranded bare copper ground per ASTM B3 and ASTM B8
  8. Binder:Polypropylene tape
  9. Inner Jacket:PVC inner jacket
  10. Armour:Aluminum Interlocked Armour (AIA)
  11. Overall Jacket:Orange Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 8kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 3/C [#AWG or #kcmil] CU 140 TRXLPE AIA 8kV 133% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldGroundInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.inchinchmilinchNo. x AWGmilinchmilinchlb/1000ftlb/1000ftinch
    TBA270.2830.6011400.6611x6801.924602.04486819052.5
    668932270.2830.6011400.6611x6801.982602.10289723642.5
    TBA1190.3220.641400.71x61102.068602.188103921593
    TBA1/0190.3620.681400.741x61102.154602.274125524433
    TBA2/0190.4050.7231400.7831x61102.247602.367152327853
    TBA3/0190.4560.7741400.8341x41102.357752.507190833233
    TBA4/0190.5120.831400.891x41102.478752.628233138453.5
    6660214/0190.5120.831400.891x41102.536752.686234744413.5
    TBA250370.5580.8841400.9441x41102.595752.745270543283.5
    664670350370.6610.9871401.0471x31102.875753.025371261994
    TBA500370.7891.1151401.1751x31253.124853.294513572404.5
    672305500370.7891.0921401.1521x31253.13853.3513977824.5
    675794500370.7891.0921401.1521x31253.13853.3513977714.5
    TBA750610.9681.3041401.3641x21253.532853.7027563100425
    TBA1000611.1171.4531401.5131x11253.854854.0249993127505.5
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    214.315920.1620.2210.0430.0260.583+j0.5330.221+j0.0432079172201
    214.715920.1620.2210.0430.0260.583+j0.5330.221+j0.0432079172201
    115.320080.1280.1750.0390.0240.540+j0.5120.175+j0.0402200197228
    1/015.925340.1020.1390.0360.0230.507+j0.4920.139+j0.0392324225257
    2/016.631940.0820.1120.0330.0210.481+j0.4710.112+j0.0382457260292
    3/017.540270.0640.0870.0310.020.458+j0.4480.087+j0.0362615297330
    4/018.450780.0510.070.0280.0190.441+j0.4250.070+j0.0352789342372
    4/018.850780.0510.070.0280.0190.441+j0.4250.070+j0.0352789342372
    25019.260000.0430.0590.0260.0180.429+j0.4040.059+j0.0342956376410
    35021.284000.0310.0430.0230.0170.409+j0.3670.043+j0.0333275460487
    50023.1120000.0210.030.020.0150.389+j0.3270.030+j0.0313672556573
    50023.1120000.0210.030.0180.0150.391+j0.3330.030+j0.0313600556573
    50023.1120000.0210.030.0180.0150.391+j0.3330.030+j0.0313600556573
    75025.9180000.0140.0210.0160.0140.366+j0.2770.021+j0.0304257678668
    100028.2240000.0110.0180.0150.0130.351+j0.2460.018+j0.0294719798772
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3/C in air copper and aluminum: D17N
    3/C direct buried copper and aluminum: D17E
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldGroundInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.mmmmmmmmNo. x AWGmmmmmmmmkg/kmkg/kminch
    TBA277.1915.273.5616.791x62.0348.871.5251.92129228352.5
    668932277.1915.273.5616.791x62.0350.341.5253.39133535182.5
    TBA1198.1816.263.5617.781x62.7952.531.5255.58154632133
    TBA1/0199.1917.273.5618.801x62.7954.711.5257.76186836363
    TBA2/01910.2918.363.5619.891x62.7957.071.5260.12226641453
    TBA3/01911.5819.663.5621.181x42.7959.871.9163.68283949453
    TBA4/01913.0021.083.5622.611x42.7962.941.9166.75346957223.5
    6660214/01913.0021.083.5622.611x42.7964.411.9168.22349366093.5
    TBA2503714.1722.453.5623.981x42.7965.911.9169.72402564413.5
    6646703503716.7925.073.5626.591x32.7973.021.9176.84552492254
    TBA5003720.0428.323.5629.851x33.1879.352.1683.677642107744.5
    6723055003720.0427.743.5629.261x33.1879.502.1683.827648115814.5
    6757945003720.0427.743.5629.261x33.1879.502.1683.827648115654.5
    TBA7506124.5933.123.5634.651x23.1889.712.1694.0311255149445
    TBA10006128.3736.913.5638.431x13.1897.892.16102.2114871189745.5
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    2363.2270840.53150.730.01310.08530.583+j0.5330.221+j0.0432079172201
    2373.3870840.53150.730.01310.08530.583+j0.5330.221+j0.0432079172201
    1388.6289360.41990.570.01190.07870.540+j0.5120.175+j0.0402200197228
    1/0403.86112760.33460.460.01100.07550.507+j0.4920.139+j0.0392324225257
    2/0421.64142130.26900.370.01010.06890.481+j0.4710.112+j0.0382457260292
    3/0444.50179200.21000.290.00940.06560.458+j0.4480.087+j0.0362615297330
    4/0467.36225970.16730.230.00850.06230.441+j0.4250.070+j0.0352789342372
    4/0477.52225970.16730.230.00850.06230.441+j0.4250.070+j0.0352789342372
    250487.68267000.14110.190.00790.05910.429+j0.4040.059+j0.0342956376410
    350538.48373800.10170.140.00700.05580.409+j0.3670.043+j0.0333275460487
    500586.74534000.06890.100.00610.04920.389+j0.3270.030+j0.0313672556573
    500586.74534000.06890.100.00550.04920.391+j0.3330.030+j0.0313600556573
    500586.74534000.06890.100.00550.04920.391+j0.3330.030+j0.0313600556573
    750657.86801000.04590.070.00490.04590.366+j0.2770.021+j0.0304257678668
    1000716.281068000.03610.060.00460.04270.351+j0.2460.018+j0.0294719798772
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3/C in air copper and aluminum: D17N
    3/C direct buried copper and aluminum: D17E

    Revision: 1.000.000

    Updated On: Dec. 31, 2024, 11:07 p.m. UTC