SPEC 26231

HVTECK AL 1/C 115TRXLPE TS PVC AIA PVC 8kV 100% CSA

Single Conductor, 115 Mils Tree Retardant Cross Linked Polyethylene, 100% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  2. Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
  3. Insulation:115 Mils Tree Retardant Cross Linked Polyethylene 100% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
  6. Inner Jacket:PVC inner jacket
  7. Armour:Aluminum Interlocked Armour (AIA)
  8. Overall Jacket:Orange Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 8kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CPT AL 115 TRXLPE AIA 8kV 100% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.inchinchmilinchmilinchmilinchlb/1000ftlb/1000ftinch
    270.2680.5361150.596650.956501.056495642.5
    1190.2990.5671150.627650.987501.087526042.5
    1/0190.3360.6041150.664651.024501.124556523
    2/0190.3760.6441150.704801.094501.194587413
    3/0190.4230.6911150.751801.141501.241628113
    4/0190.4750.7431150.803801.193501.293668933.5
    250370.520.7961150.856801.246501.346719753.5
    350370.6160.8921150.952801.342501.4427811473.5
    500370.7361.0121151.072801.562601.6828815584.5
    750610.9081.1941151.254801.744601.86410319685
    1000611.1171.4031151.463801.953602.07312023965.5
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    27.43980.2660.3650.0380.0530.698+j0.5500.366+j0.0581878169176
    17.65020.2110.2890.0350.0510.627+j0.5330.290+j0.0551974194198
    1/07.96330.1670.2290.0330.0490.571+j0.5140.230+j0.0532088222223
    2/08.47980.1330.1820.030.0480.528+j0.4950.183+j0.0522212255250
    3/08.710060.1050.1440.0280.0460.493+j0.4740.145+j0.0502358290278
    4/09.112690.0840.1150.0250.0450.467+j0.4520.116+j0.0492519329309
    2509.415000.070.0960.0230.0440.450+j0.4300.097+j0.0472683370347
    35010.121000.0510.070.020.0410.425+j0.3940.071+j0.0452981446402
    50011.830000.0360.050.0180.0410.401+j0.3540.051+j0.0443352533451
    7501345000.0230.0330.0150.0380.375+j0.3020.034+j0.0423916631500
    100014.560000.0170.0250.0120.0360.353+j0.2560.027+j0.0414564707539
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3-1/C in air copper and aluminum: D17M
    3-1/C direct buried copper and aluminum: D17A
    Table 3 – Weights and Measurements (Metric)
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.mmmmmmmmmmmmmmmmkg/kmkg/kminch
    276.8113.612.9215.141.6524.281.2726.82738392.5
    1197.5914.402.9215.931.6525.071.2727.61778992.5
    1/0198.5315.342.9216.871.6526.011.2728.55829703
    2/0199.5516.362.9217.882.0327.791.2730.338611033
    3/01910.7417.552.9219.082.0328.981.2731.529212073
    4/01912.0718.872.9220.402.0330.301.2732.849813293.5
    2503713.2120.222.9221.742.0331.651.2734.1910614513.5
    3503715.6522.662.9224.182.0334.091.2736.6311617073.5
    5003718.6925.702.9227.232.0339.671.5242.7213123194.5
    7506123.0630.332.9231.852.0344.301.5247.3515329295
    10006128.3735.642.9237.162.0349.611.5252.6517935665.5
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    2187.9617710.87271.200.01160.17390.698+j0.5500.366+j0.0581878169176
    1193.0422340.69230.950.01070.16730.627+j0.5330.290+j0.0551974194198
    1/0200.6628170.54790.750.01010.16080.571+j0.5140.230+j0.0532088222223
    2/0213.3635510.43640.600.00910.15750.528+j0.4950.183+j0.0522212255250
    3/0220.9844770.34450.470.00850.15090.493+j0.4740.145+j0.0502358290278
    4/0231.1456470.27560.380.00760.14760.467+j0.4520.116+j0.0492519329309
    250238.7666750.22970.310.00700.14440.450+j0.4300.097+j0.0472683370347
    350256.5493450.16730.230.00610.13450.425+j0.3940.071+j0.0452981446402
    500299.72133500.11810.160.00550.13450.401+j0.3540.051+j0.0443352533451
    750330.20200250.07550.110.00460.12470.375+j0.3020.034+j0.0423916631500
    1000368.30267000.05580.080.00370.11810.353+j0.2560.027+j0.0414564707539
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3-1/C in air copper and aluminum: D17M
    3-1/C direct buried copper and aluminum: D17A

    Revision: 1.000.000

    Updated On: Dec. 31, 2024, 11:07 p.m. UTC