SPEC 26206

HVTECK CU 1/C 140NLEPR CB PVC AIA PVC 8kV 133% CSA

Single Conductor, 140 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 133% Insulation Level, Concentric Bond, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Conductor Shield:Semi-conducting cross-linked copolymer
  3. Insulation:140 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Concentric Shield:Concentrically applied copper bond / shield wires. Complies with greater than the minimum requirement as per Table 44, CSA Standard C68.10 and Table 16A, Canadian Electrical Code Part 1
  6. Neutral Separator:Mylar tape
  7. Inner Jacket:PVC inner jacket
  8. Armour:Aluminum Interlocked Armour (AIA)
  9. Overall Jacket:Orange Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 8kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CU 140 NLEPR AIA 8kV 133% INS LEVEL CB [No. x SIZE] AWG SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.inchinchmilinchNo. x AWGmilinchmilinchlb/1000ftlb/1000ftinch
    270.2830.6011400.6615x12801.321501.42134111883.5
    1190.3220.641400.77x12801.36501.4644513313.5
    1/0190.3620.681400.747x12801.4501.551614414
    2/0190.4050.7231400.7837x12801.443501.54360515734
    3/0190.4560.7741400.8349x12801.594601.71475019444.5
    4/0190.5120.831400.899x12801.65601.7788921454.5
    250370.5580.8841400.94411x12801.704601.824105523744.5
    350370.6610.9871401.04713x12801.807601.927142528585
    500370.7891.1151401.17517x12801.935602.055196735415.5
    750610.9681.3041401.36421x121102.184602.304283947516
    1000611.1171.4531401.51321x121102.333752.483362357756.5
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    29.95300.1620.2210.0330.0590.521+j0.1960.224+j0.0652770215221
    110.26690.1280.1750.030.0560.419+j0.1250.179+j0.0613879245247
    1/010.58440.1020.1390.0280.0540.383+j0.1230.143+j0.0593879278275
    2/010.810640.0820.1120.0260.0520.355+j0.1220.116+j0.0583879317306
    3/01213420.0640.0870.0230.0520.288+j0.0860.092+j0.0574987357335
    4/012.416920.0510.070.0210.050.271+j0.0850.075+j0.0554987404369
    25012.820000.0430.0590.020.0490.229+j0.0650.065+j0.0536095456412
    35013.528000.0310.0430.0170.0460.190+j0.0510.050+j0.0507203537456
    50014.440000.0210.030.0150.0440.145+j0.0370.038+j0.0479420616497
    75016.160000.0140.0210.0130.0420.115+j0.0280.030+j0.04411636706551
    100017.480000.0110.0180.0110.040.112+j0.0270.027+j0.04211636813596
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3-1/C in air copper and aluminum: D17M
    3-1/C direct buried copper and aluminum: D17A
    Table 3 – Weights and Measurements (Metric)
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.mmmmmmmmNo. x AWGmmmmmmmmkg/kmkg/kminch
    277.1915.273.5616.795x122.0333.551.2736.0950717683.5
    1198.1816.263.5617.787x122.0334.541.2737.0866219813.5
    1/0199.1917.273.5618.807x122.0335.561.2738.1076821444
    2/01910.2918.363.5619.897x122.0336.651.2739.1990023414
    3/01911.5819.663.5621.189x122.0340.491.5243.54111628934.5
    4/01913.0021.083.5622.619x122.0341.911.5244.96132331924.5
    2503714.1722.453.5623.9811x122.0343.281.5246.33157035334.5
    3503716.7925.073.5626.5913x122.0345.901.5248.95212142535
    5003720.0428.323.5629.8517x122.0349.151.5252.20292752705.5
    7506124.5933.123.5634.6521x122.7955.471.5258.52422570706
    10006128.3736.913.5638.4321x122.7959.261.9163.07539285946.5
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    2251.4623590.53150.730.01010.19360.521+j0.1960.224+j0.0652770215221
    1259.0829770.41990.570.00910.18370.419+j0.1250.179+j0.0613879245247
    1/0266.7037560.33460.460.00850.17720.383+j0.1230.143+j0.0593879278275
    2/0274.3247350.26900.370.00790.17060.355+j0.1220.116+j0.0583879317306
    3/0304.8059720.21000.290.00700.17060.288+j0.0860.092+j0.0574987357335
    4/0314.9675290.16730.230.00640.16400.271+j0.0850.075+j0.0554987404369
    250325.1289000.14110.190.00610.16080.229+j0.0650.065+j0.0536095456412
    350342.90124600.10170.140.00520.15090.190+j0.0510.050+j0.0507203537456
    500365.76178000.06890.100.00460.14440.145+j0.0370.038+j0.0479420616497
    750408.94267000.04590.070.00400.13780.115+j0.0280.030+j0.04411636706551
    1000441.96356000.03610.060.00340.13120.112+j0.0270.027+j0.04211636813596
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3-1/C in air copper and aluminum: D17M
    3-1/C direct buried copper and aluminum: D17A

    Revision: 1.000.000

    Updated On: Dec. 31, 2024, 11:07 p.m. UTC