SPEC 26115
HVTECK CU 1/C 90TRXLPE CB PVC AIA PVC 5kV 100% CSA
Single Conductor, 90 Mils Tree Retardant Cross Linked Polyethylene, 100% Insulation Level, Concentric Bond, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

Construction:
- Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
- Conductor Shield:Semi-conducting cross-linked copolymer
- Insulation:90 Mils Tree Retardant Cross Linked Polyethylene 100% insulation level
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Concentric Shield:Concentrically applied copper bond / shield wires. Complies with greater than the minimum requirement as per Table 44, CSA Standard C68.10 and Table 16A, Canadian Electrical Code Part 1
- Neutral Separator:Mylar tape
- Inner Jacket:PVC inner jacket
- Armour:Aluminum Interlocked Armour (AIA)
- Overall Jacket:Orange Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire's 5kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.
Specifications:
Sample Print Legend:
(CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CU 90 TRXLPE AIA 5kV 100% INS LEVEL CB [No. x SIZE] AWG SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
Table 1 – Weights and Measurements
| Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Concentric Neutral | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Conduit Size* |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | inch | inch | mil | inch | No. x AWG | mil | inch | mil | inch | lb/1000ft | lb/1000ft | inch |
| 2 | 7 | 0.283 | 0.501 | 90 | 0.561 | 5x12 | 80 | 1.221 | 50 | 1.321 | 332 | 1059 | 3.5 |
| 1 | 19 | 0.322 | 0.54 | 90 | 0.6 | 7x12 | 80 | 1.26 | 50 | 1.36 | 437 | 1200 | 3.5 |
| 1/0 | 19 | 0.362 | 0.58 | 90 | 0.64 | 7x12 | 80 | 1.3 | 50 | 1.4 | 508 | 1307 | 3.5 |
| 2/0 | 19 | 0.405 | 0.623 | 90 | 0.683 | 7x12 | 80 | 1.343 | 50 | 1.443 | 596 | 1433 | 3.5 |
| 3/0 | 19 | 0.456 | 0.674 | 90 | 0.734 | 9x12 | 80 | 1.394 | 50 | 1.494 | 742 | 1625 | 4 |
| 4/0 | 19 | 0.512 | 0.73 | 90 | 0.79 | 9x12 | 80 | 1.45 | 50 | 1.55 | 881 | 1815 | 4 |
| 250 | 37 | 0.558 | 0.784 | 90 | 0.844 | 11x12 | 80 | 1.604 | 60 | 1.724 | 1047 | 2211 | 4.5 |
| 350 | 37 | 0.661 | 0.887 | 90 | 0.947 | 13x12 | 80 | 1.707 | 60 | 1.827 | 1417 | 2685 | 5 |
| 500 | 37 | 0.789 | 1.015 | 90 | 1.075 | 17x12 | 80 | 1.835 | 60 | 1.955 | 1958 | 3356 | 5 |
| 750 | 61 | 0.968 | 1.204 | 90 | 1.264 | 21x12 | 110 | 2.084 | 60 | 2.204 | 2831 | 4545 | 6 |
| 1000 | 61 | 1.117 | 1.353 | 90 | 1.413 | 21x12 | 110 | 2.233 | 60 | 2.353 | 3615 | 5490 | 6 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 2 | 9.2 | 530 | 0.162 | 0.221 | 0.03 | 0.057 | 0.523+j0.191 | 0.224+j0.063 | 2770 | 215 | 221 |
| 1 | 9.5 | 669 | 0.128 | 0.175 | 0.028 | 0.055 | 0.420+j0.121 | 0.180+j0.060 | 3879 | 245 | 247 |
| 1/0 | 9.8 | 844 | 0.102 | 0.139 | 0.025 | 0.053 | 0.384+j0.120 | 0.143+j0.058 | 3879 | 278 | 275 |
| 2/0 | 10.1 | 1064 | 0.082 | 0.112 | 0.023 | 0.051 | 0.356+j0.119 | 0.116+j0.056 | 3879 | 317 | 306 |
| 3/0 | 10.5 | 1342 | 0.064 | 0.087 | 0.021 | 0.049 | 0.289+j0.083 | 0.092+j0.054 | 4987 | 357 | 335 |
| 4/0 | 10.9 | 1692 | 0.051 | 0.07 | 0.019 | 0.047 | 0.272+j0.082 | 0.075+j0.052 | 4987 | 404 | 369 |
| 250 | 12.1 | 2000 | 0.043 | 0.059 | 0.018 | 0.048 | 0.230+j0.062 | 0.066+j0.052 | 6095 | 456 | 412 |
| 350 | 12.8 | 2800 | 0.031 | 0.043 | 0.015 | 0.045 | 0.190+j0.049 | 0.050+j0.049 | 7203 | 537 | 456 |
| 500 | 13.7 | 4000 | 0.021 | 0.03 | 0.013 | 0.043 | 0.145+j0.034 | 0.039+j0.046 | 9420 | 616 | 497 |
| 750 | 15.4 | 6000 | 0.014 | 0.021 | 0.011 | 0.041 | 0.116+j0.027 | 0.031+j0.043 | 11636 | 706 | 551 |
| 1000 | 16.5 | 8000 | 0.011 | 0.018 | 0.01 | 0.039 | 0.112+j0.026 | 0.027+j0.041 | 11636 | 813 | 596 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
Table 3 – Weights and Measurements (Metric)
| Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Concentric Neutral | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Conduit Size* |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | mm | mm | mm | mm | No. x AWG | mm | mm | mm | mm | kg/km | kg/km | inch |
| 2 | 7 | 7.19 | 12.73 | 2.29 | 14.25 | 5x12 | 2.03 | 31.01 | 1.27 | 33.55 | 494 | 1576 | 3.5 |
| 1 | 19 | 8.18 | 13.72 | 2.29 | 15.24 | 7x12 | 2.03 | 32.00 | 1.27 | 34.54 | 650 | 1786 | 3.5 |
| 1/0 | 19 | 9.19 | 14.73 | 2.29 | 16.26 | 7x12 | 2.03 | 33.02 | 1.27 | 35.56 | 756 | 1945 | 3.5 |
| 2/0 | 19 | 10.29 | 15.82 | 2.29 | 17.35 | 7x12 | 2.03 | 34.11 | 1.27 | 36.65 | 887 | 2133 | 3.5 |
| 3/0 | 19 | 11.58 | 17.12 | 2.29 | 18.64 | 9x12 | 2.03 | 35.41 | 1.27 | 37.95 | 1104 | 2418 | 4 |
| 4/0 | 19 | 13.00 | 18.54 | 2.29 | 20.07 | 9x12 | 2.03 | 36.83 | 1.27 | 39.37 | 1311 | 2701 | 4 |
| 250 | 37 | 14.17 | 19.91 | 2.29 | 21.44 | 11x12 | 2.03 | 40.74 | 1.52 | 43.79 | 1558 | 3290 | 4.5 |
| 350 | 37 | 16.79 | 22.53 | 2.29 | 24.05 | 13x12 | 2.03 | 43.36 | 1.52 | 46.41 | 2109 | 3996 | 5 |
| 500 | 37 | 20.04 | 25.78 | 2.29 | 27.30 | 17x12 | 2.03 | 46.61 | 1.52 | 49.66 | 2914 | 4994 | 5 |
| 750 | 61 | 24.59 | 30.58 | 2.29 | 32.11 | 21x12 | 2.79 | 52.93 | 1.52 | 55.98 | 4213 | 6764 | 6 |
| 1000 | 61 | 28.37 | 34.37 | 2.29 | 35.89 | 21x12 | 2.79 | 56.72 | 1.52 | 59.77 | 5380 | 8170 | 6 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 4 – Electrical and Engineering Data (Metric)
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | mm | newton | Ω/km | Ω/km | MΩ*km | Ω/km | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 2 | 233.68 | 2359 | 0.5315 | 0.73 | 0.0091 | 0.1870 | 0.523+j0.191 | 0.224+j0.063 | 2770 | 215 | 221 |
| 1 | 241.30 | 2977 | 0.4199 | 0.57 | 0.0085 | 0.1804 | 0.420+j0.121 | 0.180+j0.060 | 3879 | 245 | 247 |
| 1/0 | 248.92 | 3756 | 0.3346 | 0.46 | 0.0076 | 0.1739 | 0.384+j0.120 | 0.143+j0.058 | 3879 | 278 | 275 |
| 2/0 | 256.54 | 4735 | 0.2690 | 0.37 | 0.0070 | 0.1673 | 0.356+j0.119 | 0.116+j0.056 | 3879 | 317 | 306 |
| 3/0 | 266.70 | 5972 | 0.2100 | 0.29 | 0.0064 | 0.1608 | 0.289+j0.083 | 0.092+j0.054 | 4987 | 357 | 335 |
| 4/0 | 276.86 | 7529 | 0.1673 | 0.23 | 0.0058 | 0.1542 | 0.272+j0.082 | 0.075+j0.052 | 4987 | 404 | 369 |
| 250 | 307.34 | 8900 | 0.1411 | 0.19 | 0.0055 | 0.1575 | 0.230+j0.062 | 0.066+j0.052 | 6095 | 456 | 412 |
| 350 | 325.12 | 12460 | 0.1017 | 0.14 | 0.0046 | 0.1476 | 0.190+j0.049 | 0.050+j0.049 | 7203 | 537 | 456 |
| 500 | 347.98 | 17800 | 0.0689 | 0.10 | 0.0040 | 0.1411 | 0.145+j0.034 | 0.039+j0.046 | 9420 | 616 | 497 |
| 750 | 391.16 | 26700 | 0.0459 | 0.07 | 0.0034 | 0.1345 | 0.116+j0.027 | 0.031+j0.043 | 11636 | 706 | 551 |
| 1000 | 419.10 | 35600 | 0.0361 | 0.06 | 0.0030 | 0.1280 | 0.112+j0.026 | 0.027+j0.041 | 11636 | 813 | 596 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A