SPEC 70065

300V SEOPRENE® SJEOOW Cord with Black Jacket 105°C. Silicone Free

300 Volt -50°C to 105°C Flexible Cord. Premium Oil Resistance, Sunlight, Chemical, Water Resistance and Flame Retardant

...

Construction:

  1. Conductor:Class K stranded bare copper per ASTM B-174
  2. Insulation:Heat, moisture and oil resistant TPE
  3. Filler:Non-wicking polypropylene fillers, with a tissue-paper separator wrapped around the assembly
  4. Jacket:Black TPE (Other colors available upon request)

Applications and Features:

Southwire Type SJEOOW Flexible Cords are permitted for indoor and outdoor temporary power uses, portable industrial machinery, compressors, conveyors, and automated production equipment. Cords are suitable for use in temperatures between -50°C to maximum 105°C.

Specifications:

  • UL 62 Flexible Cords and Cables
  • CSA C22.2 No. 49 Flexible Cords and Cables
  • Passes CSA FT2 Flame Test
  • RoHS-3 Complies with European Directive 2015/863
  • NEC Article 400 Flexible Cords, Cables and Fixture Wire
  • Sample Print Legend:

    SOUTHWIRE{R} SEOPRENE{R} CORD X/C XX AWG (X.XXmm2) SJEOOW E46194 MASTER-DESIGN (UL) 300V -50{D}C TO 105{D}C -- CSA LL90458 SJEOOW 300V -50{D}C TO 105{D}C FT2 WATER RESISTANT P-07-KA190004-MSHA

    Packaging:

    Standard lengths: 250', 500' and 1,000' reels. Other lengths available upon request.
    Table 1 – Weights and Measurements
    Stock NumberCCI Part #Cond. SizeCond. NumberCond. StrandsInsul. ThicknessJacket ThicknessApprox. ODApprox. WeightAmpacityInsul. ColorJacket Color
    AWG/KcmilNo.No.milmilinchlb/1000ftAmp
    550528232251821630350.2863810BK,WEBK
    550445233251831630350.308477BK,WE,GNBK
    550474234251841630300.328585WE,BK,GN,RDBK
    550495232261622630300.3104613BK,WEBK
    550403233261632630300.3296010BK,WE,GNBK
    550435234261642630300.370788BK,WE,GN,RDBK
    550559232271424130300.3406018BK,WEBK
    550433233271434130350.3638015BK,WE,GNBK
    550401234271444130300.3939912BK,WE,RD,GNBK
    550627232281226530500.4109325BK,WEBK
    598755N/A1236530450.42811820BK,WE,GNBK
    550396233281236530450.42811920BK,WE,GNBK
    550465234281246530450.46815116BK,WE,RD,GNBK
    5507672322910210445650.54115830BK,WEBK
    5504482332910310445650.57320525BK,WE,GNBK
    5506282342910410445650.62826120BK,WE,RD,GNBK
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Ampacities are based on TABLE 400.5(A)(1) of the 2023 National Electrical Code and CEC Table 12.
    ^ Color Sequence: Black, Red
    ! White PVC jacket
    ** Not a Federal and Military Specification JC-580B
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Weights and Measurements (Metric)
    Stock NumberCCI Part #Cond. SizeCond. NumberCond. StrandsInsul. ThicknessJacket ThicknessApprox. ODApprox. WeightAmpacity *Insul. ColorJacket Color
    AWG/KcmilNo.No.mmmmmmkg/kmAmp
    55052823225182160.760.897.265710BK,WEBK
    55044523325183160.760.897.82707BK,WE,GNBK
    55047423425184160.760.768.33865WE,BK,GN,RDBK
    55049523226162260.760.767.876813BK,WEBK
    55040323326163260.760.768.368910BK,WE,GNBK
    55043523426164260.760.769.401168BK,WE,GN,RDBK
    55055923227142410.760.768.648918BK,WEBK
    55043323327143410.760.899.2211915BK,WE,GNBK
    55040123427144410.760.769.9814712BK,WE,RD,GNBK
    55062723228122650.761.2710.4113825BK,WEBK
    598755N/A123650.761.1410.8717620BK,WE,GNBK
    55039623328123650.761.1410.8717720BK,WE,GNBK
    55046523428124650.761.1411.8922516BK,WE,RD,GNBK
    550767232291021041.141.6513.7423530BK,WEBK
    550448233291031041.141.6514.5530525BK,WE,GNBK
    550628234291041041.141.6515.9538820BK,WE,RD,GNBK
    * Ampacities are based on TABLE 400.5(A)(1) of the 2023 National Electrical Code and CEC Table 12.
    ^ Color Sequence: Black, Red
    ! White PVC jacket
    ** Not a Federal and Military Specification JC-580B

    Revision: 1.000.004

    Updated On: Aug. 21, 2025, 11:33 a.m. UTC