SPEC 70042

600V AMERICAN MUSTANG® SOOW Cord with Yellow Jacket 105°C. MSHA Approved

600V, 105°C Flexible Cord. Heat, Moisture and Oil Resistant EPDM Rubber Insulation and Heat, Moisture and Oil Resistant Flexible CPE Jacket, UL/CSA Listed.

...

Construction:

  1. Conductor:Class K stranded bare copper per ASTM B-174
  2. Insulation:Heat, moisture and oil resistant EPDM
  3. Filler:Waxed paper or rubber fillers, with a full cotton serve or paper separator wrapped around the assembly
  4. Jacket:Yellow CPE (Other colors available upon request)

Applications and Features:

Southwire Type SOOW Flexible Cords UL/ CSA listed are permitted for use as specified by Article 400 and related articles of the 2014 National Electrical Code. The cable is rated -40°C to 105°C, water, oil, and weather resistant. Southwire Type SOOW Flexible Cords are designed for extra hard usage on industrial equipment, heavy tools, battery chargers, portable lights, welding leads, marine dockside power, power extensions and mining applications.

Specifications:

  • UL 62 Flexible Cords and Cables
  • CSA C22.2 No. 49 Flexible Cords and Cables
  • MSHA flame test - P07-KA070018-1MSHA
  • Passes CSA FT2 Flame Test
  • RoHS-3 Complies with European Directive 2015/863
  • NEC Article 400 Flexible Cords, Cables and Fixture Wire
  • Federal Specification J-C-580B
  • Sample Print Legend:

    SOUTHWIRE® American Mustang® CORD X/C XX AWG (XXmm2) SOOW E46194 (UL) 600V -40C TO 105C -- CSA LL90458 SOOW 600V -40C TO 105C FT2 WATER RESISTANT

    Packaging:

    Standard lengths: 250', 500' and 1,000' reels. Other lengths available upon request.
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. NumberCond. StrandsInsul. ThicknessJacket ThicknessApprox. ODApprox. WeightAmpacityInsul. ColorJacket Color
    AWG/KcmilNo.No.milmilinchlb/1000ftAmp
    6313441831630700.366767BK,WE,GNYW
    5702141626530700.3707413BK,WEYW
    6307301632630700.3909010BK,WE,GNYW
    6307271642630650.4151068BK,WE,RD,GNYW
    5983341424145900.51313318BK,WEYW
    6307211434145850.52515715BK,WE,GNYW
    5969811444145850.56519312BK,WE,RD,GNYW
    57021012365451150.60621720BK,WE,GNYW
    59532712365451150.60921820BK,WE,GNYW
    63072212465451150.66827416BK,WE,RD,GNYW
    598724102104451150.62022830BK,RDYW
    630724103104451150.65528025BK,WE,GNYW
    630725104104451050.71033620BK,WE,RD,GNYW
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Ampacities are based on TABLE 400.5(A)(1) of the 2023 National Electrical Code and CEC Table 12.
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Weights and Measurements (Metric)
    Stock NumberCond. SizeCond. NumberCond. StrandsInsul. ThicknessJacket ThicknessApprox. ODApprox. WeightAmpacity *Insul. ColorJacket Color
    AWG/KcmilNo.No.mmmmmmkg/kmAmp
    631344183160.761.789.301137BK,WE,GNYW
    570214162650.761.789.4011013BK,WEYW
    630730163260.761.789.9113410BK,WE,GNYW
    630727164260.761.6510.541588BK,WE,RD,GNYW
    598334142411.142.2913.0319818BK,WEYW
    630721143411.142.1613.3323415BK,WE,GNYW
    596981144411.142.1614.3528712BK,WE,RD,GNYW
    570210123651.142.9215.3932320BK,WE,GNYW
    595327123651.142.9215.4732420BK,WE,GNYW
    630722124651.142.9216.9740816BK,WE,RD,GNYW
    5987241021041.142.9215.7533930BK,RDYW
    6307241031041.142.9216.6441725BK,WE,GNYW
    6307251041041.142.6718.0350020BK,WE,RD,GNYW
    * Ampacities are based on TABLE 400.5(A)(1) of the 2023 National Electrical Code and CEC Table 12.

    Revision: 1.000.002

    Updated On: March 31, 2025, 12:28 a.m. UTC