SPEC 45502

CU 2000V XLPE Insulation Type RHH/RHW-2. 600V Type USE-2

Power Cable 2000 Volt Single Conductor Copper, Cross Linked Polyethylene (XLPE) Insulation for Type RHH/RHW-2 and 600 Volt for Type USE-2

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and B8
  2. Insulation:Cross Linked Polyethylene (XLPE) Type RHH/RHW-2

Applications and Features:

Southwire’s 2000 Volt power cables RHH/RHW are suited for use in wet and dry areas, conduits, ducts, troughs, trays, aerial supported by a messenger, and where superior electrical properties are desired. Can be used in direct burial applications at 600 Volt. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 854 Service Entrance Cable
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • Sample Print Legend:

    {SQFTG} SOUTHWIRE E32071 UL} XXX KCMIL CU XXX MILS XLP 2KV TYPE RHH-RHW-2 / 600 VOLTS TYPE USE-2 90{D}C
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrand CountDiameter Over ConductorInsul. ThicknessApprox. ODCopper WeightApprox. Weight
    AWG/KcmilNo. of Strandsinchmilinchlb/1000ftlb/1000ft
    TBA870.141700.2815074
    TBA670.177700.31781109
    TBA470.225700.365128161
    TBA270.282700.422204244
    TBA1190.322900.502258318
    TBA1/0190.361900.541325391
    TBA2/0190.405900.585410482
    TBA3/0190.456900.636518598
    TBA4/0190.512900.692653741
    TBA250370.5581050.768771884
    TBA300370.6091050.829261048
    TBA350370.6611050.87110811212
    568018500370.7891050.98615431748
    TBA600610.8651201.10518532046
    648750750610.9681201.2223152569
    TBA1000611.1171201.35730883330
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity At 75°CAllowable Ampacity At 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    TBA81.11320.6530.7860.0525055
    TBA61.22090.4110.4950.0516575
    TBA41.43330.2580.310.0488595
    TBA21.65300.1620.1950.045115130
    TBA126690.1280.1540.046130145
    TBA1/02.18440.1020.1220.044150170
    TBA2/02.310640.0810.0970.043175195
    TBA3/02.513420.0640.0780.042200225
    TBA4/02.716920.0510.0620.041230260
    TBA250320000.0430.0530.041255290
    TBA3003.324000.0310.0390.04285320
    TBA3503.428000.0310.0390.04310350
    5680185003.940000.0220.0290.039380430
    TBA6005.548000.0180.0250.039420475
    6487507506.160000.0140.0220.038475535
    TBA10006.780000.0110.0180.037545615
    * Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
    * Inductive Reactance is based on non-ferrous conduit with one diameter spacing center-to-center.

    Revision: 1.000.010

    Updated On: Jan. 15, 2026, 2:07 p.m. UTC