SPEC 45256
Flexible CU 600/1000V XLPE Insulation PVC Jacket XHHW-2. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free
Type TC-ER Power Cable 600 or 1000 Volt Flexible Three Conductor Copper, Cross Linked Polyethylene (XLPE) insulation XHHW-2 Polyvinyl Chloride (PVC) Jacket with 1 Copper Ground (Bare or Insulated). CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free.

Construction:
- Conductor:Sizes 8 - 4/0 AWG: Class K, flexible stranded bare copper per ASTM B3 and B172. Sizes 250 - 750 kcmil: Class I, flexible stranded bare copper per ASTM B3 and B172.
- Insulation:Cross Linked Polyethylene (XLPE) Type XHHW-2
- Grounding Conductor:Sizes 8 - 4/0 AWG: Class K, flexible stranded bare copper per ASTM B3 and B172. Sizes 250 - 750 kcmil: Class I, flexible stranded bare copper per ASTM B3 and B172. When present, phase cable conductor sizes 8 & 6 AWG have an insulated green ground.
- Filler:Paper filler (cable size 8 & 6 uses Polypropylene filler)
- Binder:Polyester flat thread binder tape for cable sizes larger than 2 AWG
- Overall Jacket:Polyvinyl Chloride (PVC)
Applications and Features:
Southwire’s 600 or 1000 Volt Type TC-ER flexible power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Sunlight Resistant - For Direct Burial - Silicone Free
Specifications:
Sample Print Legend:
Bare Ground: {SQFTG} SOUTHWIRE® {UL} XX AWG (X.XX{mm2}) 3/C TYPE TC-ER XHHW-2 CDRS 90°C JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600V or 1000V {NOM}-ANCE XHHW-2 CT FT4 SR 600V 90C
Green Ground: {SQFTG} SOUTHWIRE® {UL} XX AWG (X.XX{mm2}) CU 3/C TYPE TC-ER XHHW-2 CDRS GW 1 X X AWG CU GREEN INSULATED 90°C JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600V or 1000V {NOM}-ANCE XHHW-2 CT FT4 SR 600V 90C
Green Ground: {SQFTG} SOUTHWIRE® {UL} XX AWG (X.XX{mm2}) CU 3/C TYPE TC-ER XHHW-2 CDRS GW 1 X X AWG CU GREEN INSULATED 90°C JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600V or 1000V {NOM}-ANCE XHHW-2 CT FT4 SR 600V 90C
Table 1 – Weights and Measurements
| Cond. Size | Cond. Number | Strand Count | Diameter Over Conductor | Insul. Thickness | Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Jacket Color |
|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. of Strands | inch | mil | mil | inch | lb/1000ft | lb/1000ft | ||
| 8 | 3 | 168 | 0.153 | 45 | 60 | 0.651 | 189 | 299 | BK |
| 6 | 3 | 259 | 0.198 | 45 | 60 | 0.748 | 320 | 451 | BK |
| 4 | 3 | 413 | 0.235 | 45 | 80 | 0.868 | 444 | 622 | BK |
| 2 | 3 | 651 | 0.302 | 45 | 80 | 1.013 | 717 | 932 | BK |
| 1 | 3 | 836 | 0.347 | 55 | 80 | 1.153 | 886 | 1156 | BK |
| 1/0 | 3 | 1044 | 0.354 | 55 | 80 | 1.168 | 1093 | 1367 | BK |
| 2/0 | 3 | 1254 | 0.4 | 55 | 80 | 1.268 | 1235 | 1536 | BK |
| 3/0 | 3 | 1666 | 0.533 | 55 | 80 | 1.555 | 1750 | 2131 | BK |
| 4/0 | 3 | 2109 | 0.55 | 55 | 80 | 1.592 | 2177 | 2568 | BK |
| 250 | 3 | 627 | 0.605 | 65 | 110 | 1.814 | 2443 | 3007 | BK |
| 350 | 3 | 855 | 0.67 | 65 | 110 | 1.954 | 3377 | 3990 | BK |
| 400 | 3 | 980 | 0.831 | 65 | 110 | 2.302 | 4011 | 4748 | BK |
| 600 | 3 | 1480 | 0.963 | 80 | 110 | 2.652 | 5837 | 6776 | BK |
| 500 | 3 | 1225 | 0.988 | 65 | 110 | 2.641 | 5159 | 6016 | BK |
| 750 | 3 | 1850 | 1.094 | 80 | 140 | 2.995 | 7433 | 8640 | BK |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
GG: Green Insulated Ground
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Cond. Size | Cond. Number | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 75°C | Inductive Reactance @ 60Hz | Allowable Ampacity At 75°C | Allowable Ampacity At 90°C |
|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | |
| 8 | 3 | 2.6 | 396 | 0.666 | 0.827 | 0.052 | 50 | 55 |
| 6 | 3 | 3 | 629 | 0.419 | 0.52 | 0.051 | 65 | 75 |
| 4 | 3 | 3.5 | 1001 | 0.263 | 0.326 | 0.048 | 85 | 95 |
| 2 | 3 | 5.1 | 1592 | 0.167 | 0.207 | 0.045 | 115 | 130 |
| 1 | 3 | 5.8 | 2008 | 0.133 | 0.165 | 0.046 | 130 | 145 |
| 1/0 | 3 | 5.8 | 2534 | 0.105 | 0.13 | 0.044 | 150 | 170 |
| 2/0 | 3 | 6.3 | 3194 | 0.085 | 0.105 | 0.043 | 175 | 195 |
| 3/0 | 3 | 7.8 | 4027 | 0.067 | 0.083 | 0.042 | 200 | 225 |
| 4/0 | 3 | 8 | 5078 | 0.053 | 0.066 | 0.041 | 230 | 260 |
| 250 | 3 | 9.1 | 6000 | 0.045 | 0.056 | 0.041 | 255 | 290 |
| 350 | 3 | 9.8 | 8400 | 0.032 | 0.041 | 0.04 | 310 | 350 |
| 400 | 3 | 13.8 | 9600 | 0.029 | 0.037 | 0.04 | 335 | 380 |
| 600 | 3 | 15.9 | 14400 | 0.018 | 0.024 | 0.039 | 420 | 475 |
| 500 | 3 | 15.8 | 12000 | 0.022 | 0.029 | 0.039 | 380 | 430 |
| 750 | 3 | 18 | 18000 | 0.015 | 0.021 | 0.038 | 475 | 535 |
*Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
Revision: 1.000.005
Updated On: Nov. 3, 2025, 9:51 p.m. UTC

