SPEC 45059

TCU 600 EPR Insulation XHHW-2 Thermoplastic CPE-TP Jacket. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free

Type TC-ER Control Cable 600Volt Tinned Copper Conductors, Ethylene Propylene Rubber (EPR) Insulation XHHW-2 Thermoplastic Chlorinated Polyethylene (CPE-TP) Jacket, Control Cable Conductor Identification Method 1 Table 1. CT Rated - Sunlight Resistant - Oil Resistant - For Direct Burial - VW-1 rated - Silicone Free

...

Construction:

  1. Conductor:7 strands class B compressed tinned copper per ASTM B33 and ASTM B8
  2. Insulation:Ethylene Propylene Rubber (EPR) XHHW-2, 30 Mils thick for all cable sizes
  3. Overall Jacket:Thermoplastic Chlorinated Polyethylene (CPE-TP) Jacket

Applications and Features:

Southwire’s 600 Volt Type TC-ER control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. VW-1 rated - Sunlight Resistant - Oil Resistant - For Direct Burial - Silicone Free

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 44 VW-1 Vertical flame test on individual conductors
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 1
  • ICEA S-73-532 Standard for Control, Thermocouple Extension and Instrumentation Cables
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • Sample Print Legend:

    {SQFTG} SOUTHWIRE® XX AWG (X.XX{mm2}) XX/C EPR/CPE TYPE TC-ER XHHW-2 CDRS E75755 {UL} 600V 90°C DRY/90°C WET OIL RES I SUNLIGHT RESISTANT DIRECT BURIAL FT4/IEEE 1202 -- {NOM}-ANCE EPR/CPE Tipo XHHW-2 SR FT4 600V 90°C USA
    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. NumberCond. StrandsInsul. ThicknessJacket ThicknessApprox. ODCopper WeightApprox. WeightDC Resistance @ 25°CAC Resistance @ 75°CInductive RectanceMin Bending RadiusAllowable Ampacity 75°CAllowable Ampacity 90°C
    AWGNo.strandsmilmilinchlb/1000ftlb/1000ftΩ/1000ftΩ/1000ftΩ/1000ftinchAmpAmp
    14 AWG
    TBA142730450.35238802.6313.1700.0581.42025
    599457143730450.38837862.6313.1700.0581.62025
    599458144730450.423501072.6313.1700.0581.71620
    599459145730450.461621292.6313.1700.0581.81620
    595479147730450.502871702.6313.1700.0582.01417
    599460149730600.6161122322.6313.1700.0582.51417
    5994611412730600.6921502992.6313.1700.0582.81012
    TBA1415730600.7342043582.6313.1700.0582.91012
    5954751419730600.8042374342.6313.1700.0583.21012
    TBA1425730800.9423325912.6313.1700.0583.8911
    TBA1430730800.9953966882.6313.1700.0584.0911
    TBA1437730801.0724868252.6313.1700.0585.4810
    12 AWG
    595635122730450.46640861.6622.0020.0541.92530
    595472123730450.466611151.6622.0020.0541.92530
    595636124730450.466811481.6622.0020.0541.92024
    5954771212730600.4662444101.6622.0020.0541.91215
    592111125730450.5431011981.6622.0020.0542.22024
    TBA127730600.5661622631.6622.0020.0542.31721
    596919129730600.5891833191.6622.0020.0542.41721
    TBA1215730600.8193255021.6622.0020.0543.31215
    TBA1219730800.9024066461.6622.0020.0543.61215
    TBA1225730801.0505288261.6622.0020.0545.31113
    TBA1230730801.1116309671.6622.0020.0545.61113
    TBA1237730801.19877211631.6622.0020.0546.01012
    10 AWG
    595632102730450.466641161.0401.2530.0501.93540
    6457261012730800.4663886151.0401.2530.0501.91720
    595556103730450.478971611.0401.2530.0501.93540
    595633104730450.5561292231.0401.2530.0502.22832
    TBA105730600.5891932911.0401.2530.0502.42832
    TBA107730600.6412583761.0401.2530.0502.62428
    TBA109730600.7473234681.0401.2530.0503.02428
    TBA1015730800.9775177641.0401.2530.0503.91720
    TBA1019730801.0276469291.0401.2530.0505.11720
    TBA1025730801.20084011931.0401.2530.0506.01518
    TBA1030730801.271100214011.0401.2530.0506.41518
    TBA1037730801.373122816931.0401.2530.0506.91416
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    *Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
    *Ampacities have been adjusted for more than Three Current-Carrying Conductors.

    Revision: 1.000.007

    Updated On: July 3, 2024, 10:13 p.m. UTC