SPEC 44140

3/C CU 2000V EPDM/CPE Type G-GC Industrial Grade Cable 90°C. MSHA Approved

Flexible Copper conductors, Ethylene Propylene Diene Monomer (EPDM) insulation, Single Layer Chlorinated Polyethylene (CPE) Jacket

...

Construction:

  1. Conductor:Bare, soft drawn, annealed, flexible, rope-lay stranded copper per ASTM B3/B172
  2. Separator Tape:Non-conducting tape applied between the conductor and insulation to facilitate stripping
  3. Insulation:Ethylene Propylene Diene Monomer (EPDM). Color coded black, white, red
  4. Ground Check:One insulated, bare, soft drawn, annealed, rope stranded, flexible lay copper per ASTM B3/B172
  5. Ground Conductors:Two insulated, bare, soft drawn, annealed, rope stranded, flexible lay copper per ASTM B3/B172
  6. Fillers:Paper fillers applied as needed to round the cable core
  7. Reinforcement Binder:Reinforcing binder with twine applied over the core
  8. Jacket:Black, flame resistant, thermosetting Chlorinated Polyethylene (CPE)

Applications and Features:

Southwire Type G-GC cable is a heavy-duty industrial cable for use in flexible, portable, and extra-hard usage applications where equipment grounding is required per NEC Article 400. Suitable for continuous submersion in water – ideal for submersible pumps, marine application. Also suitable for use in light to medium-duty mining applications. Sunlight and oil resistant. Highly flexible and easy to work with in cold conditions. Not for use as permanent building wiring. Meets FT-5 Flame Test. cUL Listed.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B172 Standard Specification for Rope-Lay-Stranded Copper Conductors Having Bunch-Stranded Copper Conductors
  • UL 1650 Standard for Portable Power Cable
  • CSA C22.2 No. 96 Portable Power Cables
  • RoHS-2 (European Directive 2011/65/EU)
  • Sample Print Legend:

    SOUTHWIRE(R) ROYAL(R) XXX AWG (XX.XXmm2) 3/C TYPE G-GC PORTABLE POWER CABLE E172226 (UL) 2000V 90C DRY 90C WET OIL RESISTANT 60(D)C SUN RES -- 156205 CSA TYPE G-GC 2000V -40C FT1 FT5 P-07-KA110009-MSHA (MADE IN USA)
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. NumberCond. StrandsDiameter Over ConductorInsul. ThicknessGroundGround Check SizeJacket ThicknessApprox. ODApprox. WeightJacket Color
    AWG/KcmilNo.No.inchmilNo. x AWGAWGmilinchlb/1000ft
    5701031031040.125602 x 121x121200.788408BK
    56053783710.145602 x 101x101450.980655BK
    55816863650.186602 x 101x101451.055815BK
    558169431120.235602 x 81x81301.1721116BK
    558170231680.290602 x 71x81651.2891405BK
    570098132240.300802 x 61x81451.4551733BK
    5581651/032590.379802 x 51x81851.6602096BK
    5581662/033240.400802 x 41x82151.7042519BK
    5600653/034180.480802 x 31x82051.8303015BK
    5581674/035320.530802 x 21x81751.9703710BK
    57023925036080.605952 x 11x82602.2844691BK
    55928135038550.670952 x 1/01x83302.6816135BK
    570243500312210.858952 x 3/01x82902.8918028BK
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CInductive ReactanceMin Bending RadiusAllowable Ampacity In Air 60°CAllowable Ampacity In Air 75°CAllowable Ampacity In Air 90°C
    AWG/KcmilΩ/1000ftΩ/1000ftΩ/1000ftinchAmpAmpAmp
    101.0811.3020.0503.1374349
    80.6790.8180.0523.9485765
    60.4350.5240.0515.2637787
    40.2740.3300.0485.884101114
    20.1720.2070.0456.4112133152
    10.1370.1640.0467.2131156177
    1/00.1090.1310.0448.3151181205
    2/00.0870.1040.0438.5174208237
    3/00.0690.0830.0429.1201241274
    4/00.0550.0670.0419.8232277316
    2500.0470.0570.04113.7259310352
    3500.0330.0420.04016.0318381433
    5000.0230.0310.03917.3392470536
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.

    Revision: 1.000.002

    Updated On: June 19, 2025, 7:23 p.m. UTC