SPEC 25079

SIMpull™ AL 600V XLPE Insulation. RW90

Single 8000 Series Aluminum Conductor, 600V Alumaflex Strand, No. 6 AWG to 1000 KCMIL, FT4 Flame Test Rating - (in all colours), 90°C MAX -40°C MIN, Sunlight Resistant

...

Construction:

  1. Conductor:8000 Series ACM Aluminum Class B stranded conductor.
  2. Insulation:Crosslinked Polyethylene (XLPE) insulation with SIMpull®

Applications and Features:

Southwire's SIMpull ® aluminum RW90 is for open wiring used in raceways (except cabletroughs and ventilated flexible cableways) in dry or wet locations. For open wiring exposed to the weather. Minimum recommended installation temperature minus 40°C (with suitable handling procedures). Maximum conductor temperature 90°C.

Specifications:

  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • CSA Standard C22.2 No. 38 File Listing LL90458
  • Sample Print Legend:

    SOUTHWIRE® XXXX KCMIL NOLUBE® SIMpull RW90{TM} LL90458 {CSA} XXX.XX {mm2}) COMPACT AL. --- AlumaFlex {TM} AA8176 RW90 XLPE 600 VOLTS (-40°C) SR - MADE UNDER US PATENT NOS 7411129 & 7557301-RW90 500 KCMIL FT4 {MMM/DD/YYYY} - OPERATOR NAME SEQUENTIAL METER MARKS
    Table 1 – Weights and Measurements
    Cond. SizeStrandInsul. ThicknessInsulation ColorApprox. ODApprox. WeightMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity In Raceway 90°C
    AWG/KcmilNo.milinchlb/1000ftinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmp
    2745BK0.358881.43980.2660.3310.045100
    1855BK0.4091141.65020.2110.2630.046115
    1/01055BK0.4461371.86330.1670.2080.044135
    2/01255BK0.4861671.97980.1330.1660.043150
    3/01655BK0.5332052.110060.1050.1310.042175
    4/01955BK0.5852512.312690.0840.1050.041205
    2502265BK0.653022.615000.070.0870.041230
    3503565BK0.746407321000.0510.0640.04280
    4003565BK0.7894593.224000.0440.0550.04305
    5003565BK0.8665633.530000.0360.0450.039350
    7505880BK1.0688465.345000.0230.030.038435
    10005880BK1.27711116.460000.0170.0230.037500
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Weights and Measurements (Metric)
    Cond. SizeStrandInsul. ThicknessInsulation ColorApprox. ODApprox. WeightMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity In Raceway 90°C
    AWG/KcmilNo.mmmmkg/kmmmnewtonΩ/kmΩ/kmΩ/kmAmp
    271.14BK9.0913135.5617710.871.090.1476100
    181.40BK10.3917040.6422340.690.860.1509115
    1/0101.40BK11.3320445.7228170.550.680.1444135
    2/0121.40BK12.3424948.2635510.440.540.1411150
    3/0161.40BK13.5430553.3444770.340.430.1378175
    4/0191.40BK14.8637458.4256470.280.340.1345205
    250221.65BK16.5144966.0466750.230.290.1345230
    350351.65BK18.9560676.2093450.170.210.1312280
    400351.65BK20.0468381.28106800.140.180.1312305
    500351.65BK22.0083888.90133500.120.150.1280350
    750582.03BK27.131259134.62200250.080.100.1247435
    1000582.03BK32.441653162.56267000.060.080.1214500
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.