SPEC 42065

SRG-K CONTROL CABLES

Flexible Silicone Rubber Glass Braid Conductors with an Overall Aramid Fiber Jacket, Temp Rating 200°C, 600V

...

Construction:

  1. Conductor:Stranded tinned, annealed copper per ASTM B33
  2. Insulation:Silicone Rubber with a fiberglass braid over the insulation
  3. Cabling:Conductors are cabled with a left hand lay and bound with a polyester tape
  4. Jacket:K-Fiber braid, treated with a high temperature saturant, covers the core

Applications and Features:

Used for equipment wiring, as well as signal and control circuits. Ideal in locations where high temperature or hazardous conditions exist that require heat resistance at 600 volts.

K Fiber Jacket provides improved mechanical strength and abrasion resistance. Flexible. Good chemical strength. Excellent electrical properties. Passes IEEE 383 70,000 BTU/Hr Flame test while maintaining circuit integrity.

Specifications:

  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • IEEE 383 Flame Test (70,000 btu)
  • RoHS-3 Complies with European Directive 2015/863
  • Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. NumberInsul. ThicknessApprox. ODApprox. WeightTemp. RatingStandard (UL or other)
    AWG/KcmilNo.milinchlb/1000ft°CStyle/Type
    C51200142300.37555200Non-UL
    C51205143300.40075200Non-UL
    C51210144300.435100200Non-UL
    C51215145300.480125200Non-UL
    C51220147300.520170200Non-UL
    C512301412300.690280200Non-UL
    C512401419300.810415200Non-UL
    C512501437301.100810200Non-UL
    C51300122300.41075200Non-UL
    C51305123300.430110200Non-UL
    C51310124300.475145200Non-UL
    C51315125300.520175200Non-UL
    C51320127300.570240200Non-UL
    C513301212300.755410200Non-UL
    C513401219300.890625200Non-UL
    C513501237301.2501250200Non-UL
    C51400102450.525125200Non-UL
    C51405103450.555180200Non-UL
    C51410104450.615235200Non-UL
    C51415105450.675300200Non-UL
    C51420107450.740385200Non-UL
    C514301012450.990685200Non-UL
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Table 2 – Weights and Measurements (Metric)
    Stock NumberCond. SizeCond. NumberInsul. ThicknessApprox. ODApprox. WeightTemp. RatingStandard (UL or other)
    AWG/KcmilNo.mmmmkg/km°CStyle/Type
    C512001420.769.5282200Non-UL
    C512051430.7610.16112200Non-UL
    C512101440.7611.05149200Non-UL
    C512151450.7612.19186200Non-UL
    C512201470.7613.21253200Non-UL
    C5123014120.7617.53417200Non-UL
    C5124014190.7620.57618200Non-UL
    C5125014370.7627.941205200Non-UL
    C513001220.7610.41112200Non-UL
    C513051230.7610.92164200Non-UL
    C513101240.7612.07216200Non-UL
    C513151250.7613.21260200Non-UL
    C513201270.7614.48357200Non-UL
    C5133012120.7619.18610200Non-UL
    C5134012190.7622.61930200Non-UL
    C5135012370.7631.751860200Non-UL
    C514001021.1413.33186200Non-UL
    C514051031.1414.10268200Non-UL
    C514101041.1415.62350200Non-UL
    C514151051.1417.15446200Non-UL
    C514201071.1418.80573200Non-UL
    C5143010121.1425.151019200Non-UL

    Revision: 1.000.000