SPEC 48318

Copper-Clad Steel Type E Messenger

Concentric-Lay Stranded Copper and Copper-Clad Steel Composite Conductor

...

Construction:

  1. Core:30% conductivity copper-clad steel wire stranded core
  2. Stranding:Hard-drawn bare copper wires per ASTM B1

Applications and Features:

Copper-Clad Composite Type E conductors are designed for use as neutral messengers for aerial cables, catenary messengers, and ground and power conductors for electrified railroads. Features higher tensile strength with minimal sag compared to solid copper. Resistant to permanent stretch caused by seasonal changes in temperature and less susceptible to cracking from repeated flexing and mechanical vibration.

Specifications:

  • ASTM B1 Hard-Drawn Copper
  • ASTM B227 Standard for Hard-Drawn Copper-Clad Steel Wire
  • ASTM B229 Concentric-Lay-Stranded Copper and Copper-Clad Steel Composite Conductors
  • Stock
    Number
    Conductor
    Size
    Diameter
    Over
    Conductor
    Conductor
    Area
    Number & Diameter of
    EHS 30% CCS Wire
    Number & Diameter of
    Hard Drawn Cu Wire
    Minimum
    Breaking
    Strength
    WeightDC Resistance
    @ 20°C
    AWG/kcmilinchcmilnum x inchnum x inchlblb/1000ftΩ/1000ft
    4594014/00.6132116007 x 0.122512 x 0.1225207308540.05199

    All dimensions are nominal and subject to normal manufacturing tolerances.


    Revision: 1.000.007

    Updated On: Feb. 10, 2026, 3:33 p.m. UTC