SPEC 47210

3/C CU 2000V Type G-GC RHINOFLEXTM CPE Mining Cable 90°C. MSHA Approved

Flexible Copper conductors, Ethylene Propylene Rubber (EPR) insulation, Extra Heavy Duty Two Layer Chlorinated Polyethylene (CPE) Jacket with Optional Reflective Stripes

...

Construction:

  1. Conductor: Tin coated, soft drawn, annealed, flexible, rope-lay stranded copper per ASTM B33/B172
  2. Separator Tape: Non-conducting tape applied between the conductor and insulation to facilitate stripping and Ethylene Propylene Rubber (EPR), color coded black, white, red.
  3. Ground Conductors: Two mylar taped, tin coated, soft drawn, annealed, rope stranded, flexible lay copper per ASTM B33/B172
  4. Ground Check Conductor: Tin coated, soft drawn, annealed, rope stranded, flexible lay copper per ASTM B33/B172 with yellow, high durometer, Ethylene Propylene Rubber (EPR) insulation.
  5. Filler:Filler as needed
  6. Binder: Binder Tape
  7. Inner Jacket:Black, mold cured, extra heavy-duty integral fill flame resistant, thermosetting Chlorinated Polyethylene (CPE)
  8. Reinforcement:Reinforcing twine applied between the two jacket layers
  9. Outer Jacket:Black, mold cured, extra heavy-duty, modified integral fill, flame resistant, thermosetting Chlorinated Polyethylene (CPE). Alternate jacket colors available
  10. Reflective Stripe:Highly visible reflective stripe embedded into the outer jacket to increase safety and help prevent cable runover (optional, contact your sales representative for part number)

Applications and Features:

RHINOFLEXTM Type G-G cable is a heavy-duty cable for use where flexibility and maximum protection is required. For use with all portable, temporary, and permanent power applications such as mobile or stationary mining equipment, shuttle cars, mobile drills, pumps, roof bolters, conveyors, and any portable power where equipment grounding is required, It is ideal for use anytime extra-durable, flexible cable is required. Also suitable for continuous submersion in water. Ground check conductor provides fail-safe ground monitoring. Embossed print legend for easy cable identification. Cold Bend and Impact Tested to -50°C.

Specifications:

  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • ASTM B172 Standard Specification for Rope-Lay-Stranded Copper Conductors Having Bunch-Stranded Copper Conductors
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • Sample Print Legend:

    SOUTHWIRE (R) RHINOTM BRAND CABLE # AWG 3/C TYPE G-GC PORTABLE POWER CABLE 90°C WET OR DRY 2000V FT5 -50°C P-07-KA140024 MSHA
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. NumberCond. StrandsDiameter Over ConductorInsul. ThicknessDiameter Over InsulationGroundGround Check SizeInner Jacket ThicknessJacket ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.No.inchmilinchNo. x AWGAWGmilmilinchlb/1000ft
    591266831680.153600.2872 x 1010551451.026661
    585557631330.198600.3361 x 101055951.050789
    585028432590.235600.3881 x 81060951.1901014
    585725233080.302600.4522 x 7865901.3251413
    589268133850.347800.5292 x 68701201.5101724
    592479^1/032730.385800.5512 x 58651601.6502316
    5857262/033240.400800.5942 x 48851001.6362401
    5871974/035320.550800.7511 x 28801352.0403715
    59019925036080.6821000.8161 x 281001202.3904386
    58753135038550.8091000.9262 x 1/081001252.6805801
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    ^ Orange outer jacket
    Table 2 – Electrical and Engineering Data
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CInductive ReactanceWorking TensionMin Bending RadiusAllowable Ampacity In Air 90°C
    AWG/KcmilΩ/1000ftΩ/1000ftΩ/1000ftlbinchAmp
    80.7150.9030.0361128.259
    60.4500.5680.0341798.479
    40.2820.3560.0332859.5104
    20.1790.2260.03145310.6138
    10.1430.1800.03157212.0161
    1/00.1090.1420.03074613.2186
    2/00.0900.1140.03091013.0215
    4/00.0570.0730.029144716.3287
    2500.0480.0620.026171019.1320
    3500.0350.0460.025239421.4394
    * Ampacities based upon ICEA S-75-381 Table H-1.
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.

    Revision: 1.000.004

    Updated On: July 3, 2024, 9:53 p.m. UTC