SPEC 60440

EZ-QUICK™ MC Modular Cable Assembly

14 AWG through 10 AWG THHN/THWN Insulated Singles. Green Insulated Ground. UL Listed. 600 Volts. Rated VW-1. Lightweight Aluminum Interlocked Armor. Includes UL Listed Fittings and Prepared Cable Ends.

...

Construction:

  1. Conductor:Class B compressed stranded copper per ASTM B3 and ASTM B8
  2. Insulation:All phases are insulated with Polyvinyl Chloride with Nylon Sheath Type THHN/THWN
  3. Ground: Green insulated copper ground
  4. Binder:Binder tape bearing the print legend is wrapped around the cable assembly
  5. Connector:Zinc die-cast snap on connector
  6. Armor:Aluminum Interlocked Armor

Applications and Features:

Southwire EZ QUICK™ Modular Cable Assemblies are suitable for use as follows:
  • Branch, feeder and service power distribution in commercial, industrial, institutional, and multi-residential buildings.
  • Fished or embedded in plaster.
  • Concealed or exposed installations.
  • Environmental air-handling spaces per NEC 300.22 (C).
  • Places of Assembly per NEC 518.4 and theaters per NEC 520.5.
  • Installation in cable tray and approved raceways.
  • Under raised floors for information technology equipment conductors and cables per NEC 645.5(D) & 645.5(D)(2)
  • Class I Div. 2, Class II Div 2, & Class III Div. 1 Hazardous Locations.

  • Southwire EZ QUICK™ Modular Cable Assemblies - meets or exceeds the following requirements:
  • UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com )
  • Federal Specification A-A59544 (formerly J-C-30B)
  • NFPA 70 (National Electrical Code), Article 330
  • Listed for use in UL 1, 2 and 3 Hour Through Penetration Firestop Systems
  • REACH/RoHS-2 (Chemical Limit) Compliant

  • Southwire EZ QUICK™ Modular Cable Assemblies Features:
  • Reduces installation costs up to 50% over pipe and wire.
  • Lightweight aluminum armor--as much as 45% lighter than steel MC Cable.
  • Better grounding performance than Type AC
  • Pre-cut lengths eliminate on-site preparation and save installation and clean up time.
  • Pre-stripped conductors increase jobsite safety
  • UL Listed snap-in fittings applied to each end
  • UL Classified 1, 2, and 3 hour Through Penetration Firestop Systems: W-J-3037, W-L-3110, W-L-3113, W-L-3117, W-L-3120, W-L-3121, W-L-3160, C-AJ-3115, C-AJ-3140, C-AJ-3142, C-AJ-3145, C-AJ-3173, C-AJ-3202, C-AJ-4065, C-AJ-4066, F-C-3038.
  • Cable reverse wound on reel for ease of pulling and installation. When pulling from coils, pull from inside to ensure ease of installation.
  • Anti-short bushings are not required for use with MC cable per the NEC and UL
  • Specifications:

  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 1569 Metal-Clad Cables
  • UL 1479 Standard for Safety Fire Tests of Penetration Firestops
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • Buy American: Compliant with Buy American Requirements, found in 49 U.S.C. § 5323(j); specify “Made in the USA Only!” when ordering to ensure your project receives American made products.
  • Sample Print Legend:

    XX-X CU THHN BLACK/WHITE ALUMINUM MC EZ QUICK WHIP XX'

    Whip Assemblies

    Stock CodeSize AWGCond. NumSolid/StrandedColorLength ft
    564820122SolidBK, WE, GN5
    672716122SolidBK, WE, GN6
    672715122SolidBK, WE, GN7
    564821122SolidBK, WE, GN8
    564822122SolidBK, WE, GN10
    564824122SolidBK, WE, GN12
    564825122SolidBK, WE, GN15
    564826122SolidBK, WE, GN20
    564827122SolidBK, WE, GN25
    564829123SolidBK, WE, RD, GN8
    564830123SolidBK, WE, RD, GN10
    564832123SolidBK, WE, RD, GN12
    564847123SolidBK, WE, RD, GN15
    564848123SolidBK, WE, RD, GN20
    564850123SolidBK, WE, RD, GN25
    589476122StrandedBK, WE, GN8
    589477122StrandedBK, WE, GN10
    589478122StrandedBK, WE, GN12
    589479122StrandedBK, WE, GN15
    562096122StrandedBK, WE, GN15