SPEC 85004

Multi-Conductor CU 600 V FR-XLPE PVC Jacket Control Cable Color Method 1 Table 1

Control Cable, 600 Volt, Copper Conductors, Flame Retardant Cross Linked Polyethylene (FR-XLPE) Insulation, Polyvinyl Chloride (PVC) Jacket, Control Cable Conductor Identification Method 1 Table 1. Silicone Free

...

Construction:

  1. Conductor:7-strand, class B, compressed, bare copper per ASTM B3 and B8
  2. Insulation:Flame Retardant Cross Linked Polyethylene (FR-XLPE)
  3. Filler:Polypropylene filler on cables with 5 or less conductors
  4. Binder:Polypropylene binder tape applied for cables with more than 5 conductors
  5. Rip Cord:Rip cord for ease of jacket removal
  6. Overall Jacket:Polyvinyl Chloride (PVC)

Applications and Features:

Southwire’s 600 Volt control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. UL rated constructions can be used in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. UL rated constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • CSA CSA marking is available upon request
  • CSA C22.2 No.230 Tray Cables - Rated TC-ER
  • ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 1
  • ICEA S-73-532 Control, Thermocouple Extension, and Instrumentation Cables (applicable to sizes 20-9 AWG conductors)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Vertical Tray Flame Test (70,000 Btu/hr) and ICEA T-29-520 - (210,000 Btu/hr)
  • VW-1 (Vertical-Wire) Flame Test
  • Sample Print Legend:

    UL Listed:
    SOUTHWIRE E75755 {UL} XX AWG X/C FR-XLPE (XHHW-2) CDRS 90°C PVC JKT 600V TYPE TC-ER SUN. RES. DIRECT BURIAL YEAR {SEQUENTIAL FOOTAGE MARKS} SEQ FEET

    CSA Listed:
    SOUTHWIRE #P 156205 CSA XX AWG X/C FR-XLPE CDRS 90C PVC JACKET, -40C, FT-4, SUN RES, DIR BUR, 600V {MM/DD/YYYY} {SEQUENTIAL FOOTAGE MARKS} SEQ FEET

    Non UL Listed:
    SOUTHWIRE XX AWG X/C FR-XLPE CDRS 90C PVC JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600V {MM/DD/YYYY} {SEQUENTIAL FOOTAGE MARKS} SEQ FEET

    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. NumberCond. StrandsDiameter Over Cond.Insul. ThicknessJacket ThicknessApprox. ODCopper WeightApprox. WeightDC Resistance @ 25°CAC Resistance @ 75°CInductive RectanceMin Bending RadiusAllowable Ampacity 75°CAllowable Ampacity 90°CJacket Color
    AWGNo.strandsinchmilmilinchlb/1000ftlb/1000ftΩ/1000ftΩ/1000ftΩ/1000ftinchAmpAmp
    18 AWG
    62417718270.04625450.29410406.6698.2770.0361.2-14BK
    62030918470.04625450.33520616.6698.2770.0361.3-11BK
    62417618770.04625450.39235916.6698.2770.0361.6-10BK
    604208181270.04630600.588611766.6698.2770.0362.4-7BK
    14 AWG
    618791^14370.07130450.3938962.6313.2650.0581.62025BK
    TBA14570.07130450.45661252.6313.2650.0581.81620BK
    TBA14670.07130450.489791462.6313.2650.05821620BK
    61948114770.07130450.503901762.6313.2650.05821418BK
    619483^14970.07130600.6021152352.6313.2650.0582.41418BK
    664329^141270.07145600.8171543752.6313.2650.0583.31012BK
    12 AWG
    62030612270.08930450.404611151.6622.0630.0541.62530BK
    619487^12470.08930450.40441901.6622.0630.0541.62024BK
    619488^12370.08930450.429611221.6622.0630.0541.72530BK
    619489^12470.08930450.468811551.6622.0630.0541.92024BK
    61949212770.08930600.5891432601.6622.0630.0542.41821BK
    604283^121270.08930600.7672444201.6622.0630.0543.11215BK
    620307121270.08930600.7672444201.6622.0630.0543.11215BK
    10 AWG
    60401810270.11330450.452651251.041.2910.051.83540BK
    60428210270.11330450.452651371.041.2910.051.83540BK
    672864^10370.11330450.4811292071.041.2910.051.93540BK
    62076410370.11330450.481971731.041.2910.051.93540BK
    619088^†10470.11330450.511292111.041.2910.0522832BK
    604410^@104190.11330600.5581292361.041.2910.052.22832BK
    604284^†10470.11330600.5581292371.041.2910.052.22832BK
    619090^†10570.11330600.5911622821.041.2910.052.42832BK
    661859†10770.11330600.6572273651.041.2910.052.62428BK
    628428^10770.11330600.6612273641.041.2910.052.62428BK
    619498^10870.11330600.7162594131.041.2910.052.92428BK
    67308410970.11330600.7692914631.041.2910.053.12428BK
    576597^@†1012190.11330800.9043886221.041.2910.053.61820BK
    606676^†101270.11330800.9093886341.041.2910.053.61820BK
    8 AWG
    619504!8270.14245600.6021032100.6530.810.0522.45055BK
    619507^8370.14245600.641543000.6530.810.0522.65055BK
    619508^8470.14245600.72063580.6530.810.0522.84044BK
    6 AWG
    619511!6270.17845600.6741642900.4110.510.0512.76575BK
    619512^6370.17845600.7182464110.4110.510.0512.96575BK
    619514^6470.17845600.7873275270.4110.510.0513.15260BK
    4 AWG
    619517^4370.22545600.8113905780.2580.320.0483.28595BK
    619518^4470.22545800.9335217650.2580.320.0483.76876BK
    2 AWG
    6195242370.28345800.9876218860.1620.2010.0453.9115130BK
    6616762470.28345801.08282811380.1620.2010.0455.492104BK
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    ^ UL listed part number
    ! UL listed TC rated (not TC-ER)
    @ Combination unilay stranded per ASTM B787
    † Polyester flat thread binder
    • Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements. Ampacities have been adjusted for stock numbers containing more than Three Current-Carrying Conductors.
    • TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.