SPEC 81112

15kV AL 133% TRXLPE One-Third Neutral LLDPE

Single Conductor, 220 Mils Tree Retardant Cross Linked Polyethylene, 133% Insulation Level, One-third Concentric Neutral, Linear Low Density Polyethylene (LLDPE) Jacket. Silicone Free

...

Construction:

  1. Conductor:Moisture blocked class B compressed Aluminum ASTM B231 1350 ¾ hard H16/H26 ( Non Moisture Blocked Optional )
  2. Conductor Shield:Conventional Semi-conducting cross-linked copolymer; Supersmooth conductor shield optional; A conductor tape is used for cable size larger than or equal to 1500 Kcmil
  3. Insulation:220 Mils Tree Retardant Cross Linked Polyethylene 133% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Concentric Neutral:Helically applied soft drawn bare copper one-third concentric neutral
  6. Overall Jacket:Linear Low Density Polyethylene (LLDPE) Jacket, black with red extruded stripes; PowerGlide® LLDPE jacket optional

For information about our Cable-Rejuvenation Services please visit us at:  Cable-Rejuvenation Services
You can email us at: Cable-Rejuvenation Services

Applications and Features:

Southwire's 15kV cables are suited for use in wet and dry areas, conduits, ducts, direct burial, sunlight, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation. 130°C for emergency overload, and 250°C for short circuit conditions. Jacket types available that can be installed in conduit without the aid of lubrication. Rated for 1000 lbs./FT maximum sidewall pressure.

Novinium, a Southwire Company, offers CableCure® services to extend the life of primary underground cables. Visit Novinium

Specifications:

  • ASTM B231 Standard Specification for Concentric-Lay-Stranded Aluminum 1350 Conductors
  • ASTM B609 Standard Specification for Aluminum 1350 Round Wire, Annealed and Intermediate Tempers, for Electrical Purposes
  • ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5 - 46kV
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Rural Utility Standard RUS 1728F-U1 or 1728.204 (Electric standards and specifications for materials and construction)
  • UL 1072 Listed as MV 90 When Specified
  • Optional CSA 68.5: -40ºC and MV 90ºC optional marking available upon request
  • Sample Print Legend:

    SOUTHWIRE HI-DRI(R) [CONDUCTOR SIZE] [AWG or KCMIL] AL 15000 VOLTS TRXLPE INSULATION 220 MILS -- (NESC) -- SOUTHWIRE {MMM} {YYYY} NON-CONDUCTING JACKET
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralNeutral DC Resistance 25°CJacket ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull Tension
    AWG/KcmilinchinchmilinchNo. x AWGΩ/1000ftmilinchlb/1000ftinchlb
    5114032 (Solid)0.2570.7282200.8186x140.438501.0464698.4398
    6117002 (7)0.2820.7602200.8506x140.438501.0784638.6398
    TBA1 (Solid)0.2890.7672200.8576x140.438501.0855258.7502
    TBA1 (19)0.3220.8002200.8906x140.438501.1185438.9502
    TBA1/0 (Solid)0.3240.8022200.8926x140.438501.1205659.0633
    6117821/0 (19)0.3510.8222200.9126x140.438501.1405629.1633
    6278602/0 (19)0.3950.8652200.9557x140.375501.1836249.5798
    6202912/0 (19)0.3950.8652200.95510x140.263501.1836609.5798
    TBA3/0 (19)0.4430.9212201.0119x140.292501.2397299.91006
    613449†4/0 (19)0.4980.9682201.05811x140.239501.28680310.31269
    6133654/0 (19)0.4980.9682201.05811x140.239501.28680310.31269
    663916250 (37)0.5581.0382201.14813x140.202501.37693011.01500
    613615350 (37)0.6611.1412201.25118x140.146501.479114711.82100
    683847500 (37)0.7891.2692201.37916x120.103751.640149113.13000
    604179500 (37)0.7891.2692201.37916x120.103801.700155513.63000
    604102750 (61)0.9681.4582201.56824x120.069751.883207515.14500
    661909††750 (61)0.9681.4582201.56815x100.069751.925210215.44500
    610191†††750 (61)0.9681.4582201.56815x100.069751.925207415.44500
    6124941000 (61)1.1171.6072201.74720x100.052752.104267016.86000
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Pulling tension based on pulling eye directly connected to conductor
    † HiDri Plus: Moisture absorbing powder under jacket
    †† PowerGlide: Low coefficient jacket can be installed in duct without the aid of lubrication.
    ††† Non moisture block
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzCharging CurrentDielectric LossZero Sequence ImpedancePositive Sequence ImpedanceShort Circuit Current @ 30 CycleAllowable Ampacity in Duct 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftA/1000ftW/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    2 (Solid)0.1620.2040.0610.0540.1410.40.257 + j1.2780.204 + j0.5722092120150
    2 (7)0.2660.3360.0580.0520.1470.40.389 + j1.2200.336 + j0.5162092120150
    1 (Solid)0.1290.1620.0570.0520.1490.40.215 + j1.2070.162 + j0.5042092140175
    1 (19)0.2110.2660.0540.0500.1590.40.319 + j1.1480.266 + j0.4472092140175
    1/0 (Solid)0.1020.1280.0530.0500.1600.40.181 + j1.1430.128 + j0.4432092155195
    1/0 (19)0.1670.2110.0500.0490.1700.40.264 + j1.1040.211 + j0.4052092155195
    2/0 (19)0.1330.1670.0470.0470.1830.50.221 + j1.0530.167 + j0.3552441180220
    2/0 (19)0.1330.1670.0470.0470.1830.50.221 + j1.0560.167 + j0.3553487180220
    3/0 (19)0.1050.1320.0440.0450.1950.50.186 + j1.0080.132 + j0.3113138200250
    4/0 (19)0.0840.1050.0400.0440.2150.60.159 + j0.9670.105 + j0.2713836235285
    4/0 (19)0.0840.1050.0400.0440.2150.60.159 + j0.9670.105 + j0.2713836235285
    250 (37)0.0710.0900.0360.0420.2350.60.144 + j0.9290.090 + j0.2384533256309
    350 (37)0.0500.0650.0320.0400.2650.70.119 + j0.8810.065 + j0.1946277310370
    500 (37)0.0350.0460.0280.0390.3040.80.100 + j0.8360.046 + j0.1568865370445
    500 (37)0.0350.0460.0280.0390.3040.80.100 + j0.8340.046 + j0.1578865370445
    750 (61)0.0240.0330.0240.0370.3600.90.087 + j0.7920.033 + j0.12113298460525
    750 (61)0.0240.0330.0240.0380.3600.90.087 + j0.7900.033 + j0.12213211460525
    750 (61)0.0240.0330.0240.0380.3600.90.087 + j0.7900.033 + j0.12213211460525
    1000 (61)0.0180.0260.0210.0360.4041.00.080 + j0.7640.026 + j0.10117615520575
    *Ampacities for Direct Buried are based on ICEA P-117-734-2016 Single-Conductor Solid Dielectric 15-35kV. Single Circuit Flat Direct Buried Figure 3
    *Ampacities for Duct are based on ICEA P-117-734-2016 for Single-Conductor Solid Dielectric 15-35kV. Single Circuit Trefoil Conduit Figure 7.
    *Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft, Spacing: one diameter spacing center-to-center.
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralNeutral DC Resistance 25°CJacket ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull Tension
    AWG/KcmilmmmmmmmmNo. x AWGΩ/kmmmmmkg/kmmmnewton
    5114032 (Solid)6.5318.495.5920.786x141.441.2726.57698213.361771
    6117002 (7)7.1619.305.5921.596x141.441.2727.38689218.441771
    TBA1 (Solid)7.3419.485.5921.776x141.441.2727.56781220.982234
    TBA1 (19)8.1820.325.5922.616x141.441.2728.40808226.062234
    TBA1/0 (Solid)8.2320.375.5922.666x141.441.2728.45841228.602817
    6117821/0 (19)8.9220.885.5923.166x141.441.2728.96836231.142817
    6278602/0 (19)10.0321.975.5924.267x141.231.2730.05929241.303551
    6202912/0 (19)10.0321.975.5924.2610x140.861.2730.05982241.303551
    TBA3/0 (19)11.2523.395.5925.689x140.961.2731.471085251.464477
    613449†4/0 (19)12.6524.595.5926.8711x140.781.2732.661195261.625647
    6133654/0 (19)12.6524.595.5926.8711x140.781.2732.661195261.625647
    663916250 (37)14.1726.375.5929.1613x140.661.2734.951384279.406675
    613615350 (37)16.7928.985.5931.7818x140.481.2737.571707299.729345
    683847500 (37)20.0432.235.5935.0316x120.341.9141.662219332.7413350
    604179500 (37)20.0432.235.5935.0316x120.342.0343.182314345.4413350
    604102750 (61)24.5937.035.5939.8324x120.231.9147.833088383.5420025
    661909††750 (61)24.5937.035.5939.8315x100.231.9148.893128391.1620025
    610191†††750 (61)24.5937.035.5939.8315x100.231.9148.893086391.1620025
    6124941000 (61)28.3740.825.5944.3720x100.171.9153.443973426.7226700
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Pulling tension based on pulling eye directly connected to conductor
    † HiDri Plus: Moisture absorbing powder under jacket
    †† PowerGlide: Low coefficient jacket can be installed in duct without the aid of lubrication.
    ††† Non moisture block
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzCharging CurrentDielectric LossZero Sequence Impedance*Positive Sequence Impedance*Short Circuit Current @ 30 CycleAllowable Ampacity in Duct 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilΩ/kmΩ/kmMΩ*kmΩ/kmA/kmW/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    2 (Solid)0.53150.670.01860.17720.4631.31230.257 + j1.2780.204 + j0.5722092120150
    2 (7)0.87271.100.01770.17060.4821.31230.389 + j1.2200.336 + j0.5162092120150
    1 (Solid)0.42320.530.01740.17060.4891.31230.215 + j1.2070.162 + j0.5042092140175
    1 (19)0.69230.870.01650.16400.5221.31230.319 + j1.1480.266 + j0.4472092140175
    1/0 (Solid)0.33460.420.01620.16400.5251.31230.181 + j1.1430.128 + j0.4432092155195
    1/0 (19)0.54790.690.01520.16080.5581.31230.264 + j1.1040.211 + j0.4052092155195
    2/0 (19)0.43640.550.01430.15420.6001.64040.221 + j1.0530.167 + j0.3552441180220
    2/0 (19)0.43640.550.01430.15420.6001.64040.221 + j1.0560.167 + j0.3553487180220
    3/0 (19)0.34450.430.01340.14760.6401.64040.186 + j1.0080.132 + j0.3113138200250
    4/0 (19)0.27560.340.01220.14440.7051.96850.159 + j0.9670.105 + j0.2713836235285
    4/0 (19)0.27560.340.01220.14440.7051.96850.159 + j0.9670.105 + j0.2713836235285
    250 (37)0.23290.300.01100.13780.7711.96850.144 + j0.9290.090 + j0.2384533256309
    350 (37)0.16400.210.00980.13120.8692.29660.119 + j0.8810.065 + j0.1946277310370
    500 (37)0.11480.150.00850.12800.9972.62470.100 + j0.8360.046 + j0.1568865370445
    500 (37)0.11480.150.00850.12800.9972.62470.100 + j0.8340.046 + j0.1578865370445
    750 (61)0.07870.110.00730.12141.1812.95280.087 + j0.7920.033 + j0.12113298460525
    750 (61)0.07870.110.00730.12471.1812.95280.087 + j0.7900.033 + j0.12213211460525
    750 (61)0.07870.110.00730.12471.1812.95280.087 + j0.7900.033 + j0.12213211460525
    1000 (61)0.05910.090.00640.11811.3253.28080.080 + j0.7640.026 + j0.10117615520575
    *Ampacities for Direct Buried are based on ICEA P-117-734-2016 Single-Conductor Solid Dielectric 15-35kV. Single Circuit Flat Direct Buried Figure 3
    *Ampacities for Duct are based on ICEA P-117-734-2016 for Single-Conductor Solid Dielectric 15-35kV. Single Circuit Trefoil Conduit Figure 7.
    *Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft, Spacing: one diameter spacing center-to-center.