SPEC 80100

ACSR

Aluminum Conductor Steel Reinforced

...

Construction:

  1. Core: Class A core stranding is also available in zinc-5% aluminum-mischmetal alloy coating.
  2. Stranding:Aluminum 1350-H19 wires, concentrically stranded about a steel core.

  • Standard core wire for ACSR is class A galvanized.
  • For aluminum-clad (AW) ACSR, please refer to the ACSR/AW catalog sheet.
  • Additional corrosion protection is available through the application of grease to the core or infusion of the complete cable with grease.
  • ACSR conductor is also available in non-specular.

Applications and Features:

Used as bare overhead transmission conductor and as primary and secondary distribution conductor and messenger support. ACSR offers optimal strength for line design. Variable steel core stranding enables desired strength to be achieved without sacrificing ampacity

Specifications:

  • ASTM B230 Aluminum, 1350-H19 Wire for Electrical Purposes
  • ASTM B232 Concentric-Lay-Stranded, Aluminum Conductors, Coated Steel Reinforced (ACSR)
  • ASTM B498 Zinc-Coated (Galvanized) Steel Core Wire for Aluminum Conductors, Steel Reinforced (ACSR)
  • ASTM B500 Metallic Coated Stranded Steel Core for use in overhead Electrical Conductors
  • Weights, Measurements, Electrical and Engineering Data

    Stock NumberCode WordSizeStrandingSteel Core ODOverall ODAL WeightOverall WeightRated StrengthDC Resistance @ 20CAC Resistance @ 25CAllowable Ampacity+
    (AWG or kcmil)(Al/Stl)(inch)(inch)(lb/1,000')(lb/1,000')(lb)(Ohms/1,000')(Ohms/1,000')Amps
    101162Turkey66/10.06610.198243611900.64100.8060105
    101170Swan46/10.08340.250395718600.40300.5150140
    101188Swanate47/10.10300.257396723600.39900.5190140
    101196Sparrow26/10.10520.316629128500.25400.3320184
    101204Sparate27/10.12980.3256210734600.25100.3380184
    101212Robin16/10.11810.3547811535500.20100.2680212
    101220Raven1/06/10.13270.3989914543800.15900.2170242
    101238Quail2/06/10.14890.44712418353100.12600.1760276
    101246Pigeon3/06/10.16720.50215623066200.10000.1440315
    101253Penguin4/06/10.18780.56319729183500.07950.1190357
    101261Waxwing266.818/10.12170.60925028968800.06430.0787449
    101345Partridge266.826/70.23630.642251367113000.06370.0779475
    621641Ostrich30026/70.25060.680283412127000.05670.0693492
    101279Merlin336.418/10.13670.68431536586800.05100.0625519
    101360Linnet336.426/70.26540.720317462141000.05050.0618529
    101378Oriole336.430/70.31770.741318526173000.05020.0613535
    101287Chickadee397.518/10.14860.74337343199400.04320.0529576
    Brant397.524/70.25740.772374511146000.04300.0526584
    101386Ibis397.526/70.28850.783374546163000.04280.0523587
    101394Lark397.530/70.34530.806375622203000.04250.0519594
    101295Pelican47718/10.16280.814447517118000.03600.0442646
    101402Flicker47724/70.28190.846449614172000.03580.0439655
    101410Hawk47726/70.31600.858449656195000.03560.0436659
    101428Hen47730/70.37830.883450746238000.03540.0433666
    101303Osprey556.518/10.17580.879522603137000.03080.0379711
    101436Parakeet556.524/70.30450.914524716198000.03070.0376721
    101444Dove556.526/70.34130.927524765226000.03060.0375726
    101451Eagle556.530/70.40860.953525871278000.03030.0372734
    101469Peacock60524/70.31770.953570779216000.02820.0346760
    663730Squab60526/70.35590.966570832243000.02810.0345765
    Wood Duck60530/70.42600.994571946289000.02790.0342774
    101709Teal60530/190.42600.994571939300000.02790.0342773
    101311Kingbird63618/10.18800.940596690157000.02700.0332773
    Swift63636/10.13290.930596643136900.02710.0334769
    101485Rook63624/70.32560.977599818226000.02680.0330784
    101493Grosbeak63626/70.36490.991599874252000.02670.0328789
    Scoter63630/70.43681.019600995304000.02560.0325798
    101717Egret63630/190.43681.019600987315000.02660.0326798
    101519Flamingo666.624/70.33331.000628858237000.02560.0315807
    Gannet666.626/70.37361.014628916264000.02550.0313812
    Stilt715.524/70.34531.036674920255000.02390.0294844
    101527Starling715.526/70.38711.051674984284000.02380.0292849
    Redwing715.530/190.46331.0816761110346000.02360.0290859
    101337Coot79536/10.14861.040745804167100.02170.0268884
    101543Drake79526/70.40801.1077491093315000.02140.0263907
    101550Tern79545/70.26581.063749895221000.02160.0269887
    101568Condor79554/70.36401.0927491023282000.02150.0272889
    101733Mallard79530/190.48841.1407511234384000.02130.0261918
    298570Ruddy90045/70.28281.1318481013244000.01910.0239958
    101584Canary90054/70.38731.1628481158319000.01900.0241961
    101592Rail95445/70.29121.1658991074259000.01800.0225993
    101600Cardinal95454/70.39871.1968991227338000.01790.0228996
    101618Ortolan1033.545/70.30311.2129731163277000.01670.02091043
    101626Curlew1033.554/70.41501.2459731330366000.01650.02111047
    101634Bluejay111345/70.31451.25810481253298000.01550.01941092
    101741Finch111354/190.43071.29210531429391000.01540.01971093
    101642Bunting1192.545/70.32561.30211231343320000.01440.01821139
    101758Grackle1192.554/190.44581.33711291531419000.01440.01841140
    101659Bittern127245/70.33621.34511981432341000.01350.01711184
    101766Pheasant127254/190.46051.38112041633436000.01350.01731187
    101667Dipper1351.545/70.34661.38612731521362000.01270.01621229
    101774Martin1351.554/190.47461.42412791735463000.01270.01631232
    101675Bobolink143145/70.35661.42713481611383000.01200.01531272
    101691Lapwing159045/70.37591.50414981790422000.01080.01391354
    101808Falcon159054/190.51481.54415052041545000.01080.01401359
    226043Chukar178084/190.43681.60216852072510000.00970.01251453
    194241Bluebird215684/190.48081.76220402508603000.00800.01051623
    226035Kiwi216772/70.34701.73520512300498000.00800.01061607
    101816Grouse808/10.16670.3677514951900.20650.2888205
    101824Petrel101.812/70.27630.46196254104000.15830.2493234
    101832Minorca110.812/70.28850.481104276113000.14540.2331245
    101840Leghorn134.612/70.31770.530127336136000.11970.2000271
    101857Guinea15912/70.34530.576150396160000.10140.1757296
    203190Dotterel176.912/70.36420.607167441173000.09110.1618313
    101873Dorking190.812/70.37830.631180476187000.08450.1530325
    101881Brahma203.216/190.48850.714191675284000.07640.1499340
    101899Cochin211.312/70.39810.664199527207000.07630.1410343
  • +Conductor temperature of 75°C, ambient temperature 25°C, emissivity 0.5, wind 2 ft./sec., in sun.
  • Revision: 1.000.016

    Updated On: Jan. 26, 2026, 3:17 p.m. UTC