SPEC 60297

Armorlite® Type MC THHN/THWN Copper Conductor Feeder Cable 120/208V Colors. Silicone Free

Copper THHN/THWN-2 Insulated Singles. Green Insulated Copper Grounding Conductor. UL Listed. 600 Volts. Rated VW-1. Lightweight Aluminum Interlocked Armor.

...

Construction:

  1. Conductor:Class B compressed stranded copper per ASTM B3 and ASTM B8
  2. Insulation:All phases are insulated with Polyvinyl Chloride with Nylon Sheath Type THHN/THWN
  3. Ground: Green insulated copper ground
  4. Filler:Fillers as needed
  5. Binder:Mylar tape
  6. Armor:Aluminum Interlocked Armor

Applications and Features:

Southwire Armorlite® Type MC Feeder Cable is suitable for use as follows:
- Feeder and service power distribution in commercial, industrial, institutional, and multi-residential buildings.
- Where exposed to cinder fills, strong chlorides, caustic alkalis, or vapors of chlorine or of hydrochloric acids.
- Fished or embedded in plaster.
- Concealed or exposed installations.
- Suitable for Wet Location per NEC 330.10(A)(11)
- Places of Assembly per NEC 518.4 and theaters per NEC 520.5.
- Installation in cable tray and approved raceways, or as aerial cable on a messenger.
- Under raised floors for information technology equipment conductors and cables per NEC 645.5(D) & 645.5(D)(2)
- Class I Div. 2, Class II Div 2, & Class III Div. 1 Hazardous Locations.
- Type THHN/THWN rated 90ºC Dry/ 75ºC Wet

Southwire Armorlite® Type MC Feeder Cable - meets or exceeds the following requirements:
- UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com )
- Federal Specification A-A59544 (formerly J-C-30B)
- NFPA 70 (National Electrical Code), Article 330
- Listed for use in UL 1, 2 and 3 Hour Through Penetration Firestop Systems

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 1569 Metal-Clad Cables
  • UL 1479 Standard for Safety Fire Tests of Penetration Firestops
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • Buy American: Compliant with Buy American Requirements, found in 49 U.S.C. § 5323(j); specify “Made in the USA Only!” when ordering to ensure your project receives American made products.
  • Sample Print Legend:

    SOUTHWIRE {UL} E96627 X/C AWG XXX CU THHN OR THWN CDRS 600 VOLTS GW 1 X AWG X TYPE MC EZ-JKT FOR CT USE SUN. RES. 90 DEGREES C {YYYY} {SEQUENTIAL FOOTAGE MARKS} SEQ FEET
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeConductor NumberColorDiameter Over ConductorConductor StrandingInsulation ThicknessGround SizeDiameter Over ArmorCopper WeightOverall Weight
    AWG/KcmilinchmilsNo. x AWGinchlbs/1000ftlbs/1000ft
    1393931/031-BK,2-RD,WE,GN0.36119601x61.32010691398
    5687361/041-BK,2-RD,3-BE,WE0.36119601x61.45618101804
    6468351/04BK,RD,BE,WE,GN,GN/YW0.36119602x31.67718102377
    4583402/031-BK,2-RD,WE,GN0.39519601x61.40513261672
    4583982/041-BK,2-RD,3-BE,WE,GN0.39519601x61.57817422250
    4583383/041-BK,2-RD,3-BE,WE,GN0.45419601x41.71922232807
    4583364/041-BK,2-RD,3-BE,WE,GN0.51219601x41.81627693370
    5610344/041-BK,2-RD,3-BE,WE0.51219601x21.79728463424
    6773384/05BK,RD,BE,WE,WE/BK,GN0.51219601x41.96134294126
    45776725031-BK,2-RD,WE,GN0.55837701x41.76924693013
    45776925031-BK,2-RD,3-WE,GN0.55837701x2/01.86627533346
    5655452505BK,RD,BE,WE,WE,GN0.55837701x42.13640284798
    5991443504BK,BK,RD,RD,GN0.66137701x2/02.32447815673
    5978973504BK,BK,RD,RD0.66137701x2/02.26447815606
    6432573504BK,BK,RD,RD,GN0.66137701x12.28346275500
    45782150031-BK,2-RD,WE,GN0.78937701x22.25348845589
    4578195003BN,OE,YW,GN0.78937701x22.25348845595
    5788176004BK,RD,BE,WE,GN0.86561801x22.71676918702
    6784476004BK,RD,BE,WE,GN0.86561801x6003.003935511034
    643537◊2504BK,RD,BE,WE0.55837701x21.95433253994
    45684035041-BK,2-RD,3-BE,WE,GN0.66137701x32.19445305321
    4578395004BK,RD,BE,WE,GN0.78937701x4/02.60168967831
    4578375004BK,RD,BE,WE,GN0.78937701x2/02.55666527572
    45783550041-BK,2-RD,3-BE,WE,GN0.78937701x22.48664447324
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Note: Conductor number = number of phase conductors. Does not include green ground.
    Table 2 – Electrical and Engineering Data
    Cond. SizeConductor NumberMin. Bend RadiusMax Pull TensionDC Resistance at 25°CAC Resistance at 75°CInductive Reactance @ 60HzAllowable Ampacity Raceway 75°CAllowable Ampacity Raceway 90°C
    AWG/KcmilInchesLbsΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    1/039.225340.1020.1220.044150170
    1/0410.227030.1020.1220.044120136
    1/0411.727030.1020.1220.044120136
    2/039.831940.0810.1010.043175195
    2/0411.042590.0810.1010.043140156
    3/0412.042960.0640.0800.035160180
    4/0412.754160.0510.0620.041184208
    4/0412.654160.0510.0620.041184208
    4/0513.767710.0510.0620.041184182
    250312.460000.0430.0530.041255290
    250313.160000.0430.0530.041255290
    25051580000.0430.0530.041204203
    350416.3112000.0310.0390.04248280
    350415.8112000.0310.0390.04248280
    350416112000.0310.0390.04248280
    500315.8120000.0220.0290.039380430
    500315.8120000.0220.0290.039380430
    600419192000.0180.0250.039336380
    600422.2192000.0180.0250.039336380
    250413.764000.0430.0530.041204232
    350415.489600.0310.0390.04248280
    500418.2128000.0220.0290.039304344
    500417.9128000.0220.0290.039304344
    500417.4128000.0220.0290.039304344
    * Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
    * Ampacities have been adjusted for more than Three Current-Carrying Conductors.

    Revision: 1.000.017

    Updated On: June 20, 2025, 10:15 p.m. UTC