SPEC 45451

CU 2000V XLPE Insulation Three Grounds Cu Tape Shield PVC Jacket. RHH/RHW-2 Variable Frequency Drive (VFD)

Type TC-ER VFD Power Cable 2000 Volt Three Conductor Copper, Cross Linked Polyethylene (XLPE) insulation RHH/RHW-2 Polyvinyl Chloride (PVC) Jacket with 3 Symmetrical Bare CU Ground 50% Minimum Tape Shield Overlap. Silicone Free

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Insulation:Cross Linked Polyethylene (XLPE) Type RHH/RHW-2
  3. Grounding Conductor:3 Class B compressed stranded bare copper ground per ASTM B3 and ASTM B8 (Ground size is 100% for sizes 14 - 10 awg and a minimum of 50% of the phase conductor for larger sizes.)
  4. Filler:Fillers as needed to make round
  5. Tape Shield:5 mil copper tape shield with a minimum of 50% overlap
  6. Overall Jacket:Polyvinyl Chloride (PVC) Jacket. Available in thermoplastic Chlorinated Polyethylene CPE jacket on #4 AWG and larger upon request

Applications and Features:

Southwire’s 2000 Volt Type TC-ER VFD power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Type (TC-ER) per NEC 336.10.

Gland Reference: Glands

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • ICEA S-138-738 Power Cables Rated 2000 Volts or Less for use Between Variable Frequency Drives and Motors
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661
  • Sample Print Legend:

    SOUTHWIRE® VFD {UL} XX AWG 3/C TYPE TC-ER RHH OR RHW-2 CDRS CU GW 3 X XX AWG CU T/S 50% 90°C PVC JACKET SUN RES DIRECT BURIAL 2000 VOLTS {YYYY} {SEQUENTIAL FOOTAGE MARKS} SEQ FEET FT4/IEEE1202 2000 VOLTS
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. NumberStrand CountDiameter Over ConductorInsul. ThicknessGroundDia. Over ShieldJacket ThicknessApprox. ODCopper WeightApprox. WeightJacket Color
    AWG/KcmilNo. of StrandsinchmilNo. x AWGinchmilinchlb/1000ftlb/1000ft
    580672◊14370.07603 x 180.451600.57193202BK
    580685◊12370.088603 x 160.486600.606128244BK
    580693◊10370.113603 x 140.537600.657183329BK
    569388◊8370.141703 x 140.652600.772270456BK
    580701◊6370.177703 x 120.723800.883389624BK
    569389◊4370.225703 x 120.825800.985547815BK
    569387◊2370.282703 x 100.946801.1068271121BK
    67736713190.322953 x 81.316801.27210651508BK
    644333◊1/03190.361903 x 61.22801.3813731858BK
    644334◊2/03190.405903 x 61.311801.47116402164BK
    644337◊3/03190.454903 x 41.419801.57921322638BK
    644338◊4/03190.512903 x 41.5061151.73625423202BK
    644339◊2503370.5581053 x 21.6651151.89531503995BK
    TBA3003370.611053 x 31.7831102.00329563906BK
    644340◊3503370.6611053 x 21.8791152.10941105098BK
    6689213503370.6611053 x 31.8791152.10939814969BK
    TBA4003370.7051053 x 21.9881102.20839084993BK
    644341◊5003370.7891053 x 12.1491152.37957066767BK
    6690996003610.8651203 x 12.4091152.63966738025BK
    TBA7503610.9681203 x 2/02.6211402.90172359006BK
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeCond. NumberMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity At 75°CAllowable Ampacity At 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    580672◊1434986.6598.2650.0362025
    580685◊1234.21561.6622.0020.0542530
    580693◊1034.62491.041.2530.053540
    569388◊835.43960.6530.7860.0525055
    580701◊636.26290.4110.4950.0516575
    569389◊436.910010.2580.310.0488595
    569387◊237.715920.1620.1950.045115130
    677367138.920090.1290.1670.032130145
    644333◊1/039.725340.1020.1220.044150170
    644334◊2/0310.331940.0810.0970.043175195
    644337◊3/0311.140270.0640.0780.042200225
    644338◊4/0312.250780.0510.0620.041230260
    644339◊250313.360000.0430.0530.041255290
    TBA30031472000.0360.0450.041285320
    644340◊350314.884000.0310.0390.04310350
    668921350314.884000.0310.0390.04310350
    TBA400315.596000.0270.0350.04335380
    644341◊500316.7120000.0220.0290.039380430
    669099600318.5144000.0180.0250.039420475
    TBA750320.3180000.0140.0220.038475535
    * Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.

    Revision: 1.000.006

    Updated On: Aug. 5, 2025, 7:48 p.m. UTC

    VFD Sizing Calculator
    QR Code