SPEC 13008

Southwire CL4SS™ Class 4 Shielded Outdoor / General Purpose

...

Construction:

  1. Conductor:Class B or C stranded soft-drawn bare copper per ASTM B3 and B8
  2. Insulation:Twisted pair(s) with premium grade, lead-free, flame-retardant, Polyvinyl Chloride (PVC). See Table 4 for pair(s) numbers and colors.
  3. ShieldAluminum foil shield
  4. Jacket: Lead-free, flame-retardant, LS, Polyvinyl Chloride (PVC). See Table 5 for available jacket colors.

Applications and Features:

Intended for use in Fault Managed Power Systems (FMPS), remote powering, indoor Class 4 circuits per 2023 National Electrical Code (NEC) article 726. For use, primarily, in Agriculture, Intelligent Buildings, and Wireless Densification. The power source (transmitter) for Class 4 circuits shall be supplied from a power source that has a voltage output of 450 volts (peak or DC) or less. The CL4Z cables are considered for outdoor use only and are not to be attached to or used within a building structure. Type CL4Z cables comply with the applicable requirements for CL4. The CMG cables can be installed in buildings according to NEC article 722.135 and table 722.135(B).

Ratings:
Normal operating temperature: 90°C
Temperature Range: -40°C to 90°C
Rated Use: Dry or wet locations

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 1400-2 Fault-Managed Power Systems - Part 2: Requirements for Cables
  • UL 444 Communications Cables
  • Sample Print Legend:

    {SQFTG} SOUTHWIRE{R} CL4SS P/N XX AWG X PAIR SHIELDED E537761 (UL) CL4Z 90C -40C OR CMG C(UL)US 90C -- FT4/IEEE 1202 -- WET LOCATIONS -- MADE IN USA ROHS-2 COMPLIANT
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeNumber of PairsDiameter Over ConductorInsul. ThicknessJacket ThicknessApprox. ODApprox. WeightMin Bending RadiusDC Resistance @ 25°C
    AWG/Kcmilpairinchmilmilinchlb/1000ftinchΩ/1000ft
    CL4Z188S1880.04517370.417881.76.669
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Weights and Measurements (Metric)
    Stock NumberCond. SizeNumber of PairsDiameter Over ConductorInsul. ThicknessJacket ThicknessApprox. ODApprox. WeightMin Bending RadiusDC Resistance @ 25°C
    AWG/Kcmilpairinchmmmmmmlb/kmmmΩ/km
    CL4Z188S1880.0450.430.9410.5913143.1821.88

    Table 3 - Typical Electrical Capacitance for Each Pair

    SizeCapacitance
    AWGpF/ft
    18<30
    16<30
    14<30

    Table 4 - Pair Color Chart - Numbers & Colors

    2 Pair4 Pair8 Pair
    1 Black & Red1 Black & Red1 Black & Red
    2 Black & White2 Black & White2 Black & White
    3 Black & Green3 Black & Green
    4 Black & Blue4 Black & Blue
    5 Black & Yellow
    6 Black & Brown
    7 Black & Orange
    8 Black & White

    Table 5 - Stock Code by Jacket Color

    Condutor
    Size
    Number
    of Pairs
    Jacket
    Color
    AWGnum
    GreenBlackWhite
    GreenBlackWhite
    182CL4Z182S0605CL4Z182S0608CL4Z182S0601
    184CL4Z184S0605CL4Z184S0608CL4Z184S0601
    188CL4Z188S0605CL4Z188S0608CL4Z188S0601
    162CL4Z162S0605CL4Z162S0608CL4Z162S0601
    164CL4Z164S0605CL4Z164S0608CL4Z164S0601
    168CL4Z168S0605CL4Z168S0608CL4Z168S0601
    142CL4Z142S0605CL4Z142S0608CL4Z142S0601
    144CL4Z144S0605CL4Z144S0608CL4Z144S0601
    148CL4Z148S0605CL4Z148S0608CL4Z148S0601

    Revision: 1.000.006