SPEC 10090

CU 150V HVAC Wire Unshielded Thermostat CL2/CMH

CU 150V HDPE Insulation PVC Jacket CL2/CMH Power Limited Unshielded Thermostat Wire

...

Construction:

  1. Conductor:Solid bare copper per ASTM B3
  2. Insulation:High Density Polyethylene HDPE
  3. Rip Cord:Rip cord for ease of jacket strip ability
  4. Overall Jacket:Polyvinyl Chloride (PVC) Jacket in Brown

Applications and Features:

  • 150 Voltage
  • rating per NEC® Article 725
  • ETL listed to UL 13 and UL 444
  • Meets UL 1581 Vertical Tray Flame Test (FT-1)
  • Type CL2
  • C22.2 214 TYPE CMH
  • Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • UL 13 Power-Limited Circuit Cables
  • UL 444 CM/CL2
  • Sample Print Legend:

    TYPE CL2 C{ETL}US XX AWG XX/C BAROSTAT II SUN RES -- TYPE CMH FT1 -- {MM/DD/YY} {HH:MM}
    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. NumberCond. StrandsDiameter Over Cond.Insulation ColorInsul. ThicknessJacket ThicknessApprox. ODCopper WeightApprox. WeightDC Resistance @ 25°CAC Resistance @ 75°CInductive RectanceMin Bending RadiusJacket Color
    AWGNo.strandsinchmilmilinchlb/1000ftlb/1000ftΩ/1000ftΩ/1000ftΩ/1000ftinch
    20 AWG
    55210◊2010SOLID0.032RD,WE,GN,BE,YW,BN,OE,BK,PK,GY5150.202303810.50312.6550.0270.8BN
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

    Revision: 1.000.010

    Updated On: April 1, 2025, 11:18 p.m. UTC