SPEC 10028

Romex® Brand Copper SIMpull® Indoor NM-B Cable

Nonmetallic-Sheathed Cable. 600 Volt. Copper Conductor. PVC Insulation/Nylon Sheath. PVC Jacket with SIMpull® Technology for Easier Pulling.

...

Construction:

  1. Conductor: Bare copper per ASTM B3. Sizes #14 AWG - #10 AWG are solid. Sizes #8 AWG - #2 AWG are Class B compressed stranded per ASTM B8
  2. Insulation: All phases and neutral(s) are insulated with Polyvinyl Chloride (PVC) with Nylon Sheath
  3. Ground: Solid soft drawn bare copper with kraft paper wrap
  4. Binder: Kraft paper
  5. Jacket: Polyvinyl Chloride (PVC) jacket utilizing SIMpull® Technology

Applications and Features:

Southwire® Romex® Brand SIMpull® NM-B (nonmetallic-sheathed) cable may be used for both exposed and concealed work in dry locations as specified in the National Electrical Code®. NM-B cable is primarily used in residential wiring as branch circuits for outlets, switches, and other loads. NM-B cable may be run in air voids of masonry block or tile walls where such walls are not wet or damp locations. Voltage rating for NM-B cable is 600 volts.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 719 Nonmetallic-Sheathed Cables
  • RoHS-2 (European Directive 2011/65/EU)
  • Federal Specification A-A-59544
  • NOM-063-SCFI Electrical Products – Conductors – Safety Requirements
  • Sample Print Legend:

    E18679 (UL) ROMEX® SIMpull{TM} XX AWG (X.XXmm2) CU X CDR WITH XX AWG (mm2) GROUND TYPE NM-B 600 VOLTS NOM-ANCE PAT www.patentSW.com
    Table 1 – Weights and Measurements
    Cond. SizeCond. NumberStrand CountDiameter Over ConductorInsul. ThicknessGroundJacket ThicknessApprox. ODCopper WeightApprox. Weight
    AWG/KcmilNo. of StrandsinchmilNo. x AWGmilinchlb/1000ftlb/1000ft
    142Solid0.064211 x 14300.374x0.1723762
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    4/C NM-B constructions are round
    ^4 (2/2) Extra circuit construction
    Table 2 – Electrical and Engineering Data
    Cond. SizeCond. NumberMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60Hz
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ft
    1420.7652.6313.1700.058
    Ampacities based upon 2023 NEC Table 310.16. Also, see NEC sections 310.15 for additional requirements.
    Ampacities have been adjusted for more than Three Current-Carrying Conductors.

    Phase Color Code and Package #14 and 12 AWG

    Conductor NumberPackageBlackWhiteRedBlueWhite/Red
    BlackWhiteRedBlueBrown
    2Coil: 125', 250', 500'
    Spool: 500', 1000', 2500'
    XX
    3Coil: 125', 250', 500'
    Spool: 500', 1000', 2500'
    XXX
    4Coil: 125', 250', 500'
    Spool: 500', 1000', 2500'
    XXXX
    4 - (2/2)Coil: 125', 250', 500'
    Spool: 500', 1000', 2500'
    XXXX

    Phase Color Code and Package #10, #8, 6, 4, 2 AWG

    Conductor NumberPackageBlackWhiteRedBlue
    BlackWhiteRedBlue
    2Coil: 125', 250', 500'
    Spool: 500', 1000', 2500'
    XX
    3Coil: 125', 250', 500'
    Spool: 500', 1000', 2500'
    XXX
    4Coil: 125', 250', 500'
    Spool: 500', 1000', 2500'
    XXXX