SPEC 80210
MV-105 35kV AL 100% TRXLPE Full Neutral (Based on Short Circuit) HI-DRI-PLUS® Renewable (Solar or Wind)
Moisture Blocked Aluminum Conductors. TRXLP Insulation. Full Copper Concentric Neutrals. XLPE Jacket

Construction:
- Conductor:Moisture Blocked 1350 H16/H26 Aluminum, Class B Compressed or Compressed Unilay Stranded
- Strand Shield:Semi-conducting Crosslinked Polyethylene
- Insulation:Tree Retardant Crosslinked Polyethylene (TRXLP)
- Insulation Shield:Strippable Semi-conducting Crosslinked Polyethylene
- Concentric Neutral:Annealed Copper Wires Helically Applied Full Concentric Neutral
- Overall Jacket & Water Block:HI-DRI-PLUS® Water Swellable Powder Black Crosslinked Polyethylene (XLPE) with Red Extruded Stripes
Applications and Features:
- Predominately used for renewable projects with wind or solar applications.
- Suitable for use in wet or dry locations, direct burial, underground ducts, and exposure to direct sunlight.
- To be used at conductor temperature not to exceed 105ºC normal operation.
- UL listed MV-105
- The concentric neutral counts and sizes listed in Table 1 are based on the ICEA P-45-482 short circuit calculation of an MV-90 design. The short circuit value in Table 1 is calculated using a higher thermal limit of a crosslinked XLPE jacket MV-105 design.
Specifications:
Sample Print Legend:
{SQFTG} SOUTHWIRE(R) HI-DRI-PLUS(R) (UL) XXX AWG AL 345 MILS TRXLPE TYPE MV-105 35KV 100% INSUL LEVEL -- (NESC) -- SOUTHWIRE {MMM} {YYYY} NON-CONDUCTING JACKET
Table 1 – Weights and Measurements
| Stock Number | Cond. Size | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Concentric Neutral | Neutral DC Resistance 25°C | Jacket Thickness | Approx. OD | Approx. Weight | Min Bending Radius | Max Pull Tension |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | inch | inch | mil | inch | No. x AWG | Ω/1000ft | mil | inch | lb/1000ft | inch | lb | |
| 626294 | 1/0 (19) | 0.352 | 1.072 | 345 | 1.182 | 19x16 | 0.271 | 50 | 1.384 | 833 | 6.9 | 633 |
| 629793 | 3/0 (19) | 0.443 | 1.163 | 345 | 1.273 | 18x14 | 0.18 | 50 | 1.501 | 1052 | 7.5 | 1006 |
| 662956 | 4/0 (19) | 0.498 | 1.218 | 345 | 1.328 | 14x12 | 0.146 | 50 | 1.59 | 1217 | 8 | 1269 |
| 456400 | 4/0 (19) | 0.498 | 1.218 | 345 | 1.328 | 15x12 | 0.136 | 50 | 1.59 | 1236 | 8 | 1269 |
| 607596 | 4/0 (19) | 0.498 | 1.218 | 345 | 1.328 | 23x14 | 0.141 | 50 | 1.61 | 1247 | 8 | 1269 |
| TBA | 250 (37) | 0.558 | 1.294 | 345 | 1.414 | 28x14 | 0.116 | 75 | 1.692 | 1568 | 8.5 | 1500 |
| TBA | 350 (37) | 0.661 | 1.397 | 345 | 1.517 | 24x12 | 0.085 | 75 | 1.829 | 1875 | 9.1 | 2100 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Pulling tension based on pulling eye directly connected to conductor
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Cond. Size | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Short Circuit Current @ 30 Cycle | Allowable Ampacity in Duct 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 1/0 (19) | 0.167 | 0.229 | 0.069 | 0.053 | 0.460+j0.121 | 0.231+j0.058 | 6170 | 160 | 195 |
| 3/0 (19) | 0.105 | 0.144 | 0.06 | 0.05 | 0.310+j0.073 | 0.147+j0.054 | 9321 | 210 | 250 |
| 4/0 (19) | 0.084 | 0.115 | 0.056 | 0.048 | 0.253+j0.058 | 0.119+j0.053 | 11507 | 240 | 280 |
| 4/0 (19) | 0.084 | 0.115 | 0.056 | 0.048 | 0.244+j0.055 | 0.119+j0.053 | 12328 | 240 | 280 |
| 4/0 (19) | 0.084 | 0.115 | 0.056 | 0.049 | 0.248+j0.056 | 0.119+j0.053 | 11910 | 240 | 280 |
| 250 (37) | 0.07 | 0.096 | 0.052 | 0.047 | 0.207+j0.047 | 0.101+j0.052 | 14499 | 261 | 302 |
| 350 (37) | 0.051 | 0.07 | 0.046 | 0.045 | 0.153+j0.036 | 0.076+j0.049 | 19726 | 315 | 365 |
*Ampacities for Direct Buried are based on ICEA P-117-734-2016 Single-Conductor Solid Dielectric 15-35kV. Single Circuit Flat Direct Buried Figure 3
*Ampacities for Duct are based on ICEA P-117-734-2016 for Single-Conductor Solid Dielectric 15-35kV. Single Circuit Trefoil Conduit Figure 7.
*Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft.
*Ampacities for Duct are based on ICEA P-117-734-2016 for Single-Conductor Solid Dielectric 15-35kV. Single Circuit Trefoil Conduit Figure 7.
*Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft.
Table 3 – Weights and Measurements (Metric)
| Stock Number | Cond. Size | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Concentric Neutral | Neutral DC Resistance 25°C | Jacket Thickness | Approx. OD | Approx. Weight | Min Bending Radius | Max Pull Tension |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | mm | mm | mm | mm | No. x AWG | Ω/km | mm | mm | kg/km | mm | newton | |
| 626294 | 1/0 (19) | 8.94 | 27.23 | 8.76 | 30.02 | 19x16 | 0.89 | 1.27 | 35.15 | 1240 | 175.26 | 2817 |
| 629793 | 3/0 (19) | 11.25 | 29.54 | 8.76 | 32.33 | 18x14 | 0.59 | 1.27 | 38.13 | 1566 | 190.50 | 4477 |
| 662956 | 4/0 (19) | 12.65 | 30.94 | 8.76 | 33.73 | 14x12 | 0.48 | 1.27 | 40.39 | 1811 | 203.20 | 5647 |
| 456400 | 4/0 (19) | 12.65 | 30.94 | 8.76 | 33.73 | 15x12 | 0.45 | 1.27 | 40.39 | 1839 | 203.20 | 5647 |
| 607596 | 4/0 (19) | 12.65 | 30.94 | 8.76 | 33.73 | 23x14 | 0.46 | 1.27 | 40.89 | 1856 | 203.20 | 5647 |
| TBA | 250 (37) | 14.17 | 32.87 | 8.76 | 35.92 | 28x14 | 0.38 | 1.91 | 42.98 | 2333 | 215.90 | 6675 |
| TBA | 350 (37) | 16.79 | 35.48 | 8.76 | 38.53 | 24x12 | 0.28 | 1.91 | 46.46 | 2790 | 231.14 | 9345 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Pulling tension based on pulling eye directly connected to conductor
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 4 – Electrical and Engineering Data (Metric)
| Cond. Size | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance* | Positive Sequence Impedance* | Short Circuit Current @ 30 Cycle | Allowable Ampacity in Duct 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | Ω/km | Ω/km | MΩ*km | Ω/km | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 1/0 (19) | 0.5479 | 0.75 | 0.0210 | 0.1739 | 0.460+j0.121 | 0.231+j0.058 | 6170 | 160 | 195 |
| 3/0 (19) | 0.3445 | 0.47 | 0.0183 | 0.1640 | 0.310+j0.073 | 0.147+j0.054 | 9321 | 210 | 250 |
| 4/0 (19) | 0.2756 | 0.38 | 0.0171 | 0.1575 | 0.253+j0.058 | 0.119+j0.053 | 11507 | 240 | 280 |
| 4/0 (19) | 0.2756 | 0.38 | 0.0171 | 0.1575 | 0.244+j0.055 | 0.119+j0.053 | 12328 | 240 | 280 |
| 4/0 (19) | 0.2756 | 0.38 | 0.0171 | 0.1608 | 0.248+j0.056 | 0.119+j0.053 | 11910 | 240 | 280 |
| 250 (37) | 0.2297 | 0.31 | 0.0158 | 0.1542 | 0.207+j0.047 | 0.101+j0.052 | 14499 | 261 | 302 |
| 350 (37) | 0.1673 | 0.23 | 0.0140 | 0.1476 | 0.153+j0.036 | 0.076+j0.049 | 19726 | 315 | 365 |
*Ampacities for Direct Buried are based on ICEA P-117-734-2016 Single-Conductor Solid Dielectric 15-35kV. Single Circuit Flat Direct Buried Figure 3
*Ampacities for Duct are based on ICEA P-117-734-2016 for Single-Conductor Solid Dielectric 15-35kV. Single Circuit Trefoil Conduit Figure 7.
*Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft.
*Ampacities for Duct are based on ICEA P-117-734-2016 for Single-Conductor Solid Dielectric 15-35kV. Single Circuit Trefoil Conduit Figure 7.
*Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft.
Revision: 1.000.024
Updated On: Oct. 15, 2026, 2:58 p.m. UTC
Concentric Neutral Calculator

