SPEC 70207

600V ROYAL® Shielded SOOW with Black Jacket 90°C. Silicone-Free

Rated -40°C to 90°C. Class K copper conductor. Heat, moisture and oil resistant EPDM rubber insulation. Heat, moisture and oil resistant flexible CPE jacket.

...

Construction:

  1. Conductor:Tinned flexible stranded Class K copper conductors
  2. Insulation:Heat, moisture and oil resistant EPDM
  3. Filler:Non-wicking wax paper fillers, with a tissue-paper separator wrapped around the assembly
  4. Shield:Tinned CU braid shielding
  5. Jacket:Heat, moisture and oil resistant flexible CPE jacket

Applications and Features:

Southwire Type SOOW Flexible Cords are permitted for use as specified by Article 400 and related articles of the 2014 National Electrical Code. Southwire Type SOOW Flexible Cords are designed for extra hard usage on industrial equipment, heavy tools, battery chargers, portable lights welding leads, marine dockside power, power extensions and mining applications.

Specifications:

  • UL 62 Flexible Cords and Cables
  • CSA C22.2 No. 49 Flexible Cords and Cables
  • ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 1
  • MSHA flame test - P07-KA070018-1MSHA
  • Passes CSA FT2 Flame Test
  • RoHS-3 Complies with European Directive 2015/863
  • NEC Article 400 Flexible Cords, Cables and Fixture Wire
  • Federal Specification J-C-580B
  • OSHA Acceptable
  • Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. NumberCond. StrandsInsul. ThicknessJacket ThicknessApprox. ODApprox. WeightAmpacityInsul. ColorJacket Color
    AWG/KcmilNo.No.milmilinchlb/1000ftAmp
    5700401821630600.3719110BK,WEBK
    5700461831630600.3881027BK,WE,GNBK
    5700471841630600.4191245BK,WE,RD,GNBK
    5714131851630800.4941735BK,WE,RD,GN,OEBK
    5700501861630800.5191745BK,WE,RD,GN,OE,BEBK
    5700531881630800.5542044BK,WE,RD,GN,OE,BE,WE/BK,RD/BKBK
    57607818101630800.6412533See TableBK
    57003518121630800.6512763See TableBK
    57506618161630900.7563893See TableBK
    5714391622630550.38511613BK,WEBK
    5716901632630600.41712310BK,WE,GNBK
    5700271642630600.4451468BK,WE,RD,GNBK
    5700311682630800.5942517BK,WE,RD,GN,OE,BE,WE/BK,RD/BKBK
    57001216122630950.7293635See TableBK
    57001316162630950.7934425See TableBK
    5878621424145800.53517418BK,WEBK
    5712771434145800.56521015BK,WE,GNBK
    5700081444145800.60925112BK,WE,RD,GNBK
    5713161226545950.60022825BK,WEBK
    57140012365451000.62926820BK,WE,GNBK
    56998912465451000.67731716BK,WE,RD,GNBK
    58595710310445950.68532125BK,WE,GNBK
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Table 2 – Weights and Measurements (Metric)
    Stock NumberCond. SizeCond. NumberCond. StrandsInsul. ThicknessJacket ThicknessApprox. ODApprox. WeightAmpacity *Insul. ColorJacket Color
    AWG/KcmilNo.No.mmmmmmkg/kmAmp
    570040182160.761.529.4213510BK,WEBK
    570046183160.761.529.861527BK,WE,GNBK
    570047184160.761.5210.641855BK,WE,RD,GNBK
    571413185160.762.0312.552575BK,WE,RD,GN,OEBK
    570050186160.762.0313.182595BK,WE,RD,GN,OE,BEBK
    570053188160.762.0314.073044BK,WE,RD,GN,OE,BE,WE/BK,RD/BKBK
    5760781810160.762.0316.283773See TableBK
    5700351812160.762.0316.544113See TableBK
    5750661816160.762.2919.205793See TableBK
    571439162260.761.409.7817313BK,WEBK
    571690163260.761.5210.5918310BK,WE,GNBK
    570027164260.761.5211.302178BK,WE,RD,GNBK
    570031168260.762.0315.093747BK,WE,RD,GN,OE,BE,WE/BK,RD/BKBK
    5700121612260.762.4118.525405See TableBK
    5700131616260.762.4120.146585See TableBK
    587862142411.142.0313.5925918BK,WEBK
    571277143411.142.0314.3531315BK,WE,GNBK
    570008144411.142.0315.4737412BK,WE,RD,GNBK
    571316122651.142.4115.2433925BK,WEBK
    571400123651.142.5415.9839920BK,WE,GNBK
    569989124651.142.5417.2047216BK,WE,RD,GNBK
    5859571031041.142.4117.4047825BK,WE,GNBK
    * Ampacities are based on TABLE 400.5(A)(1) of the 2023 National Electrical Code and CEC Table 12.

    Revision: 1.000.000

    Updated On: July 3, 2024, 10:13 p.m. UTC