SPEC 45410

AL 2000V XLPE Insulation. RHH/RHW-2 PV

Single Conductor Photovoltaic (Type PV) Power Cable 2000 Volt Aluminum Conductor XLPE Insulation. Sizes 6 AWG through 1000 kcmil. Heat, Moisture, and Sunlight Resistant RoHS. 90°C

...

Construction:

  1. Conductor:AlumaFlex® Compact Stranded Aluminum Alloy (AA-8176)
  2. Insulation:Cross-linked Polyethylene (XLPE)

Applications and Features:

The cable is available in sizes 6 AWG through 1000 kcmil. The product is approved for use in solar power applications per the NEC article 690 and is rated 90°C for exposed or concealed wiring in wet or dry locations. Individual conductors are stranded aluminum alloy covered with a cross-linked polyethylene (XLPE) insulation and is rated for direct burial. The cable is sunlight resistant, oil resistant PRI and PRII, RoHS compliant, passes -40°C cold bend. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions.

Specifications:

  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 4703 Standard for Photovoltaic Wire
  • Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661
  • VW-1 Vertical-Wire Flame Test (Optional)
  • AA 8176 Stranded Aluminum Alloy Conductors
  • Sample Print Legend:

    SOUTHWIRE E316464 {UL} PV WIRE XXX KCMIL (XXX.XXX{mm2}) COMPACT AL. --- AlumaFlex® AA8176 2000V 90°C WET OR DRY -40°C SUN RES DIRECT BURIAL OR RHH-RHW-2 2000V --- RoHS {MMM/DD/YYYY} {SEQUENTIAL FOOTAGE MARKS} SEQ FEET
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrand CountDiameter Over ConductorInsul. ThicknessInsulation ColorApprox. ODAluminum WeightApprox. WeightJacket Color
    AWG/KcmilNo. of Strandsinchmilinchlb/1000ftlb/1000ft
    585843670.16985BK0.3492459BK
    586673470.21285BK0.3833977BK
    586672260.26885BK0.43862104BK
    619879180.298105BK0.51978146BK
    5912561/0100.336105BK0.54699164BK
    5836732/0120.376105BK0.586125195BK
    5771003/0160.422105BK0.633158235BK
    5836784/0190.474105BK0.685199284BK
    577101250220.520120BK0.760235350BK
    584290300210.569120BK0.810282397BK
    582174350350.615120BK0.856329462BK
    584291400350.659120BK0.899376518BK
    582267500340.735120BK0.978471615BK
    585499600370.812135BK1.083565745BK
    607592700580.877135BK1.147659851BN
    586013750610.908135BK1.178706904BK
    6413871000581.060135BK1.3309421168BK
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity At 75°CAllowable Ampacity At 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    58584361.41570.6740.8120.0515055
    58667341.52500.4240.5100.0486575
    58667221.83980.2670.3210.04590100
    61987912.15020.2110.2540.046100115
    5912561/02.26330.1680.2010.044120135
    5836732/02.37980.1330.1600.043135150
    5771003/02.510060.1050.1260.042155175
    5836784/02.712690.0840.1000.041180205
    5771012503.015000.0710.0860.041205230
    5842903003.218000.0590.0710.041230260
    5821743503.421000.0500.0620.040250280
    5842914003.624000.0440.0540.040270305
    5822675003.930000.0350.0440.039310350
    5854996005.436000.0290.0370.039340385
    6075927005.742000.0250.0330.038375425
    5860137505.945000.0240.0310.038385435
    64138710006.760000.0180.0250.037445500
    * Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
    * Inductive Reactance is based on non-ferrous conduit with one diameter spacing center-to-center.

    Stock Codes and Colors

    SizeBlackBrownOrangeYellowWhiteRedGreen
    AWG/KcmilBlackBrownOrangeYellowWhiteRedGreen
    6585843
    4586673
    2586672589171
    1619879589051
    1/0591256591241
    2/0583673
    3/0577100669515669516669517577843669518
    4/0583678597698607400591242
    250577101577844668535
    300584290589170675225
    350582174597996592618
    400584291596689652801
    500582267591243591244591245586671588797591246
    600585499591247588799
    700607592591248591249591250
    750592619
    1000641387641386

    Revision: 1.000.013

    Updated On: April 20, 2026, 7:10 p.m. UTC