SPEC 10005

Copper XHHW-2 Circuit Sizes (14, 12 & 10 AWG)

Power Cable 600 or 1000 Volt Single Conductor Copper, Cross Linked Polyethylene (XLPE).

...

Construction:

  1. Conductor:Solid or Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Insulation:Cross Linked Polyethylene (XLPE)

Applications and Features:

APPLICATION
Southwire XHHW-2 copper conductors circuit sizes are primarily used in conduit, or other recognized raceways, and branch circuit wiring, as specified in the National Electrical Code. XHHW-2 copper conductors may be used in wet or dry locations at temperatures not to exceed 90°C. Voltage rating for XHHW-2 conductors is 600 volts or 1000 volts. Suitable for use in Health Care Facilities per Section 517.160 of the National Electrical Code where a dielectric constant of less than 3.5 maybe specified.


FEATURES
  • SIS - Sizes 14 AWG through 10 AWG
  • RoHS Compliant
  • Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661
  • Federal Specification A-A-59544
  • NMX-J-451-ANCE Thermoset insulated wires and cables
  • NOM-063-SCFI Electrical Products – Conductors – Safety Requirements
  • Sample Print Legend:

    14 AWG thru 10 AWG
    SOUTHWIRE E30117 (UL) XX AWG (XXXmm2) CU TYPE XHHW-2 600V/1000V OR SIS 600 VOLTS NOM-ANCE

    Table 1 – Weights and Measurements
    Cond. SizeStrand CountDiameter Over ConductorInsul. ThicknessApprox. ODCopper WeightApprox. Weight
    AWG/KcmilNo. of Strandsinchmilinchlb/1000ftlb/1000ft
    12Solid0.080300.1411925
    10Solid0.101300.1623037
    1470.070300.1311217
    1270.088300.1472024
    1070.113300.1733236
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity At 75°CAllowable Ampacity At 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    120.6521.6622.0020.0542530
    100.6831.0401.2530.0503540
    140.5322.6313.1700.0582025
    120.6521.6622.0020.0542530
    100.7831.0401.2530.0503540
    *Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
    * Inductive Reactance is based on non-ferrous conduit with one diameter spacing.

    Stock Code Colors and Standard Package

    SizePackageBlackRedBlueWhiteBrownOrangeYellowGrayGreen
    BlackRedBlueWhiteBrownOrangeYellowGrayGreen
    14 (7)Reel: 2500'
    Spool: 500'
    112920370932370940370924370981370973370957371005370965
    12 (Solid)Reel: 2500'
    Spool: 500'
    550220550222550224550221550227550226550225550223
    12 (7)Reel: 2500'
    Spool: 500'
    112938371039371047371021371088371070371054371104371062
    10 (Solid)Reel: 2500'
    Spool: 500'
    137240550213550215550212550218550217550216550214
    10 (7)Reel: 2500'
    Spool: 500'
    112946371138371146371120371187371179371153371203371161

    Revision: 1.000.040

    Updated On: Aug. 17, 2024, 2:20 p.m. UTC