SPEC 45030

CU 600V Royal® Bus Drop Cable

600 Volt. 60°C PVC Insulation and Jacket. Outdoor Rated.

...

Construction:

  1. Conductor:Class C stranded bare copper per ASTM B8
  2. Insulation:Polyvinyl Chloride (PVC)
    Color Code: 3/C Black, White, Red; 4/C Black, White, Red, Blue
  3. Grounding Conductor:Class K stranded bare copper per ASTM B174
  4. Filler:Polypropylene fillers as necessary for a round assembly
  5. Binder:Tissue Paper
  6. Overall Jacket:Gray, Polyvinyl Chloride (PVC) Jacket.

Applications and Features:

Southwire Bus Drop Cable is suitable for use as branches from busways per the National Electrical Code® and for the connection of stationary equipment to facilitate the relocation of equipment.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B174 Standard Specification for Bunch-Stranded Copper
  • UL 509 Bus Drop Cable
  • Sample Print Legend:

    SOUTHWIRE(R) ROYAL(R) E357438 14-3 BUS DROP CABLE TW INS. 600V (UL) 60C OUTDOOR
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. NumberStrand CountDiameter Over ConductorInsul. ThicknessGroundJacket ThicknessApprox. ODCopper WeightApprox. WeightJacket Color
    AWG/KcmilNo. of StrandsinchmilNo. x AWGmilinchlb/1000ftlb/1000ft
    552123143190.073303 x 18450.37953101Gray
    552124123190.090303 x 16450.42084141Gray
    570109124190.090204 x 18450.411102150Gray
    552126103190.117303 x 14450.470135203Gray
    570110104190.117304 x 16450.491159223Gray
    55212783190.143453 x 14600.630182307Gray
    55212863190.179603 x 14600.794284479Gray
    55212943190.226603 x 12800.939450746Gray
    55213023190.286603 x 12801.071681998Gray
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeCond. NumberMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity At 75°CAllowable Ampacity At 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    5521231431.5982.6313.1700.0582025
    5521241231.61561.6622.0020.0542530
    5701091241.61561.6622.0020.0542024
    5521261031.82491.0401.2530.0503540
    5701101041.93321.0401.2530.0502832
    552127832.53960.6530.7860.0525055
    552128633.16290.4110.4950.0516575
    552129433.710010.2580.3100.0488595
    552130235.315920.1620.1950.045115130
    *Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
    * Ampacities have been adjusted for more than Three Current-Carrying Conductors.

    Revision: 1.000.010

    Updated On: Dec. 31, 2024, 11:07 p.m. UTC