SPEC 44030
1/C CU EPR Medium Voltage Non-Shielded Jumper & Switchgear Cable
Single Conductor Flexible Conductor with an EPR Insulation Non-Shielded Jumper Cable
Construction:
- Conductor:Flexible rope lay stranded annealed bare or tinned copper
- Conductor Shield:Nylon semi-conducting tape, helically applied
- Insulation:Heat, moisture, and ozone resistant Ethylene Propylene Rubber(EPR)
Applications and Features:
Southwire’s medium voltage non-shielded jumper and switchgear cable is a flexible power cable that is intended for use in substations installed on insulators and inside switchgear isolated from ground and where a non-shielded flexible cable is desired. These cables are capable of operating continuously at a conductor temperature not in excess of 90°C.
This cable is rated up to 40KV and is not UL listed. See Table 2 for installation guidelines
This cable is rated up to 40KV and is not UL listed. See Table 2 for installation guidelines
Specifications:
Sample Print Legend:
SOUTHWIRE® XXX SIZE NON-SHIELDED FLEXIBLE JUMPER AND SWITCHGEAR CABLE NON-UL
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Color | Diameter Over Conductor | Conductor Stranding | Insulation Thickness | Approx. OD | Copper Weight | Overall Weight |
---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | mils | inch | lbs/1000ft | lbs/1000ft | |||
569424 | 2 | RD | 0.290 | 168 | 210 | 0.753 | 169 | 177 |
587529 | 2 | OE | 0.315 | 259 | 200 | 0.770 | 169 | 424 |
569423 | 1/0 | RD | 0.379 | 259 | 210 | 0.840 | 320 | 548 |
569425 | 2/0 | RD | 0.400 | 324 | 220 | 0.883 | 406 | 674 |
569487 | 4/0 | RD | 0.530 | 532 | 210 | 0.979 | 651 | 960 |
674322 | 4/0 | OE | 0.530 | 532 | 360 | 1.280 | 638 | 1244 |
569427 | 350 | RD | 0.670 | 893 | 230 | 1.160 | 1084 | 1475 |
569428 | 500 | RD | 0.858 | 1221 | 230 | 1.350 | 1514 | 1970 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
† Ampacities based upon 2023 NEC Table 310.16. Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
Table 2 – Electrical and Engineering Data
Cond. Size | Max Pull Tension | DC Resistance at 25°C | AC Resistance at 75°C | Inductive Reactance @ 60Hz | Allowable Ampacity Raceway 75°C | Allowable Ampacity Raceway 90°C |
---|---|---|---|---|---|---|
AWG/Kcmil | Lbs | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp |
2 | 530 | 0.172 | 0.207 | 0.045 | 115 | 130 |
2 | 530 | 0.172 | 0.207 | 0.045 | 115 | 130 |
1/0 | 844 | 0.109 | 0.131 | 0.044 | 150 | 170 |
2/0 | 1064 | 0.087 | 0.104 | 0.043 | 175 | 195 |
4/0 | 1692 | 0.055 | 0.067 | 0.041 | 230 | 260 |
4/0 | 1692 | 0.055 | 0.067 | 0.041 | 230 | 260 |
350 | 2800 | 0.033 | 0.042 | 0.040 | 310 | 350 |
500 | 4000 | 0.023 | 0.031 | 0.039 | 380 | 430 |
Revision: 1.000.006