SPEC 10100

Twisted Pump Cable Type THW

600 Volts, Solid or Stranded Copper Conductors. Polyvinyl Chloride (PVC) Insulation. Water Well Cable, Moisture Resistant, Twisted Configuration. Rated 75°C,

...

Construction:

  1. Conductor:Solid soft drawn or fully annealed bare copper per ASTM B3. Stranded class B compressed bare copper ASTM B8
  2. Insulation:Polyvinyl Chloride (PVC) Type THW

Applications and Features:

For use in residential, farm and industrial water well applications where the cable is not subject to repeated handling caused by frequent servicing of the pump units. Grounded and ungrounded water well cable systems. Conductors are twisted and colored black, red, and yellow when supplied with three conductors and green ground. Cable is supplied without an overall jacket. For use within well casings.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 83 Thermoplastic Insulated Wires and Cables
  • Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. NumberCond. StrandsDiameter Over ConductorInsul. ThicknessGroundApprox. ODApprox. Weight
    AWG/KcmilNo.No.inchmilNo. x AWGinchlb/1000ft
    563703142Solid0.064301 x 140.33466
    563704143Solid0.064301 x 140.37388
    563705122Solid0.080301 x 120.34592
    563706123Solid0.080301 x 120.414122
    563707102Solid0.101301 x 100.414131
    563708103Solid0.101301 x 100.462176
    56370982190.128451 x 100.574195
    56371083190.128451 x 100.610274
    56371163190.162601 x 80.700402
    56371243190.204601 x 80.792564
    56371323190.257601 x 60.929852
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Table 2 – Electrical and Engineering Data
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CInductive ReactanceMin Bending RadiusAllowable Ampacity In Raceway At 75°CAllowable Ampacity In Raceway At 90°C
    AWG/KcmilΩ/1000ftΩ/1000ftΩ/1000ftinchAmpAmp
    142.6313.1700.0581.32025
    142.6313.1700.0581.42025
    121.6622.0020.0541.32530
    121.6622.0020.0541.62530
    101.0401.2530.0501.63540
    101.0401.2530.0501.83540
    80.6530.7860.0522.25055
    80.6530.7860.0522.45055
    60.4110.4950.0512.86575
    40.2580.3100.0483.18595
    20.1620.1950.0453.7115130
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing.

    Revision: 1.000.001

    Updated On: Dec. 11, 2023, 9:29 p.m. UTC