SPEC 10103

HI-LO Supreme Parallel Water Well 600 Volt Pump Cable

600V, Extreme, Oil-Resistant, Moisture Resistant Conditions. Rated -50°C to 90°C Dry/ 75°C Wet

...

Construction:

  1. Conductor:Class K, flexible stranded, soft drawn bare copper per ASTM B3 and B172
  2. Insulation:Thermoplastic elastomer (TPE)
  3. Jacket:Thermoplastic elastomer (TPE)

Applications and Features:

For use in residential, farm and industrial water well applications. Used in both grounded and ungrounded water well cable systems. Conductors are parallel and insulated with premium Thermoplastic Elastomer (TPE) colored black, red, and yellow. Jacketed with a premium Thermoplastic Elastomer (TPE) material. Oil resistant. Used in both high temperature and low temperature wells.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B172 Standard Specification for Rope-Lay-Stranded Copper Conductors Having Bunch-Stranded Copper Conductors
  • UL 83 Thermoplastic Insulated Wires and Cables
  • Sample Print Legend:

    SOUTHWIRE® E23919 XX AWG (X.XX{mm2}) {UL} 600V PUMP CABLE 90°C DRY 75°C WET {DD/MM/YYYY} {SEQUENTIAL FOOTAGE MARKS} SEQ FEET
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. NumberCond. StrandsDiameter Over ConductorInsul. ThicknessGroundJacket ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.No.inchmilNo. x AWGmilinchlb/1000ft
    597864831680.153451 x 10300.316 X 1.010289
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    • TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    • Cond. Number does not include ground conductor.
    Table 2 – Electrical and Engineering Data
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CInductive ReactanceMax Pull TensionMin Bending RadiusAllowable Ampacity In Raceway At 75°CAllowable Ampacity In Raceway At 90°C
    AWG/KcmilΩ/1000ftΩ/1000ftΩ/1000ftlbinchAmpAmp
    80.7150.8610.0524225.04044
    • Inductive impedance is based on non-ferrous conduit with one diameter spacing.

    Revision: 1.000.009

    Updated On: Aug. 27, 2026, 1 p.m. UTC