SPEC 45312
AL 600/1000V XLPE Insulation 50% Ground AIA PVC Jacket XHHW-2. CT Rated -Sunlight Resistant - For Direct Burial - Silicone Free
Type MC Power Cable 600Volt Three Conductor Aluminum, Cross Linked Polyethylene (XLPE) insulation XHHW-2 Three Bare AL 50% Ground Aluminum Interlocked Armor (AIA), Polyvinyl Chloride (PVC) Jacket with. Silicone Free.

Construction:
- Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
- Insulation:Cross Linked Polyethylene (XLPE) Type XHHW-2
- Grounding Conductor:Three separate ground wires with a combined circular mil of 50% of the phase condutor. Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
- Filler:Paper filler or Polypropylene filler
- Binder:Polypropylene tape
- Armor:Aluminum Interlocked Armor (AIA)
- Overall Jacket:Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire’s 600 Volt Type MC power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of op- erating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. The ground is sized to 50% of the phase conductor with three separate bare grounds one in each interstecie between condutors. Silicone Free.
Specifications:
Sample Print Legend:
{SQFTG_DUAL} SOUTHWIRE {UL} E96627 3/C XXX KCMIL COMPACT AL.--- {ALUMAFLEX}® AA8176 XX MILS XLP 600 VOLTS GW 3 X XX AWG 3E AL TYPE MC FOR CT USE SUN. RES. DIRECT BURIAL 90°C USA
Table 1 – Weights and Measurements
| Stock Number | Cond. Size | Cond. Number | Strand Count | Diameter Over Conductor | Insul. Thickness | Diameter Over Insulation | Ground | Diameter Over Armor | Jacket Thickness | Approx. OD | Jacket Color |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. of Strands | inch | mil | inch | No. x AWG | inch | mil | inch | |||
| TBA | 1/0 | 3 | 19 | 0.336 | 55 | 0.446 | 3 x 7 | 1.176 | 50 | 1.276 | BK |
| TBA | 2/0 | 3 | 19 | 0.376 | 55 | 0.486 | 3 x 6 | 1.263 | 50 | 1.363 | BK |
| TBA | 3/0 | 3 | 19 | 0.423 | 55 | 0.533 | 3 x 5 | 1.364 | 50 | 1.464 | BK |
| TBA | 4/0 | 3 | 19 | 0.475 | 55 | 0.585 | 3 x 4 | 1.577 | 50 | 1.677 | BK |
| TBA | 250 | 3 | 35 | 0.52 | 65 | 0.65 | 3 x 4 | 1.717 | 50 | 1.817 | BK |
| TBA | 300 | 3 | 35 | 0.57 | 65 | 0.7 | 3 x 3 | 1.825 | 60 | 1.945 | BK |
| 649332 | 350 | 3 | 35 | 0.616 | 65 | 0.746 | 3 x 2 | 1.951 | 60 | 2.077 | BK |
| TBA | 500 | 3 | 35 | 0.736 | 65 | 0.866 | 3 x 1/0 | 2.184 | 60 | 2.304 | BK |
| TBA | 600 | 3 | 41 | 0.813 | 80 | 0.973 | 3 x 2/0 | 2.415 | 60 | 2.535 | BK |
| 677353 | 600 | 3 | 41 | 0.813 | 80 | 0.973 | 3 x 1/0 | 2.428 | 75 | 2.586 | BK |
| 576220 | 750 | 3 | 58 | 0.908 | 80 | 1.068 | 3 x 2/0 | 2.651 | 75 | 2.808 | BK |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Strand count meets minimum number per ASTM
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Stock Number | Cond. Size | Cond. Number | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 75°C | Inductive Reactance @ 60Hz | Allowable Ampacity At 75°C | Allowable Ampacity At 90°C |
|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | ||
| TBA | 1/0 | 3 | 8.9 | 1900 | 0.167 | 0.208 | 0.044 | 120 | 135 |
| TBA | 2/0 | 3 | 9.5 | 2395 | 0.133 | 0.166 | 0.043 | 135 | 150 |
| TBA | 3/0 | 3 | 10.2 | 3020 | 0.105 | 0.131 | 0.042 | 155 | 175 |
| TBA | 4/0 | 3 | 11.7 | 3808 | 0.084 | 0.105 | 0.041 | 180 | 205 |
| TBA | 250 | 3 | 12.7 | 4500 | 0.07 | 0.087 | 0.041 | 205 | 230 |
| TBA | 300 | 3 | 13.6 | 5400 | 0.059 | 0.074 | 0.041 | 230 | 260 |
| 649332 | 350 | 3 | 14.5 | 6300 | 0.051 | 0.064 | 0.04 | 250 | 280 |
| TBA | 500 | 3 | 16.1 | 9000 | 0.036 | 0.045 | 0.039 | 310 | 350 |
| TBA | 600 | 3 | 17.7 | 10800 | 0.03 | 0.038 | 0.039 | 340 | 385 |
| 677353 | 600 | 3 | 18.1 | 10800 | 0.03 | 0.038 | 0.039 | 340 | 385 |
| 576220 | 750 | 3 | 19.7 | 13500 | 0.023 | 0.03 | 0.038 | 385 | 435 |
* Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
Revision: 1.000.008
Updated On: Dec. 31, 2024, 11:07 p.m. UTC

