SPEC 45265

AL 600/1000V XLPE Insulation PVC Jacket XHHW-2. CT Rated -Sunlight Resistant - For Direct Burial - Silicone Free

Type TC-ER Power Cable 600 or 1000 Volt Four Conductor Aluminum, Cross Linked Polyethylene (XLPE) insulation XHHW-2 Polyvinyl Chloride (PVC) Jacket with 1 Bare AL Ground. Silicone Free.

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  2. Insulation:Cross Linked Polyethylene (XLPE) Type XHHW-2
  3. Grounding Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  4. Filler:Paper filler (cable size 8 & 6 uses Polypropylene filler)
  5. Binder:Polyester flat thread binder tape for cable sizes larger than 2 AWG
  6. Overall Jacket:Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire’s 600 or 1000 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Silicone free.

Specifications:

  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • Sample Print Legend:

    {SQFTG} SOUTHWIRE® {UL} XXX AWG (XX{mm2}) 3E AL 4/C TYPE TC-ER XHHW-2 CDRS GW 1 X X AWG 3E AL 90°C JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600V or 1000V {NOM}-ANCE
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. NumberStrand CountDiameter Over ConductorInsul. ThicknessGroundJacket ThicknessApprox. ODAluminum WeightApprox. WeightJacket Color
    AWG/KcmilNo. of StrandsinchmilNo. x AWGmilinchlb/1000ftlb/1000ft
    TBA8470.134451 x 8600.66883206BK
    TBA6470.169451 x 8600.753119262BK
    TBA4470.213451 x 6800.899184384BK
    TBA2470.268451 x 6801.032280517BK
    TBA14190.299551 x 4801.156358651BK
    TBA1/04190.336551 x 4801.245438758BK
    TBA2/04190.376551 x 4801.342542892BK
    6722513/04160.423551 x 4801.4766781127BK
    5837274/04190.475551 x 2801.6018681357BK
    5821232504220.52651 x 11101.81310311694BK
    6722523004210.57651 x 21101.93412051921BK
    5821243504350.616651 x 1/01102.04514332216BK
    5785374004350.659651 x 11102.14916022434BK
    4594614004350.659651 x 1/01152.16116232479BK
    5821214004350.659651 x 3/01102.26316822531BK
    5785365004340.736651 x 11102.33519832890BK
    5821255004340.736651 x 2/01102.3520302960BK
    5965495004340.736651 x 3/01102.4620633043BK
    5821265004340.736651 x 2501102.46721413137BK
    6650385004340.736651 x 4/01152.4721043112BK
    4583836004370.813801 x 11102.6623633756BK
    5822506004370.813801 x 4/01102.69524853668BK
    5821276004370.813801 x 3501402.79926173981BK
    5785387504580.908801 x 1/01402.88729554262BK
    TBA9004610.999801 x 1/01403.09134894840BK
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeCond. NumberMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity At 75°CAllowable Ampacity At 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    TBA842.73961.0711.3340.0523236
    TBA6436290.6740.840.0514044
    TBA443.610010.4240.5280.0485260
    TBA245.215920.2660.3310.0457280
    TBA145.820080.2110.2630.0468092
    TBA1/046.225340.1670.2080.04496108
    TBA2/046.731940.1330.1660.043108120
    6722513/047.440270.1050.1310.042124140
    5837274/04850780.0840.1050.041144164
    58212325049.160000.070.0870.041164184
    67225230049.772000.0590.0710.041184208
    582124350412.384000.0510.0640.04200224
    578537400412.996000.0440.0550.04216244
    45946140041396000.0440.0550.04216244
    582121400413.696000.0440.0550.04216244
    578536500414120000.0360.0450.039248280
    582125500414.1120000.0360.0450.039248280
    596549500414.8120000.0360.0450.039248280
    582126500414.8120000.0360.0450.039248280
    665038500414.8120000.0360.0450.039248280
    458383600416144000.030.0380.039272308
    582250600416.2144000.030.0380.039272308
    582127600416.8144000.030.0380.039272308
    578538750417.3180000.0230.030.038308348
    TBA900418.5216000.0190.0250.037340384
    * Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
    * Ampacities have been adjusted for more than Three Current-Carrying Conductors.

    Revision: 1.000.006

    Updated On: April 14, 2025, 10:28 p.m. UTC