SPEC 45263

AL 600V PVC-Nylon Insulation PVC Jacket THHN/THWN-2. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free

Type TC-ER Power Cable 600Volt Three Conductor Aluminum, Polyvinyl Chloride (PVC) with nylon layer insulation THHN Polyvinyl Chloride (PVC) Jacket with 1 Bare AL Ground. Silicone Free

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  2. Insulation:Polyvinyl Chloride (PVC) with nylon layer Type THHN/THWN
  3. Grounding Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  4. Filler:Paper filler (cable size 8 & 6 uses Polypropylene filler)
  5. Binder:Polyester flat thread binder tape for cable sizes larger than 2 AWG
  6. Overall Jacket:Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire’s 600 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 75°C in wet locations and 90°C in dry locations, 105°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Silicone free

Specifications:

  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 4
  • Sample Print Legend:

    {SQFTG} SOUTHWIRE® {UL} XXX AWG AL 3 CDRS TYPE TC-ER THHN OR THWN-2 CDRS AL GW 1 X 3 AWG 90°C JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600 VOLTS {YYYY}
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. NumberStrand CountDiameter Over ConductorInsul. ThicknessGroundJacket ThicknessApprox. ODAluminum WeightApprox. Weight
    AWG/KcmilNo. of StrandsinchmilNo. x AWGmilinchlb/1000ftlb/1000ft
    TBA8370.134351 x 8600.56361160
    6713836370.169301 x 8600.66390220
    TBA4370.212501 x 6600.796142317
    6756132370.268401 x 6800.945214569
    6756181380.298501 x 6801.052263661
    5880231380.298501 x 4801.104278599
    6756201/03100.336501 x 4801.132341763
    6756222/03120.376501 x 3801.218429880
    6756243/03150.422501 x 4801.3195181001
    5782184/03190.474501 x 2801.4326671145
    6732534/03190.474501 x 2801.4326671140
    5833862503220.520601 x 2801.5777761363
    6756262503220.520601 x 2801.5777761366
    TBA3003370.569701 x 21101.7539141615
    TBA3503370.615701 x 21101.85310561811
    6780995003340.735601 x 11102.10315062464
    5993176003410.812701 x 4/01102.31819142925
    6734976003410.812701 x 6001102.49822833358
    6774007503580.908701 x 3/01102.52223003580
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeCond. NumberMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity At 75°CAllowable Ampacity At 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    TBA832.32971.0721.2900.0524045
    671383632.74720.6740.8120.0515055
    TBA433.27510.4240.5100.0486575
    675613233.811940.2670.3210.04590100
    675618135.315060.2110.2540.046100115
    588023135.515060.2110.2540.046100115
    6756201/035.719000.1680.2010.044120135
    6756222/036.123950.1330.1600.043135150
    6756243/036.630200.1050.1260.042155175
    5782184/037.238080.0840.1000.041180205
    6732534/037.238080.0840.1000.041180205
    58338625037.945000.0710.0860.041205230
    67562625037.945000.0710.0860.041205230
    TBA30038.854000.0590.0710.041230260
    TBA35039.363000.0500.0620.040250280
    678099500312.690000.0350.0440.039310350
    599317600313.9108000.0290.0370.039340385
    673497600315.0108000.0290.0370.039340385
    677400750315.1135000.0240.0310.038385435
    * Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.