SPEC 45251
CU 600V PVC-Nylon Insulation PVC Jacket THHN/THWN-2. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free
Type TC-ER Power Cable 600Volt Three Conductor Copper, Polyvinyl Chloride (PVC) with nylon layer insulation THHN/THWN-2 Polyvinyl Chloride (PVC) Jacket with 1 Bare CU Ground. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free.

Construction:
- Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
- Insulation:Polyvinyl Chloride (PVC) with nylon layer Type THHN/THWN-2
- Grounding Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8 (cable size 8 & 6 has insulated green ground)
- Filler:Paper filler (cable size 8 & 6 uses Polypropylene filler)
- Binder:Polyester flat thread binder tape for cable sizes larger than 2 AWG
- Overall Jacket:Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire’s 600 Volt Type TC-ER THHN/THWN-2 power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C in dry or wet locations, 105°C for emergency overload, and 150°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Sunlight Resistant - For Direct Burial - Silicone Free
Specifications:
Sample Print Legend:
{SQFTG} SOUTHWIRE® {UL} XX AWG (XX.X{mm2}) CU 3 CDRS TYPE TC-ER THHN OR THWN CDRS GW 1 X X AWG 90°C JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600 VOLTS {NOM}-ANCE {YYYY}
Table 1 – Weights and Measurements
| Stock Number | Cond. Size | Cond. Number | Strand Count | Diameter Over Conductor | Insul. Thickness | Ground | Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Jacket Color |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. of Strands | inch | mil | No. x AWG | mil | inch | lb/1000ft | lb/1000ft | |||
| 443390◊ | 8 | 3 | 7 | 0.142 | 30 | 1 x 10 | 60 | 0.64 | 187 | 307 | BK |
| 443408◊ | 6 | 3 | 7 | 0.178 | 30 | 1 x 8 | 60 | 0.734 | 297 | 452 | BK |
| 443416◊ | 4 | 3 | 7 | 0.225 | 40 | 1 x 8 | 60 | 0.818 | 442 | 621 | BK |
| 443424◊ | 2 | 3 | 7 | 0.283 | 40 | 1 x 6 | 80 | 0.991 | 703 | 982 | BK |
| 443432◊ | 1 | 3 | 19 | 0.322 | 50 | 1 x 6 | 80 | 1.121 | 865 | 1171 | BK |
| 443440◊ | 1/0 | 3 | 19 | 0.362 | 50 | 1 x 6 | 80 | 1.197 | 1070 | 1405 | BK |
| 443457◊ | 2/0 | 3 | 19 | 0.405 | 50 | 1 x 6 | 80 | 1.292 | 1327 | 1687 | BK |
| 443465◊ | 3/0 | 3 | 19 | 0.456 | 50 | 1 x 4 | 80 | 1.4 | 1700 | 2096 | BK |
| 443473◊ | 4/0 | 3 | 19 | 0.512 | 50 | 1 x 4 | 80 | 1.495 | 2110 | 2571 | BK |
| 443481◊ | 250 | 3 | 37 | 0.558 | 60 | 1 x 4 | 80 | 1.637 | 2469 | 3034 | BK |
| 443507◊ | 350 | 3 | 37 | 0.661 | 60 | 1 x 3 | 110 | 1.911 | 3439 | 4183 | BK |
| 443523◊ | 500 | 3 | 37 | 0.789 | 60 | 1 x 2 | 110 | 2.181 | 4885 | 5726 | BK |
| 604777 | 600 | 3 | 61 | 0.866 | 70 | 1 x 2 | 110 | 2.389 | 5820 | 6788 | BK |
| 602094◊ | 750 | 3 | 61 | 0.968 | 70 | 1 x 1 | 110 | 2.665 | 7277 | 8519 | BK |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Stock Number | Cond. Size | Cond. Number | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 75°C | Inductive Reactance @ 60Hz | Allowable Ampacity At 75°C | Allowable Ampacity At 90°C |
|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | ||
| 443390◊ | 8 | 3 | 2.6 | 396 | 0.653 | 0.81 | 0.052 | 50 | 55 |
| 443408◊ | 6 | 3 | 2.9 | 629 | 0.411 | 0.51 | 0.051 | 65 | 75 |
| 443416◊ | 4 | 3 | 3.3 | 1001 | 0.258 | 0.32 | 0.048 | 85 | 95 |
| 443424◊ | 2 | 3 | 4 | 1592 | 0.162 | 0.201 | 0.045 | 115 | 130 |
| 443432◊ | 1 | 3 | 5.6 | 2008 | 0.128 | 0.159 | 0.046 | 130 | 145 |
| 443440◊ | 1/0 | 3 | 6 | 2534 | 0.102 | 0.127 | 0.044 | 150 | 170 |
| 443457◊ | 2/0 | 3 | 6.5 | 3194 | 0.082 | 0.102 | 0.043 | 175 | 195 |
| 443465◊ | 3/0 | 3 | 7 | 4027 | 0.064 | 0.079 | 0.042 | 200 | 225 |
| 443473◊ | 4/0 | 3 | 7.5 | 5078 | 0.051 | 0.063 | 0.041 | 230 | 260 |
| 443481◊ | 250 | 3 | 8.2 | 6000 | 0.043 | 0.053 | 0.041 | 255 | 290 |
| 443507◊ | 350 | 3 | 9.6 | 8400 | 0.031 | 0.039 | 0.04 | 310 | 350 |
| 443523◊ | 500 | 3 | 13.1 | 12000 | 0.021 | 0.027 | 0.039 | 380 | 430 |
| 604777 | 600 | 3 | 14.3 | 14400 | 0.018 | 0.024 | 0.039 | 420 | 475 |
| 602094◊ | 750 | 3 | 16 | 18000 | 0.014 | 0.019 | 0.038 | 475 | 535 |
*Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
Revision: 1.000.006
Updated On: Dec. 31, 2024, 11:07 p.m. UTC


