SPEC 45059

TCU 600/1000V EPR Insulation XHHW-2 Thermoplastic CPE-TP Jacket. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free

Type TC-ER Control Cable, 600/1000 Volt, Tinned Copper Conductors, Ethylene Propylene Rubber (EPR) Insulation XHHW-2, Thermoplastic Chlorinated Polyethylene (CPE-TP) Jacket, Control Cable Conductor Identification Method 1 Table 1, CT Rated, Sunlight Resistant, Oil Resistant, For Direct Burial, VW-1 Rated, Silicone Free

...

Construction:

  1. Conductor:7-strand class B compressed tinned copper per ASTM B33 and B8
  2. Insulation:Ethylene Propylene Rubber (EPR) Type XHHW-2
  3. Overall Jacket:Thermoplastic Chlorinated Polyethylene (CPE-TP)

Applications and Features:

Southwire’s 600/100 Volt Type TC-ER control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Constructions with 2 conductors are rated TC. VW-1 rated. Sunlight Resistant. Oil Resistant. For Direct Burial. Silicone Free.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 44 VW-1 Vertical flame test on individual conductors
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 1
  • ICEA S-73-532 Control, Thermocouple Extension, and Instrumentation Cables (applicable to sizes 20-9 AWG conductors)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • Sample Print Legend:

    {SQFTG} SOUTHWIRE® XX AWG (X.XX{MM2}) X/C EPR/CPE TYPE TC-ER XHHW-2 CDRS E75755 {UL} 600V/1000V 90°C DRY/90°C WET OIL RES I SUNLIGHT RESISTANT DIRECT BURIAL FT4/IEEE 1202 -- {NOM}-ANCE EPR/CPE Tipo XHHW-2 SR FT4 600V/1000V 90°C USA
    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. NumberCond. StrandsDiameter Over Cond.Insul. ThicknessJacket ThicknessApprox. ODCopper WeightApprox. WeightDC Resistance @ 25°CAC Resistance @ 75°CInductive RectanceMin Bending RadiusAllowable Ampacity 75°CAllowable Ampacity 90°CJacket Color
    AWGNo.strandsinchmilmilinchlb/1000ftlb/1000ftΩ/1000ftΩ/1000ftΩ/1000ftinchAmpAmp
    14 AWG
    TBA14270.07130450.35839752.6313.2650.0581.42025BK
    59945714370.07130450.38838862.6313.2650.0581.62025BK
    59945814470.07130450.423501082.6313.2650.0581.71620BK
    59945914570.07130450.461631302.6313.2650.0581.81620BK
    59547914770.07130450.502881712.6313.2650.05821418BK
    59946014970.07130600.6161132332.6313.2650.0582.51418BK
    599461141270.07130600.6921502992.6313.2650.0582.81012BK
    TBA141570.07130600.7432093622.6313.2650.05831012BK
    595475141970.07130800.8042384342.6313.2650.0583.21012BK
    TBA142570.07130800.9523415982.6313.2650.0583.8911BK
    TBA143070.07130801.0064066982.6313.2650.0585911BK
    TBA143770.07130801.0834988392.6313.2650.0585.4810BK
    12 AWG
    59563512270.08930450.39641851.6622.0630.0541.62530BK
    59547212370.08930450.419611151.6622.0630.0541.72530BK
    59563612470.08930450.466811481.6622.0630.0541.92024BK
    59211112570.08930600.5431021971.6622.0630.0542.22024BK
    TBA12770.08930600.5731612591.6622.0630.0542.31821BK
    59691912970.08930600.7131833301.6622.0630.0542.91821BK
    595477121270.08930600.7542444101.6622.0630.0543.01215BK
    TBA121570.08930800.8683235291.6622.0630.0543.51215BK
    TBA121970.08930800.9114036401.6622.0630.0543.61215BK
    TBA122570.08930801.065258211.6622.0630.0545.31114BK
    TBA123070.08930801.1216269631.6622.0630.0545.61114BK
    TBA123770.08930801.20976711611.6622.0630.05461012BK
    10 AWG
    59563210270.11330450.466651171.041.2910.051.93540BK
    59555610370.11330450.478971621.041.2910.051.93540BK
    59563310470.11330600.5561292211.041.2910.052.22832BK
    TBA10570.11330600.5931932871.041.2910.052.42832BK
    TBA10770.11330600.6452583731.041.2910.052.62428BK
    TBA10970.11330600.7513224631.041.2910.0532428BK
    645726101270.11330800.8993886171.041.2910.053.61820BK
    TBA101570.11330800.9815167571.041.2910.053.91820BK
    TBA101970.11330801.0316469241.041.2910.055.21820BK
    TBA102570.11330801.20484011891.041.2910.0561618BK
    TBA103070.11330801.275100113981.041.2910.056.41618BK
    TBA103770.11330801.377122716911.041.2910.056.91416BK
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    *Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
    *Ampacities have been adjusted for more than Three Current-Carrying Conductors.