SPEC 45051

CU 600V PVC-Nylon Insulation PVC Jacket THHN/THWN. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free

Type TC-ER Control Cable 600 Volt Copper Conductors, Polyvinyl Chloride (PVC) with nylon layer Insulation Type THHN/THWN or TFFN/TFN, Polyvinyl Chloride (PVC) Jacket, Control Cable Conductor Identification Method 1 Table 2. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free - VW-1 Rated.

...

Construction:

  1. Conductor:7 strands class B compressed bare copper per ASTM B3 and B8 for 14, 12, and 10 AWG cables. Class K bare copper per ASTM B3 and B174 for 16 AWG (26 strands) and 18 AWG (16 strands) cables.
  2. Insulation:Polyvinyl Chloride (PVC) with nylon layer. Type TFFN/TFN for 18 and 16 AWG cables. Type THHN or THWN for 14, 12, and 10 AWG cables. Types THHN or THWN are VW-1 rated.
  3. Filler:Polypropylene filler on cables with 5 or less conductors
  4. Binder:Polyester flat thread binder tape applied for cables with more than 5 conductors
  5. Overall Jacket:Polyvinyl Chloride (PVC)

Applications and Features:

Southwire’s 600 Volt Type TC-ER control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 75°C in wet locations and 90°C in dry locations, 105°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 66 Fixture Wire
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 2
  • ICEA S-73-532 Control, Thermocouple Extension, and Instrumentation Cables (applicable to sizes 20-9 AWG conductors)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • Sample Print Legend:

    {SQFTG} SOUTHWIRE® {UL} XX AWG (X.XX{mm2}) CU XX CDRS TYPE TC-ER THHN OR THWN CDRS 90°C JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600 VOLTS {NOM}-ANCE
    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. NumberCond. StrandsDiameter Over Cond.Insul. ThicknessDiameter Over InsulationJacket ThicknessApprox. ODCopper WeightApprox. WeightDC Resistance @ 25°CAC Resistance @ 75°CInductive RectanceMin Bending RadiusAllowable Ampacity 75°CAllowable Ampacity 90°CJacket Color
    AWGNo.strandsinchmilinchmilinchlb/1000ftlb/1000ftΩ/1000ftΩ/1000ftΩ/1000ftinchAmpAmp
    18 AWG
    57787918270.046150.076450.26810366.6698.2770.0361.1-14BK
    65218818370.046150.076450.2815466.6698.2770.0361.1-14BK
    57787818470.046150.076450.30620556.6698.2770.0361.2-11BK
    65219118570.046150.076450.33625666.6698.2770.0361.3-11BK
    65219418670.046150.076450.36130766.6698.2770.0361.4-11BK
    65219718870.046150.076450.38840946.6698.2770.0361.6-10BK
    652200181070.046150.076450.441501426.6698.2770.0361.8-7BK
    652203181270.046150.076450.458611566.6698.2770.0361.8-7BK
    652215181670.046150.076450.512802026.6698.2770.0362-7BK
    652209181970.046150.076650.564962416.6698.2770.0362.37BK
    652212182470.046150.076650.6591213226.6698.2770.0362.66BK
    16 AWG
    604843◊162260.057150.087450.29216454.1815.1890.0331.2-18BK
    604850◊163260.057150.087450.30824584.1815.1890.0331.2-18BK
    604868◊164260.057150.087450.33432704.1815.1890.0331.3-14BK
    604876◊165260.057150.087450.36340824.1815.1890.0331.5-14BK
    TBA16670.057200.097450.38756994.1815.1890.0331.5-14BK
    679257166260.057150.087450.39348974.1815.1890.0331.6-14BK
    604892◊167260.057150.087450.393561084.1815.1890.0331.6-13BK
    TBA16870.057200.097450.417721234.1815.1890.0331.7-13BK
    604918◊169260.057150.087450.455721354.1815.1890.0331.8-13BK
    TBA161070.057200.097450.484881504.1815.1890.0331.9-9BK
    604942◊1612260.057150.087450.51961754.1815.1890.0332-9BK
    6049751615260.057150.087600.5961202274.1815.1890.0332.4-9BK
    605014◊1619260.057150.087600.6251522754.1815.1890.0332.5-9BK
    TBA162070.057200.097600.6411692854.1815.1890.0332.6-9BK
    6050711625260.057150.087600.72023504.1815.1890.0332.8-8BK
    6051211630260.057150.087600.7672424134.1815.1890.0333.1-8BK
    605196◊1637260.057150.087800.8672985294.1815.1890.0333.5-7BK
    14 AWG
    408484◊14270.071150.101450.31826592.6313.2650.0581.32025BK
    408518◊14370.071150.101450.33438772.6313.2650.0581.32025BK
    408542◊14470.071150.101450.36551982.6313.2650.0581.51620BK
    408575◊14570.071150.101450.395641142.6313.2650.0581.61620BK
    60883614670.071150.101450.433771352.6313.2650.0581.71620BK
    TBA14870.071200.111450.4631181772.6313.2650.0581.91418BK
    408740◊14970.071150.101450.491151872.6313.2650.05821418BK
    605477141070.071150.101600.5781282302.6313.2650.0582.31012BK
    408807◊141270.071150.101600.5961542652.6313.2650.0582.41012BK
    412874141570.071150.101600.6581923232.6313.2650.0582.61012BK
    412908◊141970.071150.101600.6912443962.6313.2650.0582.81012BK
    608729142070.071150.101600.7262574172.6313.2650.0582.91012BK
    552133◊142570.071150.101600.8043205082.6313.2650.0583.2911BK
    557553143070.071150.101800.8823846192.6313.2650.0583.5911BK
    552190◊143770.071150.101800.9594757612.6313.2650.0583.8810BK
    12 AWG
    408468◊12270.089150.119450.35241781.6622.0630.0541.42530BK
    408526◊12370.089150.119450.373611091.6622.0630.0541.52530BK
    408559◊12470.089150.119450.405811511.6622.0630.0541.62024BK
    408583◊12570.089150.119450.4441021851.6622.0630.0541.82024BK
    408641◊12770.089150.119450.4781432361.6622.0630.0541.91821BK
    60873712670.089150.119450.4871221911.6622.0630.0541.92024BK
    TBA12870.089200.129600.5531812641.6622.0630.0542.21821BK
    408757◊12970.089150.119600.581833291.6622.0630.0542.31821BK
    TBA121070.089200.129600.6422223231.6622.0630.0542.61215BK
    408815◊121270.089150.119600.6652444291.6622.0630.0542.71215BK
    412882121570.089150.119600.7433054591.6622.0630.05431215BK
    622420121670.089150.119600.7473264821.6622.0630.05431215BK
    412916121970.089150.119600.7813885671.6622.0630.0543.11215BK
    TBA122070.089200.129600.8114245811.6622.0630.0543.21215BK
    552166122570.089150.119800.9545097681.6622.0630.0543.81114BK
    TBA123070.089200.129800.9936268711.6622.0630.05441114BK
    552224123770.089150.119851.07375510921.6622.0630.0545.41012BK
    10 AWG
    408492◊10270.113200.153450.42651151.041.2910.051.73540BK
    408534◊10370.113200.153450.45971621.041.2910.051.83540BK
    408567◊10470.113200.153450.5051292081.041.2910.0522832BK
    408591◊10570.113200.153600.5661622581.041.2910.052.32832BK
    TBA10670.113250.163600.6152253211.041.2910.052.52832BK
    408658◊10770.113200.153600.6152273811.041.2910.052.52428BK
    TBA10870.113250.163600.6662904031.041.2910.052.72428BK
    408765◊10970.113200.153600.7162915021.041.2910.052.92428BK
    TBA101070.113250.163600.7783554921.041.2910.053.11820BK
    408823◊101270.113200.153600.8063886531.041.2910.053.21820BK
    601666101970.113200.153800.9936139041.041.2910.0541820BK
    TBA102070.113250.163801.0326789351.041.2910.055.21820BK
    TBA102570.113250.163801.14484011431.041.2910.055.71618BK
    TBA103070.113250.163801.211100113441.041.2910.056.11618BK
    TBA103770.113250.163801.307122716271.041.2910.056.51416BK
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    *Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
    *Ampacities have been adjusted for more than Three Current-Carrying Conductors.