SPEC 25030
CSA TECK 90 CU 3/C 5000V NON-SHIELDED EPR POWER CABLE
5000V, Non-Shielded, EPR Insulated, FT4, -40°C, HL (Hazardous Locations), AG14 & 90°C

Construction:
- Conductor:Class B stranded copper, compressed or compact, in accordance with ASTM B3 and B8.
- Conductor Shield:Extruded semi-conducting thermosetting polymeric layer
- Insulation:No-Lead EPR (ethylene propylene rubber), Thickness: 0.090” (2.3 mm) - nominal, 90°C
- Grounding Conductor:Class B compressed or compact stranded bare copper, in accordance with ASTM B3 and B8
- Binder:Polypropylene tape
- Inner Jacket:Black PVC, Thickness: No. 2 AWG to No. 3/0 AWG = 0.080” (2.0 mm); No. 4/0 AWG to 500 kcmil = 0.110” (2.8 mm); 750 kcmil to 1000 kcmil = 0.140” (3.6 mm)
- Armor:Aluminum Interlocked Armour (AIA)
- Overall Jacket:Orange PVC (optional colours available), Thickness: No. 2 AWG to 250 kcmil = 0.060” (1.5 mm); 350 kcmil to 750 kcmil = 0.075” (1.9 mm); 1000 kcmil = 0.090” (2.3 mm)
Applications and Features:
Southwire’s 5KV TECK 90, 5000V, non-shielded, EPR insulated power cable is a CSA approved armoured cable for industrial and commercial medium voltage applications. FT4, -40°C, HL, AG14 and 90°C rated for use in harsh Canadian environments. Rated for installation in cable trays, duct banks, direct burial, troughs, hazardous locations, continuous rigid cable supports, and is concrete encaseable.
- -40°C - CSA Cold Bend and Impact Temperature
- -25°C - Min. Installation Temperature
- 90°C - Max. Continuous Operating Temperature
- 140°C for Emergency Overload Temperature
- 250°C for Short Circuit Temperature
Specifications:
Sample Print Legend:
SOUTHWIRE {CSA} LL90458 3/C XX KCMIL CU TECK 90 EPCV CDRS WITH GROUND -40°C FT4 SUN. RES. AG14 5000V HL {YYYY} USA {SEQUENTIAL METER MARKS}
Table 1 – Weights and Measurements
| Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Ground | Ground Size | Inner Jacket Thickness | Dia. Over Inner Jacket | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | inch | inch | mil | No. x AWG | AWG | mil | inch | inch | mil | inch | lb/1000ft | lb/1000ft | |
| 568467◊ | 2 | 7 | 0.283 | 0.505 | 90 | 1x6 | 6 | 85 | 1.267 | 1.585 | 55 | 1.695 | 703 | 1548 |
| 568468◊ | 1 | 19 | 0.322 | 0.55 | 90 | 1x6 | 6 | 85 | 1.364 | 1.682 | 55 | 1.792 | 865 | 1788 |
| 568470◊ | 1/0 | 19 | 0.362 | 0.59 | 90 | 1x6 | 6 | 85 | 1.45 | 1.769 | 55 | 1.879 | 1070 | 2055 |
| 568471◊ | 2/0 | 19 | 0.405 | 0.634 | 90 | 1x6 | 6 | 85 | 1.545 | 1.874 | 55 | 1.984 | 1327 | 2439 |
| 568472◊ | 3/0 | 19 | 0.456 | 0.684 | 90 | 1x4 | 4 | 85 | 1.653 | 1.982 | 55 | 2.092 | 1700 | 2893 |
| 568473◊ | 4/0 | 19 | 0.512 | 0.726 | 90 | 1x4 | 4 | 115 | 1.804 | 2.136 | 55 | 2.246 | 2110 | 3497 |
| 568474◊ | 250 | 37 | 0.558 | 0.778 | 90 | 1x4 | 4 | 115 | 1.916 | 2.248 | 55 | 2.358 | 2469 | 3954 |
| 568475◊ | 350 | 37 | 0.661 | 0.877 | 90 | 1x3 | 3 | 115 | 2.13 | 2.462 | 65 | 2.594 | 3439 | 5154 |
| 568476◊ | 500 | 37 | 0.789 | 1.002 | 90 | 1x3 | 3 | 115 | 2.4 | 2.732 | 65 | 2.864 | 4842 | 6785 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Other conductor sizes and outer jacket colours are available upon request. (#s in brackets represent # of strands / conductor. Number of strands may vary as per CSA standard.)
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Inductive Reactance @ 60Hz | Allowable Ampacity In Raceway 90°C |
|---|---|---|---|---|---|---|
| AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp |
| 2 | 11.9 | 1592 | 0.162 | 0.221 | 0.045 | 130 |
| 1 | 12.5 | 2008 | 0.128 | 0.175 | 0.046 | 145 |
| 1/0 | 13.2 | 2534 | 0.102 | 0.139 | 0.044 | 170 |
| 2/0 | 13.9 | 3194 | 0.082 | 0.112 | 0.043 | 195 |
| 3/0 | 14.6 | 4027 | 0.064 | 0.087 | 0.042 | 225 |
| 4/0 | 15.7 | 5078 | 0.051 | 0.07 | 0.041 | 260 |
| 250 | 16.5 | 6000 | 0.043 | 0.059 | 0.041 | 290 |
| 350 | 18.2 | 8400 | 0.031 | 0.043 | 0.04 | 350 |
| 500 | 20 | 12000 | 0.021 | 0.03 | 0.039 | 430 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
Table 3 – Weights and Measurements (Metric)
| Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Ground | Ground Size | Inner Jacket Thickness | Dia. Over Inner Jacket | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | mm | mm | mm | No. x AWG | AWG | mm | mm | mm | mm | mm | kg/km | kg/km | |
| 568467◊ | 2 | 7 | 7.19 | 12.83 | 2.29 | 1x6 | 6 | 2.16 | 32.18 | 40.26 | 1.40 | 43.05 | 1046 | 2304 |
| 568468◊ | 1 | 19 | 8.18 | 13.97 | 2.29 | 1x6 | 6 | 2.16 | 34.65 | 42.72 | 1.40 | 45.52 | 1287 | 2661 |
| 568470◊ | 1/0 | 19 | 9.19 | 14.99 | 2.29 | 1x6 | 6 | 2.16 | 36.83 | 44.93 | 1.40 | 47.73 | 1592 | 3058 |
| 568471◊ | 2/0 | 19 | 10.29 | 16.10 | 2.29 | 1x6 | 6 | 2.16 | 39.24 | 47.60 | 1.40 | 50.39 | 1975 | 3630 |
| 568472◊ | 3/0 | 19 | 11.58 | 17.37 | 2.29 | 1x4 | 4 | 2.16 | 41.99 | 50.34 | 1.40 | 53.14 | 2530 | 4305 |
| 568473◊ | 4/0 | 19 | 13.00 | 18.44 | 2.29 | 1x4 | 4 | 2.92 | 45.82 | 54.25 | 1.40 | 57.05 | 3140 | 5204 |
| 568474◊ | 250 | 37 | 14.17 | 19.76 | 2.29 | 1x4 | 4 | 2.92 | 48.67 | 57.10 | 1.40 | 59.89 | 3674 | 5884 |
| 568475◊ | 350 | 37 | 16.79 | 22.28 | 2.29 | 1x3 | 3 | 2.92 | 54.10 | 62.53 | 1.65 | 65.89 | 5118 | 7670 |
| 568476◊ | 500 | 37 | 20.04 | 25.45 | 2.29 | 1x3 | 3 | 2.92 | 60.96 | 69.39 | 1.65 | 72.75 | 7206 | 10097 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Other conductor sizes and outer jacket colours are available upon request. (#s in brackets represent # of strands / conductor. Number of strands may vary as per CSA standard.)
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 4 – Electrical and Engineering Data (Metric)
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Inductive Reactance @ 60Hz | Allowable Ampacity In Raceway 90°C |
|---|---|---|---|---|---|---|
| AWG/Kcmil | mm | newton | Ω/km | Ω/km | Ω/km | Amp |
| 2 | 302.26 | 7084 | 0.5315 | 0.73 | 0.1476 | 130 |
| 1 | 317.50 | 8936 | 0.4199 | 0.57 | 0.1509 | 145 |
| 1/0 | 335.28 | 11276 | 0.3346 | 0.46 | 0.1444 | 170 |
| 2/0 | 353.06 | 14213 | 0.2690 | 0.37 | 0.1411 | 195 |
| 3/0 | 370.84 | 17920 | 0.2100 | 0.29 | 0.1378 | 225 |
| 4/0 | 398.78 | 22597 | 0.1673 | 0.23 | 0.1345 | 260 |
| 250 | 419.10 | 26700 | 0.1411 | 0.19 | 0.1345 | 290 |
| 350 | 462.28 | 37380 | 0.1017 | 0.14 | 0.1312 | 350 |
| 500 | 508.00 | 53400 | 0.0689 | 0.10 | 0.1280 | 430 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.