SPEC 22061

RW90 Copper Circuit Sizes (14, 12 & 10 AWG)

Copper Conductor, 600V, 90°C MAX, -40°C MIN. Sunlight Resistant in Black Only.

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Insulation:Cross Linked Polyethylene (XLPE)

Applications and Features:

Single copper conductor with low temperature, moisture resisting XLPE (cross linked polyethylene) insulation. Sunlight Resistant in black only. This product meets the current RoHS requirements. No lead is added or used in manufacturing.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 38 Thermoset-insulated wires and cables
  • CSA SUN RES - for Sunlight Resistant rating
  • Sample Print Legend:

    SOUTHWIRE& LL90458 (CSA) 12 AWG CU RW90 XLPE 600 VOLTS (-40°C) SR
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandInsul. ThicknessInsulation ColorApprox. ODApprox. WeightMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity In Raceway 90°C
    AWG/KcmilNo.milinchlb/1000ftinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmp
    956110◊14SOLID30BK0.128170.5322.6313.2650.05825
    956177◊14SOLID30RD0.128170.5322.6313.2650.05825
    557917◊14SOLID30OE0.128170.5322.6313.2650.05825
    956144◊14SOLID30WE0.128170.5322.6313.2650.05825
    956250◊14SOLID30BN0.128170.5322.6313.2650.05825
    956235◊14SOLID30BE0.128170.5322.6313.2650.05825
    956201◊14SOLID30GN0.128170.5322.6313.2650.05825
    956276◊14SOLID30YW0.128170.5322.6313.2650.05825
    955666◊14730BE0.135180.5322.6313.2650.05825
    955245◊14730RD0.135180.5322.6313.2650.05825
    955617◊14730GN0.135180.5322.6313.2650.05825
    955708◊14730YW0.135180.5322.6313.2650.05825
    951731◊14730BK0.135180.5322.6313.2650.05825
    557924◊14730OE0.135180.5322.6313.2650.05825
    955682◊14730BN0.135180.5322.6313.2650.05825
    955351◊14730WE0.135180.5322.6313.2650.05825
    956227◊12SOLID30BE0.145250.6521.6622.0630.05430
    956243◊12SOLID30BN0.145250.6521.6622.0630.05430
    956169◊12SOLID30RD0.145250.6521.6622.0630.05430
    956102◊12SOLID30BK0.145250.6521.6622.0630.05430
    956268◊12SOLID30YW0.145250.6521.6622.0630.05430
    956136◊12SOLID30WE0.145250.6521.6622.0630.05430
    956193◊12SOLID30GN0.145250.6521.6622.0630.05430
    557861◊12SOLID30OE0.145250.6521.6622.0630.05430
    955690◊12730YW0.153260.6521.6622.0630.05430
    95174912730BK0.153260.6321.6622.0630.05430
    955658◊12730BE0.153260.6521.6622.0630.05430
    955674◊12730BN0.153260.6521.6622.0630.05430
    955237◊12730RD0.153260.6521.6622.0630.05430
    557923◊12730OE0.153260.6521.6622.0630.05430
    955609◊12730GN0.153260.6521.6622.0630.05430
    955344◊12730WE0.153260.6521.6622.0630.05430
    557931◊10SOLID30YW0.166370.7831.041.2910.0540
    956219◊10SOLID30BE0.166370.7831.041.2910.0540
    956185◊10SOLID30GN0.166370.7831.041.2910.0540
    956128◊10SOLID30WE0.166370.7831.041.2910.0540
    557929◊10SOLID30BN0.166370.7831.041.2910.0540
    956094◊10SOLID30BK0.166370.7831.041.2910.0540
    557930◊10SOLID30OE0.166370.7831.041.2910.0540
    956151◊10SOLID30RD0.166370.7831.041.2910.0540
    955591◊10730GN0.177390.7831.041.2910.0540
    557921◊10730OE0.177390.7831.041.2910.0540
    955641◊10730BE0.177390.7831.041.2910.0540
    557920◊10730BN0.177390.7831.041.2910.0540
    557922◊10730YW0.177390.7831.041.2910.0540
    955229◊10730RD0.177390.7831.041.2910.0540
    955336◊10730WE0.177390.7831.041.2910.0540
    95175610730BK0.177390.7521.041.2910.0540
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    †Ampacities derived from the 2015 Canadian Electrical Code - Table 1 - For single conductor in free air and based on an ambient temperature of 30°C. - Table 2 - for Cable in Conduit. Not more than 3 aluminum conductors in a conduit and based on an ambient temperature of 30°C.
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandInsul. ThicknessInsulation ColorApprox. ODApprox. WeightMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity In Raceway 90°C
    AWG/KcmilNo.mmmmkg/kmmmnewtonΩ/kmΩ/kmΩ/kmAmp
    956110◊14SOLID0.76BK3.252512.701428.6310.710.190325
    956177◊14SOLID0.76RD3.252512.701428.6310.710.190325
    557917◊14SOLID0.76OE3.252512.701428.6310.710.190325
    956144◊14SOLID0.76WE3.252512.701428.6310.710.190325
    956250◊14SOLID0.76BN3.252512.701428.6310.710.190325
    956235◊14SOLID0.76BE3.252512.701428.6310.710.190325
    956201◊14SOLID0.76GN3.252512.701428.6310.710.190325
    956276◊14SOLID0.76YW3.252512.701428.6310.710.190325
    955666◊1470.76BE3.432712.701428.6310.710.190325
    955245◊1470.76RD3.432712.701428.6310.710.190325
    955617◊1470.76GN3.432712.701428.6310.710.190325
    955708◊1470.76YW3.432712.701428.6310.710.190325
    951731◊1470.76BK3.432712.701428.6310.710.190325
    557924◊1470.76OE3.432712.701428.6310.710.190325
    955682◊1470.76BN3.432712.701428.6310.710.190325
    955351◊1470.76WE3.432712.701428.6310.710.190325
    956227◊12SOLID0.76BE3.683715.242315.456.770.177230
    956243◊12SOLID0.76BN3.683715.242315.456.770.177230
    956169◊12SOLID0.76RD3.683715.242315.456.770.177230
    956102◊12SOLID0.76BK3.683715.242315.456.770.177230
    956268◊12SOLID0.76YW3.683715.242315.456.770.177230
    956136◊12SOLID0.76WE3.683715.242315.456.770.177230
    956193◊12SOLID0.76GN3.683715.242315.456.770.177230
    557861◊12SOLID0.76OE3.683715.242315.456.770.177230
    955690◊1270.76YW3.893915.242315.456.770.177230
    9517491270.76BK3.893915.241425.456.770.177230
    955658◊1270.76BE3.893915.242315.456.770.177230
    955674◊1270.76BN3.893915.242315.456.770.177230
    955237◊1270.76RD3.893915.242315.456.770.177230
    557923◊1270.76OE3.893915.242315.456.770.177230
    955609◊1270.76GN3.893915.242315.456.770.177230
    955344◊1270.76WE3.893915.242315.456.770.177230
    557931◊10SOLID0.76YW4.225517.783693.414.240.164040
    956219◊10SOLID0.76BE4.225517.783693.414.240.164040
    956185◊10SOLID0.76GN4.225517.783693.414.240.164040
    956128◊10SOLID0.76WE4.225517.783693.414.240.164040
    557929◊10SOLID0.76BN4.225517.783693.414.240.164040
    956094◊10SOLID0.76BK4.225517.783693.414.240.164040
    557930◊10SOLID0.76OE4.225517.783693.414.240.164040
    956151◊10SOLID0.76RD4.225517.783693.414.240.164040
    955591◊1070.76GN4.505817.783693.414.240.164040
    557921◊1070.76OE4.505817.783693.414.240.164040
    955641◊1070.76BE4.505817.783693.414.240.164040
    557920◊1070.76BN4.505817.783693.414.240.164040
    557922◊1070.76YW4.505817.783693.414.240.164040
    955229◊1070.76RD4.505817.783693.414.240.164040
    955336◊1070.76WE4.505817.783693.414.240.164040
    9517561070.76BK4.505817.782313.414.240.164040
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    †Ampacities derived from the 2015 Canadian Electrical Code - Table 1 - For single conductor in free air and based on an ambient temperature of 30°C. - Table 2 - for Cable in Conduit. Not more than 3 aluminum conductors in a conduit and based on an ambient temperature of 30°C.
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

    Table 3 - Stock Code Colors

    Size (Strand)BlackRedBlueWhiteBrownOrangeYellowGreen
    14 (Solid)956110956177956235956144956250557917956276956201
    14 (7)951731955245955666955351955682557924955708955617
    12 (Solid)956102956169956227956136956243557861956268956193
    12 (7)951749955237955658955344955674557923955690955609
    10 (Solid)956094956151956219956128557929557930557931956185
    10 (7)951756955229955641955336557920557921557922955591

    Revision: 1.000.017

    Updated On: Oct. 20, 2025, 1:45 p.m. UTC