SPEC 22053

NMWU Copper

Copper Conductors, 300V / -40ºC MIN, 60ºC MAX, PVC Insulation, PVC Jacket

...

Construction:

  1. Conductor:Bare copper per ASTM B3. Sizes #14 AWG - #10 AWG are solid. Sizes #8 AWG - #2 AWG are Class B compressed stranded per ASTM B8.
  2. Insulation:All phases are insulated with heat-resistant thermoplastic polyvinyl chloride (PVC) insulation
  3. Jacket:Polyvinyl Chloride (PVC) jacket. Sunlight, moisture, and fungus-resistant

  • Conductor Colors: 2/C Black, White
  • Conductor Colors: 3/C Black, Red, White
  • Applications and Features:

    Southwire's CSA-NWMU cables may be used for underground installations, including direct burial. It may also be used for environments exposed to the weather in dry and wet locations. The maximum allowable conductor temperature is 60°C. The minimum recommended installation temperature is -40°C for two-conductor cables (sizes AWG 14 to AWG 6) and -25°C for all other sizes. For three-conductor cables the minimum recommended installation temperature is -10°C (with suitable handling procedures). Material should be properly stored above 0°C for 24 hours prior to installation. The maximum voltage rating for all intended applications is 300 volts. Consult the Canadian Electrical Code for further information related to applications.

    Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 48 non-metallic sheathed cable
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • Sample Print Legend:

    SOUTHWIRE LL90458 MASTER-DESIGN CSA XX AWG CU XX CDRS NMWU 300 VOLTS FT1
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeConductor NumberDiameter Over ConductorConductor StrandingInsulation ThicknessGround SizeJacket ThicknessApprox. ODCopper WeightOverall Weight
    AWG/KcmilinchmilsNo. x AWGmilinchlbs/1000ftlbs/1000ft
    14 AWG | Solid
    471847◊1420.064Solid601 x 14300.244x0.4923788
    471888◊1430.064Solid601 x 14300.50450117
    12 AWG | Solid
    471854◊1220.080Solid601 x 14300.261x0.52651109
    471896◊1230.080Solid601 x 14300.54472148
    10 AWG | Solid
    471863◊1020.101Solid601 x 12300.282x0.58582146
    471912◊1030.101Solid601 x 12300.595115200
    471870◊820.1437751 x 10450.382x0.775133253
    471920◊830.1437751 x 10450.794186344
    481275◊620.1797901 x 8450.448x0.948213375
    471938◊630.1797901 x 8450.954297513
    672626◊430.2267901 x 6601.097470755
    672634◊230.2867901 x 6801.2777021085
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Table 2 – Electrical and Engineering Data
    Cond. SizeConductor NumberMin. Bend RadiusDC Resistance at 25°CAC Resistance at 75°CInductive Reactance @ 60HzAllowable Ampacity Raceway 75°CAllowable Ampacity Raceway 90°C
    AWG/KcmilInchesΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    14 AWG | Solid
    1422.0002.6313.1700.0582025
    1432.0162.6313.1700.0582025
    12 AWG | Solid
    1222.4001.6622.0020.0542530
    1232.1761.6622.0020.0542530
    10 AWG | Solid
    1022.3001.0401.2530.0503540
    1032.3801.0401.2530.0503540
    823.1000.6530.7860.0525055
    833.1760.6530.7860.0525055
    623.6000.4110.4950.0516575
    633.8160.4110.4950.0516575
    435.4850.2580.3100.0488595
    236.3850.1620.1950.045115130
    * Ampacity values based on Canadian Electrical Code, Part 1 2024 Table 2 and do not take into account the overcurrent protection limitations in CEC Rule 14-104(2) of 15 A for 14 AWG Cu, 20 A for 12 AWG Cu, and 30 A for 10 AWG Cu (independent of the conductor temperature rating and stranding). See also CEC Rules 4-004 and 4-006 for additional requirements.
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.

    Revision: 1.000.009

    Updated On: May 1, 2025, 6:46 p.m. UTC