SPEC 10006

Copper SIMpull XHHW-2®/RW90

Conductor size 8 AWG and larger. Power Cable 600 or 1000 Volt Single Conductor Copper, Cross Linked Polyethylene (XLPE) with SIMpull technology for easier pulling.

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Insulation:Cross Linked Polyethylene (XLPE) with SIMpull technology

Applications and Features:

APPLICATION
Southwire® SIMpull XHHW-2®/RW90 copper conductors are primarily used in conduit, cable tray or other recognized raceways for services, feeders, and branch circuit wiring, as specified in the National Electrical Code. SIMpull XHHW-2®/RW90 copper conductors may be used in wet or dry locations at temperatures not to exceed 90°C. Voltage rating for XHHW-2 conductors is 600 volts or 1000 volts for all sizes. Suitable for use in Health Care Facilities per Section 517.160 of the National Electrical Code where a dielectric constant of less than 3.5 maybe specified. This cable is designed to be installed without the application of pulling lubricant. RW90 is for open wiring and use in raceways (except cabletroughs and ventilated flexible cableways) in dry or wet locations as per Canadian Electrical Code. For open wiring exposed to the weather.

FEATURES
  • SIS - 8 AWG
  • Sunlight resistant
  • -40°C Cold bend
  • FT1
  • Gasoline and Oil Resistant II
  • CT Rated - 1/0 AWG and larger
  • FT4 - 350 kcmil and larger
  • RoHS/REACH Compliant
  • SPEC 10005 for circuit sizes 14 AWG, 12 AWG, and 10 AWG
  • Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B787 19 Wire Combination Unilay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test (1/0 and Larger)
  • CSA C22.2 No. 38 Thermoset-insulated wires and cables
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202/FT4 Flame Test (70,000 BTU/hr) 350kcmil and Larger
  • Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661
  • Federal Specification A-A-59544
  • NMX-J-451-ANCE Thermoset insulated wires and cables
  • NOM-063-SCFI Electrical Products – Conductors – Safety Requirements
  • Sample Print Legend:

    8 AWG thru 1 AWG
    {SQFTG} SOUTHWIRE{R} {NOLUBE}{R} {SIMPULL}{R} E30117 {UL} TYPE XHHW-2 8 AWG (8.37{MM2}) CU 600V/1000V SR GRII PRII OR SIS 600V - LL90458 {CSA} RW90 XLPE 8 AWG (8.37{mm2}) CU 600V GRI PRI -40{D}C SR FT1 - {NOM}-ANCE LS - PAT WWW.PATENTSW.COM

    1/0 AWG thru 300 kcmil
    {SQFTG} SOUTHWIRE{R} {NOLUBE}{R} {SIMPULL}{R} E30117 {UL} TYPE XHHW-2 1/0 AWG (53.5{MM2}) CU 600V/1000V SR FOR CT USE GRII PRII - LL90458 {CSA} RW90 XLPE 1/0 AWG (53.5{mm2}) CU 600V GRI PRI -40{D}C SR FT1 - {NOM}-ANCE LS - PAT WWW.PATENTSW.COM

    350 kcmil and Larger
    {SQFTG} SOUTHWIRE{R} {NOLUBE}{R} {SIMPULL}{R} E30117 {UL} TYPE XHHW-2 350 KCMIL (177{MM2}) CU 600V/1000V SR FOR CT USE GRII PRII FT4 - LL90458 {CSA} RW90 XLPE 350 KCMIL (177{mm2}) CU 600V GRI PRI -40{D}C SR FT4 - {NOM}-ANCE LS - PAT WWW.PATENTSW.COM
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandDiameter Over ConductorInsul. ThicknessApprox. ODCopper WeightApprox. Weight
    AWG/KcmilNo.inchmilinchlb/1000ftlb/1000ft
    550361870.141450.2385064
    112953870.141450.2385064
    952721870.141450.2385064
    553062870.141450.2385064
    553060870.141450.2385064
    553063870.141450.2385064
    952739870.141450.2385064
    952713870.141450.2385064
    553059870.141450.2385064
    112961670.177450.2748197
    683391670.177450.2748197
    678607670.177450.2748197
    553067670.177450.2748197
    683383670.177450.2748197
    553068670.177450.2748197
    553230670.177450.2748197
    952705670.177450.2748197
    959916670.177450.2748197
    112979470.225450.321128148
    553848470.225450.321128148
    678599470.225450.321128148
    553847470.225450.321128148
    553850470.225450.321128148
    558627470.225450.321128148
    952697470.225450.321128148
    553846470.225450.321128148
    267278370.252450.348162184
    890469370.252450.348162184
    112987270.282450.379204228
    553089270.282450.379204228
    218107270.282450.379204228
    553090270.282450.379204228
    553088270.282450.379204228
    553091270.282450.379204228
    474122270.282450.379204228
    218115270.282450.379204228
    553087270.282450.379204228
    5538551190.322550.435258291
    5508081190.322550.435258291
    5538561190.322550.435258291
    5538541190.322550.435258291
    5538571190.322550.435258291
    5507661190.322550.435258291
    5507611190.322550.435258291
    5507621190.322550.435258291
    1129951190.322550.435258291
    5538641/0190.361550.480326363
    5538581/0190.361550.480326363
    1130011/0190.361550.480326363
    5538651/0190.361550.480326363
    5538631/0190.361550.480326363
    5538661/0190.361550.480326363
    5538621/0190.361550.480326363
    5538601/0190.361550.480326363
    5538611/0190.361550.480326363
    5538742/0190.405550.524410452
    5538702/0190.405550.524410452
    1130192/0190.405550.524410452
    5538762/0190.405550.524410452
    5538732/0190.405550.524410452
    5538772/0190.405550.524410452
    5520702/0190.405550.524410452
    5538712/0190.405550.524410452
    5538722/0190.405550.524410452
    5538823/0190.456550.574518564
    5538863/0190.456550.574518564
    5538803/0190.456550.574518564
    1130273/0190.456550.574518564
    5538873/0190.456550.574518564
    5538853/0190.456550.574518564
    5538883/0190.456550.574518564
    5538843/0190.456550.574518564
    5538813/0190.456550.574518564
    5530794/0190.512550.630655707
    5530824/0190.512550.630655707
    1130354/0190.512550.630655707
    5530774/0190.512550.630655707
    5530834/0190.512550.630655707
    5530804/0190.512550.630655707
    5530844/0190.512550.630655707
    5520714/0190.512550.630655707
    5530784/0190.512550.630655707
    553894250370.558650.700771838
    553897250370.558650.700771838
    113043250370.558650.700771838
    553892250370.558650.700771838
    553898250370.558650.700771838
    553896250370.558650.700771838
    553899250370.558650.700771838
    553895250370.558650.700771838
    553893250370.558650.700771838
    561130300370.610650.753926998
    113050300370.610650.753926998
    561131300370.610650.753926998
    561129300370.610650.753926998
    584039300370.610650.753926998
    553904350370.661650.80310801158
    553907350370.661650.80310801158
    113068350370.661650.80310801158
    553902350370.661650.80310801158
    553908350370.661650.80310801158
    553906350370.661650.80310801158
    553910350370.661650.80310801158
    553905350370.661650.80310801158
    553903350370.661650.80310801158
    561702400370.705650.84812351317
    113076400370.705650.84812351317
    561112400370.705650.84812351317
    561132400370.705650.84812351317
    561113400370.705650.84812351317
    561703400370.705650.84812351317
    558666400370.705650.84812351317
    561701400370.705650.84812351317
    561111400370.705650.84812351317
    550261500370.789650.90815431632
    113084500370.789650.90815431632
    550262500370.789650.90815431632
    553071500370.789650.90815431632
    550259500370.789650.90815431632
    553074500370.789650.90815431632
    553072500370.789650.90815431632
    550369500370.789650.90815431632
    550260500370.789650.90815431632
    553918600610.865801.03818521973
    553915600610.865801.03818521973
    113092600610.865801.03818521973
    553919600610.865801.03818521973
    553913600610.865801.03818521973
    553920600610.865801.03818521973
    553921600610.865801.03818521973
    553916600610.865801.03818521973
    553914600610.865801.03818521973
    553930750610.968801.14023152449
    113100750610.968801.14023152449
    553931750610.968801.14023152449
    553926750610.968801.14023152449
    553932750610.968801.14023152449
    553934750610.968801.14023152449
    553929750610.968801.14023152449
    553927750610.968801.14023152449
    1131341000611.117801.28930873240
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CInductive Reactance @ 60HzAllowable Ampacity In Raceway 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmp
    81.01320.6530.7860.05255
    81.01320.6530.7860.05255
    81.01320.6530.7860.05255
    81.01320.6530.7860.05255
    81.01320.6530.7860.05255
    81.01320.6530.7860.05255
    81.01320.6530.7860.05255
    81.01320.6530.7860.05255
    81.01320.6530.7860.05255
    61.12090.4110.4950.05175
    61.12090.4110.4950.05175
    61.12090.4110.4950.05175
    61.12090.4110.4950.05175
    61.12090.4110.4950.05175
    61.12090.4110.4950.05175
    61.12090.4110.4950.05175
    61.12090.4110.4950.05175
    61.12090.4110.4950.05175
    41.33330.2580.3100.04895
    41.33330.2580.3100.04895
    41.33330.2580.3100.04895
    41.33330.2580.3100.04895
    41.33330.2580.3100.04895
    41.33330.2580.3100.04895
    41.33330.2580.3100.04895
    41.33330.2580.3100.04895
    31.44200.2050.2460.047115
    31.44200.2050.2460.047115
    21.55300.1620.1950.045130
    21.55300.1620.1950.045130
    21.55300.1620.1950.045130
    21.55300.1620.1950.045130
    21.55300.1620.1950.045130
    21.55300.1620.1950.045130
    21.55300.1620.1950.045130
    21.55300.1620.1950.045130
    21.55300.1620.1950.045130
    11.76690.1280.1540.046145
    11.76690.1280.1540.046145
    11.76690.1280.1540.046145
    11.76690.1280.1540.046145
    11.76690.1280.1540.046145
    11.76690.1280.1540.046145
    11.76690.1280.1540.046145
    11.76690.1280.1540.046145
    11.76690.1280.1540.046145
    1/01.98440.1020.1220.044170
    1/01.98440.1020.1220.044170
    1/01.98440.1020.1220.044170
    1/01.98440.1020.1220.044170
    1/01.98440.1020.1220.044170
    1/01.98440.1020.1220.044170
    1/01.98440.1020.1220.044170
    1/01.98440.1020.1220.044170
    1/01.98440.1020.1220.044170
    2/02.110640.0810.0970.043195
    2/02.110640.0810.0970.043195
    2/02.110640.0810.0970.043195
    2/02.110640.0810.0970.043195
    2/02.110640.0810.0970.043195
    2/02.110640.0810.0970.043195
    2/02.110640.0810.0970.043195
    2/02.110640.0810.0970.043195
    2/02.110640.0810.0970.043195
    3/02.313420.0640.0780.042225
    3/02.313420.0640.0780.042225
    3/02.313420.0640.0780.042225
    3/02.313420.0640.0780.042225
    3/02.313420.0640.0780.042225
    3/02.313420.0640.0780.042225
    3/02.313420.0640.0780.042225
    3/02.313420.0640.0780.042225
    3/02.313420.0640.0780.042225
    4/02.516920.0510.0620.041260
    4/02.516920.0510.0620.041260
    4/02.516920.0510.0620.041260
    4/02.516920.0510.0620.041260
    4/02.516920.0510.0620.041260
    4/02.516920.0510.0620.041260
    4/02.516920.0510.0620.041260
    4/02.516920.0510.0620.041260
    4/02.516920.0510.0620.041260
    2502.820000.0430.0530.041290
    2502.820000.0430.0530.041290
    2502.820000.0430.0530.041290
    2502.820000.0430.0530.041290
    2502.820000.0430.0530.041290
    2502.820000.0430.0530.041290
    2502.820000.0430.0530.041290
    2502.820000.0430.0530.041290
    2502.820000.0430.0530.041290
    3003.024000.0360.0450.041320
    3003.024000.0360.0450.041320
    3003.024000.0360.0450.041320
    3003.024000.0360.0450.041320
    3003.024000.0360.0450.041320
    3503.228000.0310.0390.040350
    3503.228000.0310.0390.040350
    3503.228000.0310.0390.040350
    3503.228000.0310.0390.040350
    3503.228000.0310.0390.040350
    3503.228000.0310.0390.040350
    3503.228000.0310.0390.040350
    3503.228000.0310.0390.040350
    3503.228000.0310.0390.040350
    4003.432000.0270.0350.040380
    4003.432000.0270.0350.040380
    4003.432000.0270.0350.040380
    4003.432000.0270.0350.040380
    4003.432000.0270.0350.040380
    4003.432000.0270.0350.040380
    4003.432000.0270.0350.040380
    4003.432000.0270.0350.040380
    4003.432000.0270.0350.040380
    5003.640000.0220.0290.039430
    5003.640000.0220.0290.039430
    5003.640000.0220.0290.039430
    5003.640000.0220.0290.039430
    5003.640000.0220.0290.039430
    5003.640000.0220.0290.039430
    5003.640000.0220.0290.039430
    5003.640000.0220.0290.039430
    5003.640000.0220.0290.039430
    6005.248000.0180.0250.039475
    6005.248000.0180.0250.039475
    6005.248000.0180.0250.039475
    6005.248000.0180.0250.039475
    6005.248000.0180.0250.039475
    6005.248000.0180.0250.039475
    6005.248000.0180.0250.039475
    6005.248000.0180.0250.039475
    6005.248000.0180.0250.039475
    7505.760000.0140.0220.038535
    7505.760000.0140.0220.038535
    7505.760000.0140.0220.038535
    7505.760000.0140.0220.038535
    7505.760000.0140.0220.038535
    7505.760000.0140.0220.038535
    7505.760000.0140.0220.038535
    7505.760000.0140.0220.038535
    10006.480000.0110.0180.037615
    *Ampacities based upon 2023 NEC Table 310.16 Raceway or Cable, Not more than 3 copper conductors on an ambient temperature of 30°C.
    *Ampacities derived from the 2021 Canadian Electrical Code. - Table 2 - for Raceway or Cable. Not more than 3 copper conductors on an ambient temperature of 30°C.
    * Inductive Reactance is based on non-ferrous conduit with one diameter spacing.
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandDiameter Over ConductorInsul. ThicknessApprox. ODCopper WeightApprox. Weight
    AWG/KcmilNo.mmmmmmkg/kmkg/km
    550361873.581.146.057495
    112953873.581.146.057495
    952721873.581.146.057495
    553062873.581.146.057495
    553060873.581.146.057495
    553063873.581.146.057495
    952739873.581.146.057495
    952713873.581.146.057495
    553059873.581.146.057495
    112961674.501.146.96121144
    683391674.501.146.96121144
    678607674.501.146.96121144
    553067674.501.146.96121144
    683383674.501.146.96121144
    553068674.501.146.96121144
    553230674.501.146.96121144
    952705674.501.146.96121144
    959916674.501.146.96121144
    112979475.721.148.15190220
    553848475.721.148.15190220
    678599475.721.148.15190220
    553847475.721.148.15190220
    553850475.721.148.15190220
    558627475.721.148.15190220
    952697475.721.148.15190220
    553846475.721.148.15190220
    267278376.401.148.84241274
    890469376.401.148.84241274
    112987277.161.149.63304339
    553089277.161.149.63304339
    218107277.161.149.63304339
    553090277.161.149.63304339
    553088277.161.149.63304339
    553091277.161.149.63304339
    474122277.161.149.63304339
    218115277.161.149.63304339
    553087277.161.149.63304339
    5538551198.181.4011.05384433
    5508081198.181.4011.05384433
    5538561198.181.4011.05384433
    5538541198.181.4011.05384433
    5538571198.181.4011.05384433
    5507661198.181.4011.05384433
    5507611198.181.4011.05384433
    5507621198.181.4011.05384433
    1129951198.181.4011.05384433
    5538641/0199.171.4012.19485540
    5538581/0199.171.4012.19485540
    1130011/0199.171.4012.19485540
    5538651/0199.171.4012.19485540
    5538631/0199.171.4012.19485540
    5538661/0199.171.4012.19485540
    5538621/0199.171.4012.19485540
    5538601/0199.171.4012.19485540
    5538611/0199.171.4012.19485540
    5538742/01910.291.4013.31610673
    5538702/01910.291.4013.31610673
    1130192/01910.291.4013.31610673
    5538762/01910.291.4013.31610673
    5538732/01910.291.4013.31610673
    5538772/01910.291.4013.31610673
    5520702/01910.291.4013.31610673
    5538712/01910.291.4013.31610673
    5538722/01910.291.4013.31610673
    5538823/01911.581.4014.58771839
    5538863/01911.581.4014.58771839
    5538803/01911.581.4014.58771839
    1130273/01911.581.4014.58771839
    5538873/01911.581.4014.58771839
    5538853/01911.581.4014.58771839
    5538883/01911.581.4014.58771839
    5538843/01911.581.4014.58771839
    5538813/01911.581.4014.58771839
    5530794/01913.001.4016.009751052
    5530824/01913.001.4016.009751052
    1130354/01913.001.4016.009751052
    5530774/01913.001.4016.009751052
    5530834/01913.001.4016.009751052
    5530804/01913.001.4016.009751052
    5530844/01913.001.4016.009751052
    5520714/01913.001.4016.009751052
    5530784/01913.001.4016.009751052
    5538942503714.171.6517.7811471247
    5538972503714.171.6517.7811471247
    1130432503714.171.6517.7811471247
    5538922503714.171.6517.7811471247
    5538982503714.171.6517.7811471247
    5538962503714.171.6517.7811471247
    5538992503714.171.6517.7811471247
    5538952503714.171.6517.7811471247
    5538932503714.171.6517.7811471247
    5611303003715.491.6519.1313781485
    1130503003715.491.6519.1313781485
    5611313003715.491.6519.1313781485
    5611293003715.491.6519.1313781485
    5840393003715.491.6519.1313781485
    5539043503716.791.6520.4016071723
    5539073503716.791.6520.4016071723
    1130683503716.791.6520.4016071723
    5539023503716.791.6520.4016071723
    5539083503716.791.6520.4016071723
    5539063503716.791.6520.4016071723
    5539103503716.791.6520.4016071723
    5539053503716.791.6520.4016071723
    5539033503716.791.6520.4016071723
    5617024003717.911.6521.5418381960
    1130764003717.911.6521.5418381960
    5611124003717.911.6521.5418381960
    5611324003717.911.6521.5418381960
    5611134003717.911.6521.5418381960
    5617034003717.911.6521.5418381960
    5586664003717.911.6521.5418381960
    5617014003717.911.6521.5418381960
    5611114003717.911.6521.5418381960
    5502615003720.041.6523.0622962429
    1130845003720.041.6523.0622962429
    5502625003720.041.6523.0622962429
    5530715003720.041.6523.0622962429
    5502595003720.041.6523.0622962429
    5530745003720.041.6523.0622962429
    5530725003720.041.6523.0622962429
    5503695003720.041.6523.0622962429
    5502605003720.041.6523.0622962429
    5539186006121.972.0326.3727562936
    5539156006121.972.0326.3727562936
    1130926006121.972.0326.3727562936
    5539196006121.972.0326.3727562936
    5539136006121.972.0326.3727562936
    5539206006121.972.0326.3727562936
    5539216006121.972.0326.3727562936
    5539166006121.972.0326.3727562936
    5539146006121.972.0326.3727562936
    5539307506124.592.0328.9634453645
    1131007506124.592.0328.9634453645
    5539317506124.592.0328.9634453645
    5539267506124.592.0328.9634453645
    5539327506124.592.0328.9634453645
    5539347506124.592.0328.9634453645
    5539297506124.592.0328.9634453645
    5539277506124.592.0328.9634453645
    11313410006128.372.0332.7445944822
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CInductive Reactance @ 60HzAllowable Ampacity In Raceway 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmΩ/kmAmp
    825.405872.14242.580.170655
    825.405872.14242.580.170655
    825.405872.14242.580.170655
    825.405872.14242.580.170655
    825.405872.14242.580.170655
    825.405872.14242.580.170655
    825.405872.14242.580.170655
    825.405872.14242.580.170655
    825.405872.14242.580.170655
    627.949301.34841.620.167375
    627.949301.34841.620.167375
    627.949301.34841.620.167375
    627.949301.34841.620.167375
    627.949301.34841.620.167375
    627.949301.34841.620.167375
    627.949301.34841.620.167375
    627.949301.34841.620.167375
    627.949301.34841.620.167375
    433.0214820.84651.020.157595
    433.0214820.84651.020.157595
    433.0214820.84651.020.157595
    433.0214820.84651.020.157595
    433.0214820.84651.020.157595
    433.0214820.84651.020.157595
    433.0214820.84651.020.157595
    433.0214820.84651.020.157595
    335.5618690.67260.810.1542115
    335.5618690.67260.810.1542115
    238.1023590.53150.640.1476130
    238.1023590.53150.640.1476130
    238.1023590.53150.640.1476130
    238.1023590.53150.640.1476130
    238.1023590.53150.640.1476130
    238.1023590.53150.640.1476130
    238.1023590.53150.640.1476130
    238.1023590.53150.640.1476130
    238.1023590.53150.640.1476130
    143.1829770.41990.510.1509145
    143.1829770.41990.510.1509145
    143.1829770.41990.510.1509145
    143.1829770.41990.510.1509145
    143.1829770.41990.510.1509145
    143.1829770.41990.510.1509145
    143.1829770.41990.510.1509145
    143.1829770.41990.510.1509145
    143.1829770.41990.510.1509145
    1/048.2637560.33460.400.1444170
    1/048.2637560.33460.400.1444170
    1/048.2637560.33460.400.1444170
    1/048.2637560.33460.400.1444170
    1/048.2637560.33460.400.1444170
    1/048.2637560.33460.400.1444170
    1/048.2637560.33460.400.1444170
    1/048.2637560.33460.400.1444170
    1/048.2637560.33460.400.1444170
    2/053.3447350.26570.320.1411195
    2/053.3447350.26570.320.1411195
    2/053.3447350.26570.320.1411195
    2/053.3447350.26570.320.1411195
    2/053.3447350.26570.320.1411195
    2/053.3447350.26570.320.1411195
    2/053.3447350.26570.320.1411195
    2/053.3447350.26570.320.1411195
    2/053.3447350.26570.320.1411195
    3/058.4259720.21000.260.1378225
    3/058.4259720.21000.260.1378225
    3/058.4259720.21000.260.1378225
    3/058.4259720.21000.260.1378225
    3/058.4259720.21000.260.1378225
    3/058.4259720.21000.260.1378225
    3/058.4259720.21000.260.1378225
    3/058.4259720.21000.260.1378225
    3/058.4259720.21000.260.1378225
    4/063.5075290.16730.200.1345260
    4/063.5075290.16730.200.1345260
    4/063.5075290.16730.200.1345260
    4/063.5075290.16730.200.1345260
    4/063.5075290.16730.200.1345260
    4/063.5075290.16730.200.1345260
    4/063.5075290.16730.200.1345260
    4/063.5075290.16730.200.1345260
    4/063.5075290.16730.200.1345260
    25071.1289000.14110.170.1345290
    25071.1289000.14110.170.1345290
    25071.1289000.14110.170.1345290
    25071.1289000.14110.170.1345290
    25071.1289000.14110.170.1345290
    25071.1289000.14110.170.1345290
    25071.1289000.14110.170.1345290
    25071.1289000.14110.170.1345290
    25071.1289000.14110.170.1345290
    30076.20106800.11810.150.1345320
    30076.20106800.11810.150.1345320
    30076.20106800.11810.150.1345320
    30076.20106800.11810.150.1345320
    30076.20106800.11810.150.1345320
    35081.28124600.10170.130.1312350
    35081.28124600.10170.130.1312350
    35081.28124600.10170.130.1312350
    35081.28124600.10170.130.1312350
    35081.28124600.10170.130.1312350
    35081.28124600.10170.130.1312350
    35081.28124600.10170.130.1312350
    35081.28124600.10170.130.1312350
    35081.28124600.10170.130.1312350
    40086.36142400.08860.110.1312380
    40086.36142400.08860.110.1312380
    40086.36142400.08860.110.1312380
    40086.36142400.08860.110.1312380
    40086.36142400.08860.110.1312380
    40086.36142400.08860.110.1312380
    40086.36142400.08860.110.1312380
    40086.36142400.08860.110.1312380
    40086.36142400.08860.110.1312380
    50091.44178000.07220.100.1280430
    50091.44178000.07220.100.1280430
    50091.44178000.07220.100.1280430
    50091.44178000.07220.100.1280430
    50091.44178000.07220.100.1280430
    50091.44178000.07220.100.1280430
    50091.44178000.07220.100.1280430
    50091.44178000.07220.100.1280430
    50091.44178000.07220.100.1280430
    600132.08213600.05910.080.1280475
    600132.08213600.05910.080.1280475
    600132.08213600.05910.080.1280475
    600132.08213600.05910.080.1280475
    600132.08213600.05910.080.1280475
    600132.08213600.05910.080.1280475
    600132.08213600.05910.080.1280475
    600132.08213600.05910.080.1280475
    600132.08213600.05910.080.1280475
    750144.78267000.04590.070.1247535
    750144.78267000.04590.070.1247535
    750144.78267000.04590.070.1247535
    750144.78267000.04590.070.1247535
    750144.78267000.04590.070.1247535
    750144.78267000.04590.070.1247535
    750144.78267000.04590.070.1247535
    750144.78267000.04590.070.1247535
    1000162.56356000.03610.060.1214615
    *Ampacities based upon 2023 NEC Table 310.16 Raceway or Cable, Not more than 3 copper conductors on an ambient temperature of 30°C.
    *Ampacities derived from the 2021 Canadian Electrical Code. - Table 2 - for Raceway or Cable. Not more than 3 copper conductors on an ambient temperature of 30°C.
    * Inductive Reactance is based on non-ferrous conduit with one diameter spacing.

    Stock Code Colors and Standard Package

    SizePackageBlackRedBlueWhiteBrownOrangeYellowGrayGreen
    US/CanadaBlackRedBlueWhiteBrownOrangeYellowGrayGreen
    8US Reel: 1000'/2500'/5000'
    Spool: 500'
    CAN Reel: 984'/4921'/9842'/246'
    112953952713553059952721553060550361553062553063952739
    6US Reel: 1000'/2500'/5000'
    Spool: 500'
    CAN Reel: 984'/4921'/492'/246'
    112961952705959916678607683383683391553067553068553230
    4US Reel: 1000'/2500'/5000'
    Spool: 500'
    CAN Reel: 984'/4921'
    112979952697553846678599553847553848553849553850558627
    3US Reel: 1000'
    Spool: 500'
    CAN Reel: 984'/4921'/492'/246'
    267278890469
    2US Reel: 1000'/2500'/5000'
    Spool: 500
    CAN Reel: 984'/4921'/492'/1969'
    112987218115553087218107553088553089553090553091474122
    1US Reel: 1000'/2500'/5000'
    Spool: 500'
    CAN Reel: 984'/4921'
    112995550761550762550808553854553855553856553857550766
    1/0US Reel: 1000'/2500'/5000'
    Spool: 500'
    CAN Reel: 984'/4921'
    113001553860553861553858553863553864553865553866553862
    2/0US Reel: 1000'/2500'/5000'
    Spool: 500'
    CAN Reel: 984'/4921'
    113019553871553872553870553873553874553876553877552070
    3/0US Reel: 1000'/2500'/5000'
    Spool: 500'
    CAN Reel: 984'/4921'/492
    113027553881553882553880553885553886553887553888553884
    4/0US Reel: 1000'/2500'/5000'
    Spool: 500'
    CAN Reel: 984'/4921'
    113035553078553079553077553080553082553083553084552071
    250US Reel: 1000'/2500'/5000'
    Spool: 500'
    CAN Reel: 984'/4921'
    113043553893553894553892553896553897553898553899553895
    300US Spool: 500'
    CAN Reel: 984'/4921'
    113050561129561130561131584039
    350US Reel: 1000'/2500'
    CAN Reel: 984'/4921'
    113068553903553904553902553906553907553908553910553905
    400US Reel: 1000'/2500'
    Spool: 500'
    CAN Reel: 984'/4921'
    113076561701561702561132561111561112561113561703558666
    500US Reel: 1000'/2500'
    Spool: 500'
    CAN Reel: 984'/2952'/4921'
    113084550369550261553071550260550262550259553074553072
    600US Reel: 1000'/2500'
    Spool: 500'
    CAN Reel: 984'/2952'/1969'
    113092553914553915553913553918553919553920553921553916
    700N/A586272
    750US Reel: 2500'
    CAN Reel: 984'/2500'
    113100553927553930553926553930553931553932553934553929
    1000US N/A
    CAN Reel: 984'/1969'
    113134

    Revision: 1.000.111

    Updated On: Aug. 27, 2024, 9:39 a.m. UTC