SPEC 10015

Aluminum AlumaFlex® SIMpull XHHW-2®/RW90

Power Cable 600 or 1000 Volts. Alumaflex® Brand Aluminum Alloy (AA-8176) Conductor. Cross-linked Polyethylene (XLPE) Insulation. Moisture Resistant High Heat.

...

Construction:

  1. Conductor:Class B compact stranded bare aluminum per ASTM B800 and ASTM B801
  2. Insulation:Heat and moisture resistant cross-linked polyethylene (XLPE) insulation in various colors

Applications and Features:

Southwire SIMpull XHHW-2®/RW90 Aluminum Wire & Cable with Alumaflex® Brand conductors are primarily used in conduit and cable trays for services, feeders and branch circuits in commercial or industrial applications as specified in the National Electrical Code. XHHW-2/RW90 conductors is suitable for use in dry locations at temperatures not to exceed 90°C. Voltage for all applications is up to 1000 volts. Suitable for use in Health Care Facilities per section 517.160 of the NEC where a dielectric constant of 3.5 or less may be specified. This cable can be installed without application of pulling lubricant. RW90 is for open wiring and use in raceways (except cabletroughs and ventilated flexible cableways) in dry or wet locations as per Canadian Electrical Code. For open wiring exposed to the weather.

Southwire Aluminum SIMpull XHHW-2®/RW90 conductors comply with the following:
  • Federal Specification AA-59544
  • NOM-ANCE, XHHW-2, 90ºC
  • CT Rated - Sizes 1/0 AWG and larger
  • FT4 - 350 Kcmil and larger
  • National Electrical Code
  • Gas and Oil Resistant II - All sizes
  • Sunlight Resistant - Sizes 6 AWG and larger
  • RoHS/Reach Compliant
  • Specifications:

  • ASTM B800 8000 Series Aluminum Alloy Wire
  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • CSA C22.2 No. 38 Thermoset-insulated wires and cables
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • NMX-J-451-ANCE Thermoset insulated wires and cables
  • NOM-063-SCFI Electrical Products – Conductors – Safety Requirements
  • Sample Print Legend:

    6 AWG thru 1 AWG
    {SQFTG} SOUTHWIRE{R} {NOLUBE}{R} {SIMPULL}{R} {ALUMAFLEX}{R} E30117 {UL} TYPE XHHW-2 6 AWG (13.3{MM2}) AL AA8176 600V/1000V SR GRII PRII - LL90458 {CSA} RW90 XLPE 6 AWG (13.3{mm2}) AL AA8176 600V GRI PRI -40{D}C SR FT1 - {NOM}-ANCE LS - PAT WWW.PATENTSW.COM

    1/0 AWG thru 300 kcmil
    {SQFTG} SOUTHWIRE{R} {NOLUBE}{R} {SIMPULL}{R} {ALUMAFLEX}{R} E30117 {UL} TYPE XHHW-2 1/0 AWG (53.5{MM2}) AL AA8176 600V/1000V SR FOR CT USE GRII PRII - LL90458 {CSA} RW90 XLPE 1/0 AWG (53.5{mm2}) AL AA8176 600V GRI PRI -40{D}C SR FT1 - {NOM}-ANCE LS - PAT WWW.PATENTSW.COM

    350 kcmil and Larger
    {SQFTG} SOUTHWIRE{R} {NOLUBE}{R} {SIMPULL}{R} {ALUMAFLEX}{R} E30117 {UL} TYPE XHHW-2 350 KCMIL (177{MM2}) AL AA8176 600V/1000V SR FOR CT USE GRII PRII FT4 - LL90458 {CSA} RW90 XLPE 350 KCMIL (177{mm2}) AL AA8176 600V GRI PRI -40{D}C SR FT4 - {NOM}-ANCE LS - PAT WWW.PATENTSW.COM
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandDiameter Over ConductorInsul. ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.inchmilinchlb/1000ft
    593379400350.659650.797454
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CInductive Reactance @ 60HzAllowable Ampacity In Raceway 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmp
    4003.224000.0440.0540.040305
    *Ampacities based upon 2023 NEC Table 310.16 Raceway or Cable, Not more than 3 copper conductors on an ambient temperature of 30°C.
    *Ampacities derived from the 2021 Canadian Electrical Code. - Table 4 - for Raceway or Cable. Not more than 3 aluminum conductors on an ambient temperature of 30°C.
    * Inductive Reactance is based on non-ferrous conduit with one diameter spacing.
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandDiameter Over ConductorInsul. ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.mmmmmmkg/km
    5933794003516.741.6520.24676
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CInductive Reactance @ 60HzAllowable Ampacity In Raceway 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmΩ/kmAmp
    40081.28106800.14440.180.1312305
    *Ampacities based upon 2023 NEC Table 310.16 Raceway or Cable, Not more than 3 copper conductors on an ambient temperature of 30°C.
    *Ampacities derived from the 2021 Canadian Electrical Code. - Table 4 - for Raceway or Cable. Not more than 3 aluminum conductors on an ambient temperature of 30°C.
    * Inductive Reactance is based on non-ferrous conduit with one diameter spacing.

    Stock Code Colors and Standard Package

    SizePackageBlackBrownOrangeYellowGrayWhiteRedBlueGreen
    US/Canada
    Black
    Brown
    Orange
    Yellow
    Gray
    White
    Red
    Blue
    Green
    6US Reel: 2500'/1000'/5000'
    CAN Reel: 984'/4921'/9842'
    112706591209591210591211585321
    4US Reel: 2500'/1000'/5000'
    CAN Reel: 984'/4921'/9842'
    112714591201591202591203591116591114591115585320
    2US Reel: 2500'/1000'/5000'
    CAN Reel: 984'/4921'/9842'/492'
    112722591213591214591215585319
    1US Reel: 2500'/1000'
    CAN Reel: 984'/4921'
    112730591207591208591216596497591206591204591205585318
    1/0US Reel: 500'/2500'/1000'
    CAN Reel: 984'/4921'
    112748585291585292585293585294591286591284591285585290
    2/0US Reel: 500'/2500'/1000'/5000'
    CAN Reel: 984'/4921'
    112755585296585297585298585300591290591288591289585295
    3/0US Reel: 2500'/1000'/5000'
    CAN Reel: 984'/4921'
    112763585305585306585308585309585304585302585303585301
    4/0US Reel: 500'/2500'/1000'/5000'
    CAN Reel: 984'/4921'/246'
    112771585313585312585311585310585314585317585316567439
    250US Reel: 2500'/1000'/5000'
    CAN Reel: 984'/4921
    278341576385576386576387576388576392576390576391567440
    300US Reel: 2500'/1000'
    CAN Reel: 984'/4921'
    278358576133576134576135576136576384576382576383576361
    350US Reel: 2500'/1000'/5000'
    Reel: 984'/4921'
    278366576374576375576376576377576380576378576379567437
    400US Reel: 1000'/5000'
    CAN Reel: 984'/4921'
    278374576127576129576130576131576373576370576372567384
    500US Reel: 500'/2500'/1000'/5000'
    CAN Reel: 984'/2952'/4921'
    278382576362576364576365576366576369576367576368576394
    600US Reel: 500'/2500'/5000'
    CAN Reel: 984'/2952'
    278390576345576346576347576349576352576350576351567375
    700N/A278408576341576342576343576344591295591293591294591296
    750US Reel: 500'/2500'/1000'
    CAN Reel: 984'/2952'/4921'
    278416567432567433567434567435592235592233592234567436
    900N/A554059560445560446560447560448
    1000US Reel: 1000'
    CAN Reel: 984'/1969'
    278424

    Revision: 1.000.076

    Updated On: July 3, 2024, 10:12 p.m. UTC