SPEC 60100

Armorlite® Type MC THHN/THWN Circuit Size Copper Conductor 120/208V Colors

Copper THHN/THWN Insulated Singles. Green Insulated Copper Grounding Conductor. UL Listed. 600 Volts Rated VW-1. Lightweight Aluminum Interlocked Armor.

...

Construction:

  1. Conductor:Solid or 19 strands class C compressed copper per ASTM B3 and ASTM B8
  2. Insulation:All phases are insulated with Polyvinyl Chloride with Nylon Sheath Type THHN/THWN
  3. Ground:Green insulated ground. Polyvinyl Chloride with Nylon Sheath Type THHN/THWN
  4. Binder:Mylar tape with print legend wrapped around assembly.
  5. Armor:Aluminum Interlocked Armor

Applications and Features:

Southwire Armorlite® Type MC Cable is suitable for use as follows:
- Branch and service power distribution in commercial, industrial, institutional, and multi-residential buildings.
- Fished or embedded in plaster.
- Concealed or exposed installations.
- Environmental air-handling spaces per NEC 300.22 (C).
- Places of Assembly per NEC 518.4 and theaters per NEC 520.5.
- Installation in cable tray and approved raceways.
- Under raised floors for information technology equipment conductors and cables per NEC Article 645
- Class I Div. 2, Class II Div 2, & Class III Div. 1 Hazardous Locations.
- Binder tape with print legend wrapped around assembly.
- Type THHN/THWN rated 90ºC Dry.
- Anti-Short bushing not required

Southwire Armorlite® Type MC Cable - meets or exceeds the following requirements:
- UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com )
- Federal Specification A-A59544 (formerly J-C-30B)
- NFPA 70 (National Electrical Code), Article 330
- Listed for use in UL 1, 2 and 3 Hour Through Penetration Firestop Systems

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 1569 Metal-Clad Cables
  • UL 1479 Standard for Safety Fire Tests of Penetration Firestops
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • RoHS-2 (European Directive 2011/65/EU)
  • Buy American: Compliant with Buy American Requirements, found in 49 U.S.C. § 5323(j); specify “Made in the USA Only!” when ordering to ensure your project receives American made products.
  • VW-1 (Vertical-Wire) Flame Test
  • Sample Print Legend:

    SOUTHWIRE E96627 {UL} TYPE MC XX AWG THHN OR THWN CDRS FOR USE IN CABLE TRAYS 600 VOLTS
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeConductor NumberColorDiameter Over ConductorConductor StrandingInsulation ThicknessGround SizeDiameter Over ArmorCopper WeightOverall Weight
    AWG/KcmilinchmilsNo. x AWGinchlbs/1000ftlbs/1000ft
    14 AWG | Solid
    551394142RD,WE,GN0.064Solid201x140.4423779
    553208142BE,WE,GN0.064Solid201x140.4423779
    685792142BK,WE0.064Solid201x140.4513779
    685826143BK,RD,WE0.064Solid201x140.4785097
    687186144BK,RD,BE,WE0.064Solid201x140.50862116
    12 AWG | Solid
    580367122BE,WE/BE,GN0.08Solid201x120.47459105
    590615122BE,WE/BE,GN0.08Solid201x120.47459105
    593377122BK,RD0.08Solid201x120.4445999
    553200122BK,RD,GN0.08Solid201x120.47559107
    590611122BK,WE/BK,GN0.08Solid201x120.47459105
    553213122BE,WE,GN0.08Solid201x120.47559105
    590118122BK,YW,GN0.08Solid201x120.47459105
    553199122RD,BE,GN0.08Solid201x120.47559105
    592484122RD,WE0.08Solid201x120.4445999
    553212122RD,WE,GN0.08Solid201x120.47559105
    590613122RD,WE/RD,GN0.08Solid201x120.47459105
    555145122BE,BK,GN0.08Solid201x120.47559105
    580369123BK,PE,WE,GN0.08Solid201x120.50579131
    553770123BK,BE,WE,GN0.08Solid201x120.50679131
    553025123BE,RD,WE,GN0.08Solid201x120.50679131
    599038123BE,PK,WE,GN0.08Solid201x120.50579131
    677407124RD,PE,PE,WE,GN0.08Solid201x120.5499159
    580364124BK,RD,PE,WE,GN0.08Solid201x120.5499159
    689521122RD,WE0.080Solid201x120.48359105
    689489122BE,WE0.080Solid201x120.48359105
    685800122BK,WE0.080Solid201x120.48359107
    610971123RD,BE,WE0.080Solid201x120.51479132
    610973123BK,BE,WE0.080Solid201x120.51479132
    685834123BK,RD,WE0.080Solid201x120.51479132
    550172124BK,WE,RD,WE/BK0.080Solid201x120.54999159
    687194124BK,RD,BE,WE0.080Solid201x120.54999159
    12 AWG | 19 Strands
    587581122BE,RD,GN0.08819201x120.49560109
    551256122BE,WE,GN0.08819201x120.49660109
    576315122BK,WE0.08819201x120.5860115
    576623122BK,WE0.08819201x120.4760102
    576110122BK,WE,GN0.08819201x120.5860135
    552318122RD,WE,GN0.08819201x120.49660109
    551264123BK,WE,BE,GN0.08819201x120.5380137
    576542123BK,RD,WE0.08819201x120.52580132
    551262123BE,RD,WE,GN0.08819201x120.5380137
    576114123BK,RD,WE0.08819201x120.5880138
    576498124BK,RD,WE,BE0.08819201x120.58100164
    10 AWG | Solid
    610520102PE,GY0.101Solid251x100.55092151
    583662102BK,RD0.101Solid251x100.50492140
    610518102BE,WE0.101Solid251x100.55092151
    685818102BK,WE0.101Solid251x100.55092151
    610521102RD,WE0.101Solid251x100.55092151
    555943102BE,WE,GN0.101Solid251x100.54292150
    552973102BK,BE,GN0.101Solid251x100.54192150
    554407102BK,RD,GN0.101Solid251x100.54192150
    552981102RD,BE,GN0.101Solid251x100.54192150
    555941102RD,WE,GN0.101Solid251x100.54292150
    551171103BE,RD,WE,GN0.101Solid251x100.58123191
    553026103BE,RD,WE,GN0.101Solid251x100.58123191
    563382103BK,BE,WE,GN0.101Solid251x100.58123191
    611650103BK,RD,BE,GN0.101Solid251x100.58123191
    551170103BK,WE,BE,GN0.101Solid251x100.58123191
    685842103BK,RD,WE0.101Solid251x100.589123192
    553023104BK,WE,RD,BE,GN0.101Solid251x100.625154232
    687202104BK,RD,BE,WE0.101Solid251x100.633154232
    10 AWG | 19 Strands
    563492102BK,RD,GN0.11319251x100.57497162
    551270102BE,WE,GN0.11319251x100.57497162
    576316102BK,WE0.11319251x100.6695161
    551272102RD,WE,GN0.11319251x100.57497162
    556403103RD,BE,WE,GN0.11319251x100.617129205
    590715103BK,RD,BE,GN0.11319251x100.617129206
    576333103BK,RD,WE0.11319251x100.66127202
    14 AWG | 19 Strands
    550177142BK,WE0.07319201x140.4683883
    550180143BK,RD,WE0.07319201x140.49751102
    12 AWG | 19 Strands
    691147122BK,WE0.09019201x120.50460110
    691154123BK,RD,WE0.09019201x120.53880138
    691162124BK,RD,BE,WE0.09019201x120.576100167
    10 AWG | 19 Strands
    691170102BK,WE0.11719251x100.58397163
    691188103BK,RD,BE0.11719251x100.626129206
    691196104BK,RD,BE,WE0.11719251x100.674161251
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Note: Conductor number = number of phase conductors plus neutral. Does not include green ground.
    Table 2 – Electrical and Engineering Data
    Cond. SizeConductor NumberMin. Bend RadiusDC Resistance at 25°CAC Resistance at 75°CInductive Reactance @ 60HzAllowable Ampacity Raceway 75°CAllowable Ampacity Raceway 90°C
    AWG/KcmilInchesΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    14 AWG | Solid
    1423.12.6313.170.0582025
    1423.12.6313.170.0582025
    1423.22.6313.1700.0582025
    1433.32.6313.1700.0582025
    1443.62.6313.1700.0581620
    12 AWG | Solid
    1223.31.6622.0020.0542530
    1223.31.6622.0020.0542530
    1223.11.6622.0020.0542530
    1223.31.6622.0020.0542530
    1223.31.6622.0020.0542530
    1223.31.6622.0020.0542530
    1223.31.6622.0020.0542530
    1223.31.6622.0020.0542530
    1223.11.6622.0020.0542530
    1223.31.6622.0020.0542530
    1223.31.6622.0020.0542530
    1223.31.6622.0020.0542530
    1233.51.6622.0020.0542524
    1233.51.6622.0020.0542524
    1233.51.6622.0020.0542524
    1233.51.6622.0020.0542524
    1243.81.6622.0020.0542024
    1243.81.6622.0020.0542024
    1223.41.6622.0020.0542530
    1223.41.6622.0020.0542530
    1223.41.6622.0020.0542530
    1233.61.6622.0020.0542530
    1233.61.6622.0020.0542530
    1233.61.6622.0020.0542530
    1243.81.6622.0020.0542024
    1243.81.6622.0020.0542024
    12 AWG | 19 Strands
    1223.51.6622.0020.0542530
    1223.51.6622.0020.0542530
    1224.11.6622.0020.0542530
    1223.31.6622.0020.0542530
    1224.11.6622.0020.0542530
    1223.51.6622.0020.0542530
    1233.71.6622.0020.0542524
    1233.71.6622.0020.0542524
    1233.71.6622.0020.0542524
    1234.11.6622.0020.0542524
    1244.11.6622.0020.0542024
    10 AWG | Solid
    1023.91.0401.2530.0503540
    1023.51.041.2530.053540
    1023.91.0401.2530.0503540
    1023.91.0401.2530.0503540
    1023.91.0401.2530.0503540
    1023.81.041.2530.053540
    1023.81.041.2530.053540
    1023.81.041.2530.053540
    1023.81.041.2530.053540
    1023.81.041.2530.053540
    1034.11.041.2530.053532
    1034.11.041.2530.053532
    1034.11.041.2530.053532
    1034.11.041.2530.053540
    1034.11.041.2530.053532
    1034.11.0401.2530.0503540
    1044.41.041.2530.052832
    1044.41.0401.2530.0502832
    10 AWG | 19 Strands
    10241.041.2530.053540
    10241.041.2530.053540
    1024.61.041.2530.053540
    10241.041.2530.053540
    1034.31.041.2530.053532
    1034.31.041.2530.053540
    1034.61.041.2530.053532
    14 AWG | 19 Strands
    1423.32.6313.1700.0582025
    1433.52.6313.1700.0582025
    12 AWG | 19 Strands
    1223.51.6622.0020.0542530
    1233.81.6622.0020.0542530
    1244.01.6622.0020.0542024
    10 AWG | 19 Strands
    1024.11.0401.2530.0503540
    1034.41.0401.2530.0503540
    1044.71.0401.2530.0502832
    * Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
    * Ampacities have been adjusted for more than Three Current-Carrying Conductors.

    Revision: 1.000.006

    Updated On: June 24, 2025, 3:24 p.m. UTC