SPEC 84025

3-Layer 25kV AAAC CAMV™ Covered Conductor (Tree Wire or Spacer Cable)

An Alternative and Robust Design to Bare AAAC Conductors to Harden the Electrical Grid.
3-Layer, 25kV, Covered Conductor, Concentrically Stranded AAAC, Track-Resistant Crosslinked Polyethylene.

...

Construction:

  1. Conductor:Concentrically stranded, aluminum-alloy 6201-T81 wires, AAAC
  2. Strand Shield:Semi-conducting cross linked polymer
  3. Inner Layer:Low-Density Crosslinked Polyethylene (LDXLPE)
  4. Outer Layer:High-Density Track-Resistant Crosslinked Polyethylene (HDTRXLPE)

Applications and Features:

  • Used for primary and secondary overhead distribution where limited space is available or desired for rights-of-way. Installed the same as bare conductors, however, covering is effective in preventing direct shorts and instantaneous flashovers should tree limbs or other objects contact conductors in such close proximity.
  • Tree Wire - Used for spans where trees crowd the right-of-way, such as in wooded residential areas, when a minimum of interference with the environment is desired. Covering minimizes power outages due to conductor contact with tree limbs, reducing the need for frequent or severe trimming.
  • Covered Aerial MV Cable (CAMV)/Spacer Cable - Installed with other Covered Aerial MV cables and a supporting messenger through a series of space-maintaining devices (spacers). The resulting close-proximity configuration minimizes the amount of space and hardware required for line installation, particularly useful in congested areas.
  • Covering Rated 90°C Normal and 130°C Emergency Operation. Unless adequate knowledge of the thermal characteristics of the environment is known, the permissible conductor temperature should be reduced by 10°C or in accordance with available data.
  • Specifications:

  • ASTM B398 Standard Specification for Aluminum-Alloy 6201-T81 and 6201-T83 Wire for Electrical Purposes
  • ASTM B400 Standard Specification for Compact Round Concentric-Lay-Stranded, Aluminum 1350 Conductors
  • ICEA S-121-733 Tree Wire and Messenger Supported Spacer Cable
  • Table 1 – Weights and Measurements
    Cond. SizeCond. StrandsDiameter Over ConductorConductor Shield ThicknessInner Layer ThicknessOuter Layer ThicknessApprox. ODApprox. WeightRated Strength
    AWG/Kcmil#inchmilmilmilinchlb/1000ftlb
    48.6970.250151251250.7802251584
    77.4770.316151251250.8462752520
    123.370.398151251250.9283484014
    155.470.447151251250.9773964851
    195.770.502151251251.0324546111
    246.970.563151251251.0935257704
    All dimensions are nominal and subject to normal manufacturing tolerances
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

    Revision: 1.000.003

    Updated On: Oct. 9, 2025, 2:08 p.m. UTC