SPEC 85003

Re3™ Rodent-Resistant Power & Control Cables- CU 600V FR-XLPE LCT Shielded LSZH Jacket for Substations

Single Conductor, 600 Volt, Copper Conductors, Cross Linked Polyethylene and Thermoplastic Low Smoke Zero Halogen Jacket (XLPE/LSZH). Silicone Free

...

Construction:

  1. Conductor:Class B, compressed, stranded bare copper per ASTM B3 and B8
  2. Insulation:Cross Linked Polyethylene (XLPE)
  3. Shield:5 mil annealed Longitudinally-Corrugated Copper Tape (LCT)
  4. Rip Cord:Rip cord for ease of jacket removal
  5. Jacket:Black, moisture and sunlight resistant, Thermoplastic, Polyolefin, Low Smoke Zero Halogen (LSZH)

Applications and Features:

Southwire's single conductor shielded control cable is used primarily in utility generating plants and substations. Can be installed indoors or outdoors. Conductor operating temperature is 90°C, 130°C for emergency overload, and 250°C for short circuit conditions. The double-shielding design prevents wildlife attacks on cables, including but not limited to rats, moles, squirrels, gophers, and termites. Copper is a natural animal deterrent and protects the dielectric insulated phase conductors from chewing damage. The extra layers of copper material also mitigate EMI/EMF due to interferences from the high voltage or extra high voltage equipment at the transmission or distribution substations. This shielded single conductor can be deployed at any utility’s critical infrastructure projects.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • Sample Print Legend:

    {SQFTG} SOUTHWIRE XX AWG 1/C FR-XLPE CDR 90°C LSZH JACKET SUNLIGHT RESISTANT 600V {MMM/DD/YYYY}
    Table 1 – Weights and Measurements
    Cond. SizeStrand CountDiameter Over ConductorInsul. ThicknessDiameter Over InsulationJacket ThicknessApprox. ODCopper WeightApprox. WeightJacket Color
    AWG/KcmilNo. of Strandsinchmilinchmilinchlb/1000ftlb/1000ft
    670.178450.268300.2688199BK
    470.225450.315300.315129151BK
    1/0190.362550.472450.472326367BK
    2/0190.405550.515450.515411456BK
    4/0190.512550.622450.622653708BK
    250370.558650.688650.688772844BK
    500370.789650.919650.91915441642BK
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity At 75°CAllowable Ampacity At 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    63.22090.4110.510.0516575
    43.83330.2580.320.0488595
    1/05.78440.1020.1270.044150170
    2/06.210640.0820.1020.043175195
    4/07.516920.0510.0630.041230260
    2508.320000.0430.0530.041255290
    5001140000.0210.0270.039380430
    * Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.

    Revision: 1.000.011

    Updated On: March 20, 2026, 3:39 p.m. UTC