SPEC 84029
3-Layer 25kV AAC CAMV™ Covered Conductor (Tree Wire or Spacer Cable)
An Alternative and Robust Design to Bare AAC Conductors to Harden the Electrical Grid.
3-Layer, 25kV, Covered Conductor, Concentrically Stranded AAC, Track-Resistant Crosslinked Polyethylene.

Construction:
- Conductor:Concentrically stranded AAC
- Strand Shield:Semi-conducting cross linked polymer
- Inner Layer:Low-Density Crosslinked Polyethylene (LDXLPE)
- Outer Layer:High-Density Track-Resistant Crosslinked Polyethylene (HDTRXLPE)
Applications and Features:
Specifications:
Table 1 – Weights and Measurements
Cond. Size | Cond. Strands | Diameter Over Conductor | Conductor Shield Thickness | Inner Layer Thickness | Outer Layer Thickness | Approx. OD | Approx. Weight | Rated Strength |
---|---|---|---|---|---|---|---|---|
AWG/Kcmil | # | inch | mil | mil | mil | inch | lb/1000ft | lb |
1/0 | 7 | 0.336 | 15 | 125 | 125 | 0.866 | 309 | 1791 |
2/0 | 7 | 0.376 | 15 | 125 | 125 | 0.906 | 350 | 2259 |
3/0 | 7 | 0.423 | 15 | 125 | 125 | 0.953 | 400 | 2736 |
4/0 | 7 | 0.475 | 15 | 125 | 125 | 1.005 | 460 | 3447 |
266.8 | 19 | 0.537 | 15 | 125 | 125 | 1.067 | 531 | 4473 |
All dimensions are nominal and subject to normal manufacturing tolerances